| 1 | General Notes:a) All supply items shall be quoted as per technical specification & BoQ description for supply to site including charges towards TPI, packing & forwarding, loading, transportation, transit insurance, unloading, stacking at site.b) Third party inspection (TPI) for the supply items shall be in scope of successfull bidder. c) Approval of TPI agency to be engaged for inspection of material shall be obtained from IOCL on award of contract to sucessfull Bidder..d) Clearance of all materials shall be based on compliance to Technical Specifications, approved makes and as per agreed/approved Quality Assurance Plan (QAP) to be submitted by sucessfull bidder after award of contract for approval of IOCL. |
| 2 | PART A - SUPPLY OF ELECTRICAL ITEMS |
| 3 | VCB PANEL |
| 4 | Design, manufacture, assembly, routine testing and supply of 11 kV indoor, metal-clad, metal-enclosed, draw-out type switchgear rated for 12 kV, 630 A, 40 kA for 1 second, comprising two incomer feeders and one bus coupler feeder as per approved SLD, complete with vacuum circuit breakers, aluminium busbars, current transformers and potential transformers, numerical protection relays, auxiliary and trip relays, metering instruments, indicating lamps, control and selector switches, spring-charged motor operated mechanisms, electrical and mechanical interlocks, space heaters, internal wiring, earthing bus, terminal blocks, shutters, nameplates and all standard accessories and auxiliaries, fully wired, assembled, factory tested and supplied in accordance with the technical specifications, data sheets, applicable IS/IEC standards, complete in all respects. |
| 5 | LV SWITCHBOARDS / DISTRIBUTION PANELS / DISTRIBUTION BOARD/BUSDUCT |
| 6 | Design,supply of sheet steel enclosed, floor mounted, compartmentalised, free standing switch-boards, including transportation from store/yard to site at the place of installation, unpacking, assembly, including mounting and wiring of loose parts supplied by equipment vendor, interconnection of shipping sections and requisite inter-panel wiring between shipping sections, including supply of foundation base material frame including supply of GI bolts, nuts and washers etc., assembling of shipping sections,connection of inner panel busbars, checking of terminal connection for tightness and proper wiring, including all labour and materials, as per attached specification of this tender and directions of Engineer-in-Charge. Panel shall be with hinged doors, with neoprene gasket, 2 Nos earth terminal shall be provided at the Panel frame with extension link for earthing connections, with pad locking arrangement & along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders. Incoming & outgoing feeders with ACB/MCCB,CTs/PTs, Relays/ Contactors, meters, space heaters, MFM, selector switches, indication lamps etc.as per applicable SLDs. The Panel will have IP-42 rating degree of protection or otherwise specified in respective item. Colour shade of final paint shall be RAL 7032 or as approved by IOCL.The item is inclusive of the stenciling/ lettering of the LT/HT Panel Boards/Control Panels/LDBs & PDBs/Motors etc. Suitabledouble compression glands to be supplied with all switchboards and panels. |
| 7 | PMCC-01-5000 Amp with Dual Incomer415V PMCC :Supply of CRCA sheet steel enclosed, floor mounted, free standing PMCC Switch Board, 415V, 50 Hz, 3 Ph, 4 Wire, 5000 Amp, 65kA for 1 sec. AL. bus bar including transportation from store/yard to site at the place of installation, unpacking, assembly, including mounting and wiring of loose parts supplied by equipment vendor, interconnection of shipping sections and requisite inter-panel wiring between shipping sections, including installation on foundations or steel structures, aligning, leveling, grouting, testing and calibration of relays and meters etc., including all labour and materials, as per attached specification and Single Line Diagram of this tender and directions of Engineer-in-Charge. (Location: Substation/PMCC) |
| 8 | PMCC-02 -Dual Incomer with 4000 Amp415V PMCC :Supply of double front PMCC panel of rating 4000 Amp (Dual Incomer) CRCA sheet steel enclosed, floor mounted, free standing PMCC Switch Board, 415V, 50 Hz, 3 Ph, 4 Wire, 65 kA for 1 sec. AL. bus bar including transportation from store/yard to site at the place of installation, unpacking,assembly, including mounting and wiring of loose parts supplied by equipment vendor, interconnection of shipping sections and requisite inter-panel wiring between shipping sections, including all labour and materials, as per attached specification and Single Line Diagram of this tender and directions of Engineer-in-Charge. (Location: Substation/PMCC) |
