| 1 | Supply and Installation, Testing, Commissioning of 500KVA (3 Nos.) D.G. Set Work at Government Medical College, Kannaur (U.P.) |
| 2 | Supply of 500 KVA, CPCB IV+ compliant Three Phase, Prime duty Silent DG Set six Cylinder Liquid cooled comprising of Engine developing Minimum 594 BHP Electronic Fuel system and 500 KVA, 415 V, 50HZ, PF 0.8,voltage Regulation ±0.5% tested on 50 Degree C ambient Stamford make alternator mounted on a common base, complete with Fuel tank Minimum 760 Lts. Batteries and leads, Acoustic Enclosure, First fill of lube oil, Performance class ISO 8528-5 G2,H Class Insulation,Hospital Grade silence with Exhaust Treatment system as per CPCB 4 Compliant inside the canopy to meet Stringent emission standard Electronic Governing, Remote start stop, 4G compatible, Alert & warning, Isolated RS485G, Mod Bus interface (RS 485G RTU ), External Fuel Filling arrangement, 11 Pre Treatment process, DEF tank Provided with inlet and outlet connections |
| 3 | Supply of 500 KVA AMF Panel for each set & Synchronize panel common for all (one unit) |
| 4 | Supply & Erection of factory fabricated & wired metal clad dust and vermin proof floor mounting, M.S. Channel Base with bottom and top cable entries Electrical control panel with TPN ACB(65 KA,4Pole Elect. draw out, Micro Processor Release IPR2) and TPN MCCB's (Four Pole 36 KA with thermal magnatic release) Switches and instrument chamber etc.complete in all respects. The instrument chamber shall be separate and shall comprise of flush type/digital ammeter Voltmeter, Selector switches for ammeter and Voltmeter, instrument fuses, current transformer etc. The Board shall have suitable capacity electrolytic aluminium busbars as per IS8623 insulated with heat shrink sleeving and mounted on non hygroscopic supports such as CMC/ DMC support with detachable side covers and shall be suitable for extension on the sides. The switches entry boxes shall be complete with suitable cable end boxes reverse. The Job includes the grouting of the board as per directions of Engineer-in charge. All out goings of 100 Amp and above Will be provided with Amp Metie, current transformers and selector switches etc and instrument fuse. The switch board shall be fabricated with CRCA sheet with a minimum thickness of 1.6 mm/2mm. Cubicle type switch board shall be of cat A & B OnlyIncoming630 Amp /415Volt ACB-1 NoOUTGOING100 Amp.MCCB-5 Nos., & 63 Amp.MCCB-INOCat, B Pannel Cubicle Type |
| 5 | S/F and laying of HDPE pipes (upto Pn 6kg pressure Rating material Grade PE 80, Nominal Dia (OD) 160mm 9.1mm thicknes with cable below ground upto 1.50m to 2.00m By Drilling machine Complete in all respect as per relevants IS Technical Specification. |
| 6 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.400 Sqmm 3.5 core |
| 7 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer- Incharge.400 Sqmm |
| 8 | Supply and fixing of plain or pin type copper tin plated cable socket (lug) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge.(i) 240 Sqmm |
| 9 | (ii) 400 Sqmm |
| 10 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 11 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 12 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. |
| 13 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) (Base Concrete) |
| 14 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 15 | Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: With Chlorpyriphos/Lindane E.C. 20% with 1% concentration |
| 16 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size) (Plinth Band) |
| 17 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 18 | Brick work with common burnt clay F.P.S. (non modular) bricks of class-150 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 19 | 20mm Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement. |
| 20 | 62 mm thick cement concrete flooring with concrete hardener topping, under layer 50 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate, 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacture’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 21 | GST Extra as per applicable Please Enable Macros to View BoQ information |