| 9 | Emergency Distribution Board - 1000A with two Incomers415V EDB : Supply of emergency distribution board of rating 1000 Amp (Dual Incomer) CRCA sheet steel enclosed, floor mounted, free standing Emergency Switch Board, 415V, 50 Hz, 3 Ph, 4 Wire, 1000Amp,35 kA for 1 sec.. AL. bus bar including transportation from store/yard to site at the place of installation, unpacking, assembly,including mounting and wiring of loose parts supplied by equipment vendor, interconnection of shipping sections and requisite inter-panel wiring between shipping sections including all labour and materials, as per attached specification and Single Line Diagram of this tender and directions of Engineer-in-Charge. (Location: Substation/PMCC) |
| 10 | AUTOMATIC POWER FACTOR CORRECTION PANEL (APFC PANEL)Supply of CRCA sheet steel enclosed, floor mounted, free standing indoor APFC Panel 415 V,TPN 50 kA for 1.0sec, with detuned filter of 700 kVAR in steps of (3 X 100 kVAR, 2 X 75 kVAR, 2 X 50 kVAR & 2X 20 kVAR. 3 X10kVAR, 5 x 4 kVAR ) with automatic correction of Power Factor. ACBs shall be drawout type with single front type indoor with operating mechanism, all accessories, auxiliaries and all other necessary components for smooth operation including transportation from store/yard to site at the place of installation, unpacking, assembly, including mounting and wiring of loose parts supplied by equipment vendor, including all labour and materials, etc complete in all respects as specified in technical specification,data sheet & SLD of APFC of this tender, and directions of Engineer-in-Charge |
| 11 | POWER DISTRIBUTION BOARD (PDB)-400 Amp415V EDB : Supply of power distribution board of rating 400 Amp (Dual Incomer) CRCA sheet steel enclosed, floor mounted, free standing Emergency Switch Board, 415V, 50 Hz, 3 Ph, 4 Wire, 400Amp,25 kA for 1 sec.. AL. bus bar including transportation from store/yard to site at the place of installation, unpacking, assembly,including mounting and wiring of loose parts supplied by equipment vendor, interconnection of shipping sections and requisite inter-panel wiring between shipping sections, including all labour and materials, as per attached specification and Single Line Diagram of this tender and directions of Engineer-in-Charge. (Location: Substation/PMCC) |
| 12 | MOV-DB for field.Supply of CRCA sheet steel enclosed, floor mounted type MOV-DB ,415V, 50 Hz, 3 Ph, 4 Wire,63 Amp, TPN, 25 kA for 1 sec. AL. bus bar, IP 55,outdoor & weatherproof type, CRCA sheet,distribution board with incomer MCCB including transportation from store/yard to site at the place of installation, unpacking,assembly, including mounting and wiring of loose parts supplied by equipment vendor, including installation on foundations or steel structures, aligning, leveling, grouting, testing and calibration of relays and meters etc., including all labour and materials, as per attached specification and Single Line Diagram of this tender and directions of Engineer-in-Charge.I/C : 63A, 4P MCCB, Outgoing : 30 nos. 16A 4P MPCB. |
| 13 | BUSDUCTSupply of BUS DUCT of 5000A, TPN, Non-segregated, 415V, 50 Hz, 65 kA for 1 sec., TPN, Al Bus Duct, Horizontal bends and Vertical bends with CRCA sheet steel enclosure including necessary equipment connection flanges, wall entrance seals, transformer/ equipment adaptor box, elbows, offsets, wall supports, flexible connectors, phase crossover chamber (if any), inspection cover, supporting insulator,expansion joint, rubber bellow, aluminium flexibles, space heater, all supporting structure, seal of bushing and all other accessories., etc. including storing, transportation from store/yard to site at the place of installation, unpacking, positioning in place, site assembly of loosely furnished accessories, including connection of auxiliary circuits, including fixing of nuts and bolts etc. including all labour and materials, as per attached specificatiions of this tender and directions of Engineer-in-Charge. (Location: Substation) |
| 14 | Design, engineering, manufacture, inspection, testing and supply of 415 V, 3-phase, 50 Hz Variable Frequency Drive (VFD) panel suitable for 200 kW motor, with 50 kA short-circuit withstand capacity for 1 second, complete with inbuilt PLC, power and control components, protections, metering, cooling system, internal wiring and all accessories, manufactured strictly in accordance with the approved SLD, technical specifications, data sheets, applicable IEC/IS standards and tender requirements, complete in all respects, for supply only. |
| 15 | LIGHTING DISTRIBUTION BOARDS |
| 16 | Supply of 415V/240V lighting/power DB, Surface/Recess mounting type sheet steel enclosure of approved make having 4 Pole MCCB/MCB with current limiting 25 kA (LSIG)/RCCB/ELCB as incoming and SP/DP/TP MCB (10kA/16kA type) for out going circuit complete with wiring,indication lamp, ammeter etc including transportation from store/yard to site at the place of installation, unpacking, assembly, including mounting and wiring of loose parts supplied by equipment vendor, testing and calibration of relays and meters etc., all labour and materials as per specification, Single Line Diagram of this tender and the direction of Engineer-in-charge. The Panel will have IP-42 rating for indoor and IP 65 for FLP & IP-55 for outdoor type or otherwise specified in respective item. Colour shade of final paint shall be RAL 7032 or as approved by IOCL. |
| 17 | Main Lighting Distribution Board (MLDB): Supply of CRCA sheet steel enclosed, floor mounted, free standing Lighting Board, 415V, 50 Hz, 3 Ph, 4 Wire, 400 Amp, 25kA for 1 sec. Cu. bus bar, single front, fixed type microprocessor based MCCBs,compartmentalized, Indoor, with Incomers and Outgoing feeders, Metering and protection, MCCBs (LSIG protection),distribution board with incomer,indicating lamps, main contactor & auxiliary contactors etc including transportation from store/yard to site at the place of installation, unpacking, assembly, including mounting and wiring of loose parts supplied by equipment vendor, interconnection of shipping sections and requisite inter-panel wiring between shipping sections, including installation on foundations or steel structures, aligning, leveling, grouting, testing and calibration of relays and meters etc.,including all labour and materials, as per attached specification and Single Line Diagram of MLDB of this tender and directions of Engineer-in-Charge. Panel shall be suitable for bottom cable entry for incoming / outgoing feeders. along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders |
| 18 | Flame Proof Indoor Lighting Distribution Board (ILDB):TLF & PHSupply of 415V, 50 Hz, 3 Ph, 4 Wire, 32 A, 10 kA for 1 sec.Cu busbar, IP-65,Indoor Type, 'Ex-d' type suitable for Zone-2, Gas Group-IIA/ IIB/ IIC, Temperature Class-T3, Aluminium alloy (LM6) enclosure,wall or frame mounted, IP 65, Weatherproof ,Non-compartmentalised, Double door, Lighting Panels along with Flameproof proof double compression Ni plated brass cable glands and lugs suitable for bottom cable entry, incomer and outgoing feeders, with indication lamp, etc complete in all respect as per attached SLD, Specification, Data sheet of this tender.Incomer : 1 No. 32A, 4P RCBO (30mA sensitivity)Outgoing : 9 Nos. 16A, SPN MCBs |
| 19 | Indoor Lighting Distribution Board (ILDB):For Control & Customer Care RoomSupply of 415V, 50 Hz, 3 Ph, 4 Wire, 32A, 10 kA for 1 sec. Cu busbar, Indoor Type, Floor/Wall mounted Lighting Panel IP42, CRCA sheet steel enclosure, wall or frame mounted, Non-compartmentalised, Double door, Weatherproof, along with Weatherproof double compression Ni plated brass cable glands and lugs and sheet steel canopy, suitable for bottom cable entry, incomer and outgoing feeders, with indication lamp, etc complete in all respect as per attached SLD , Specification, Data sheet of this tender.Incomer : 1 No. 32A, 4P RCBO (30mA sensitivity)Outgoing : 9 Nos. 16A, SPN MCBs |
| 20 | Indoor Lighting Distribution Board (ILDB):For Store RoomSupply of 415V, 50 Hz, 3 Ph, 4 Wire, 16A, 10 kA for 1 sec. Cu busbar, Indoor Type, Floor/Wall mounted Lighting Panel IP42, CRCA sheet steel enclosure, wall or frame mounted, Non-compartmentalised, Double door, Weatherproof, along with Weatherproof double compression Ni plated brass cable glands and lugs and sheet steel canopy, suitable for bottom cable entry, incomer and outgoing feeders, with indication lamp, etc complete in all respect as per attached SLD , Specification, Data sheet of this tender.Incomer : 1 No. 16A, 4P RCBO (30mA sensitivity)Outgoing : 3 Nos. 6A, SPN MCBs |
| 21 | Flame proof Outdoor Lighting Distribution Board (OLDB):Supply of 415V, 50 Hz, 3 Ph, 4 Wire, 63 A, 10 kA for 1 sec. cu busbar, IP-65,Indoor Type, 'Ex-d' type suitable for Zone-2, Gas Group-IIA/ IIB/ IIC, Temperature Class-T3, Aluminium alloy (LM6) enclosure,wall or frame mounted, IP 65, Weatherproof with Canopy, Non-compartmentalised, Double door, Lighting Panels along with Flameproof proof double compression Ni plated brass cable glands and lugs suitable for bottom cable entry, incomer and outgoing feeders, with indication lamp, etc complete in all respect as per attached SLD, Specification, Data sheet of this tender.Incomer : 1 No. 63A, 4P MCCB (30mA sensitivity)Outgoing :2 Nos. 32A, TPN ,3 Nos. 16A, SPN MCBs (with timer) 2 Nos. 32A, TPN ,3 Nos. 16A, SPN MCBs (without timer) |
| 22 | Local control station (LCS) |
| 23 | Supply of following Industrial type LCS, Weatherproof, Flameproof “Ex-d”(suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2), IP 65, Local Control Station suitable for Wall / Column / Structure mounting. All LCS shall be made up of Aluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA sheet with side cover. LCS shall confirm to attached specification/data sheet. LCS shall be supplied along with Flameproof Double compression, Ni plated brass cable glands & lugs as per attached specification of this tender. |
| 24 | FLP (Zone-1, IIA/IIB, T3) IP65 Local control station provided with recess type START STOP PB, Suppressed scale Ammeter & 1no. mushroom head stay put type emergency stop PB with Keys/lock & pin arrangement, Local remote switch (with additionalcontacts to give the status of Local remote switch to DCS/PLC) including flameproof double compression stainless steel cableglands & plugs, suitable for outdoor installation as required as per attached specifications of this tender. |
| 25 | Break glass type Emergency Trip Push Button (ETPB) for transformer: weather proof emergency stop push button(EPB) with ON-OFF LED indication break glass type enclosure, 3mm thick CRCA canopy, weatherproof double compression Nickel Plted Brasscable glands(2 nos.) and 1NO+1 NC contact. |
| 26 | JUNCTION BOX (JBs) |
| 27 | JUNCTION BOXES FOR PUMP MOTOR (WEATHER PROOF, FLAME PROOF): Supply of following 415V, 3P, Industrial type, Weatherproof, Flame proof “Ex-d”(suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2), IP 65 suitable for Wall / Column / Structure mounting including cabling from JB to terminal box for VFD pump motor connection.All JBs shall be made up of cast Aluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA sheet with side cover. JBs shall confirm to attached specification/data sheet. Junction Boxes shall be complete with busbar of suitable rating, support insulator, suitable for tentative cable sizes as indicated below & shall be supplied along with FLP type double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (2 runs of Incoming cable size 3C x 240 sqmm /2 runs of Outgoing Cable shall be 3C x 185/150 sqmm, XLPE insulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables.) |
| 28 | JUNCTION BOXES FOR LIGHTING FIXTURES (WEATHER PROOF, NON-FLAME PROOF): Supply of following 16A, 240V, 4-way, Ph-N, Industrial type, Weatherproof, IP 65 suitable for Wall / Column / Structure/ Pole mounting. Including wiring from JB to Fixture with terminals block with additional earthing terminals and end clamps etc. All JBs shall be made up of cast Aluminium alloy (LM6 grade). JBs shall confirm to attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be supplied along with Double compression cable glands, Ni plated brass cable glands, lugs & plugs, PVC shrouds. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPEinsulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. |
| 29 | JUNCTION BOXES FOR LIGHTING FIXTURES (WEATHER PROOF, FLAME PROOF): Supply of following 16A, 240V, 4-way, Ph-N, Industrial type, Weatherproof, IP 65 suitable for Wall / Column / Structure/ Pole mounting. Including wiring from JB to Fixture with terminals block with additional earthing terminals and end clamps etc. All JBs shall be made up of cast Aluminium alloy (LM6 grade) Flameproof “Ex-d” (suitable for hazardous area of gas groupIIA/IIB, temperature class T3 and Zone-2). JBs shall confirm to attached specification/data sheet. Junction Boxes shall besuitable for cable sizes tentatively as indicated below & shall be supplied along with Flameproof double compression, Ni platedbrass cable glands, lugs & plugs, PVC Shrouds. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPEinsulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. |
| 30 | CANOPY FOR JBS/LCS/FIELD EQUIPMENTS.Supply of Sheet steel canopies made of 14 gauge CRCA sheet with side cover, PU painted to be provided as applicable for junction boxes, local control stations and others electrical equipment's located outdoor.Note: This items is applicable as per site requirement and direction of Engineering-in charge. |
| 31 | JUNCTION BOXES FOR POWER SOCKETS (WEATHER PROOF, FLAME PROOF): Supply of following Industrial type, Weatherproof, IP 65 suitable for Wall /Column / Structure mounting JBs with terminals block with additional earthing terminals and end clamps etc.All JBs shall be made up of cast Aluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA with side cover, Flameproof “Ex-d”(suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2). JBs shall confirm to attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be supplied along with Flameproof Double compression, Ni plated brass cable glands, lugs & plugs, PVC shrouds. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPEinsulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. 16A, 415V,TPN, 6-way |
| 32 | JUNCTION BOXES FOR POWER SOCKETS (WEATHER PROOF, NON-FLAME PROOF): Supply of following Industrial type, Weatherproof, IP 65 suitable for Wall /Column / Structure mounting JBs with terminals block with additional earthing terminals and end clamps etc. All JBs shall be made up of cast Aluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA with side cover. JBs shall confirm to attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be supplied along with Weatherproof Double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPEinsulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. 16A, 415V,TPN, 6-way |
| 33 | EARTHING SYSTEM |
| 34 | Supply and design for complete earthing including lightining protection system for entire plant, earth electrodes/ pit, earth main ring, earthing of electrical equipment, instrument panels, field instruments, with heavy duty perforated GI pipe electrode / Copper Plate Electrode, providing suitable earth bus for interconnection, SS nut bolts to be used for Copper earthing and clamps of the GI earthing which are operated on regular basis i.e. clamp connections at top, providing a mixture of salt & charcoal, making RCC/Brick earth pit chamber and associated civil works as per standard Drg. etc. all complete as per specification & direction of Site-In-charge.Item also includes Supply and fixing of Earth resistance display board of size 450 X 300 mm with 3mm thick AluminiumComposite Material (ACM)/ Aluminium Composite Panel (ACP) bolted to 25 X 25 X 5 mm (with 2 bolts MS angle section, 60 cmlong (minmum 200 mm embedded in ground). The rate shall also include supply and pasting of UV resistant vinyl sticker havingdetails as per Site-in-charge. |
| 35 | Earth Pits- Earth electrode with following sizes: 100 mm dia, 3.8 M long heavy duty perforated GI pipe electrode (Galvanisation is 610 gms/sq. mtr or as per IS-4759/ISO 1461.) as per IS:3043 |
| 36 | GI Strip (75 x 10) mm |
| 37 | GI Strip (50 x 6) mm |
| 38 | GI Strip (25 x 3) mm |
| 39 | Supply of GI wire / rope 10 Sq mm including nut bolt, washer,lugs and all balance earthing material as per the specification. |
| 40 | Supply of 8 SWG GI wire rope including nut bolt, washer,lugs and all balance earthing material as per the specification. |
| 41 | Supply of 25mm square copper strip/braided flexible cable |
| 42 | Supply 1C x6 sq mm green colur copper flexible cable for earthing of fitting |
| 43 | Supply 1C x 150 sq mm green colur copper flexible cable for earthing |
| 44 | Supply of 16 Ways GI. Earthing Plate -Thickness 12 mm, LENGTH 1000 mm |
| 45 | Supply of lightning conductor finial made of 25 mm dia 1800 mm long GI tube having single prong at top with 85 mm dia 3 mm thick GI base plate including holes etc. complete as required. |
| 46 | Supply of 50 x 6 strip fixing saddles for ligtning protection complete with other accessories as required. |
| 47 | Supply of square tape clamp for ligtning protection complete with other accessories as required. |
| 48 | Supply of test link box for ligtning protection (for connection of each down conductor to earth pit) complete with other accessories as required. |
| 49 | HT CABLE & TERMINATION KIT |
| 50 | Supply of 11 kV(E) grade, stranded, multicore, Al. Conductor, conductor scrren, XLPE insulated, Insulationscreen, PVC inner sheath, steel wire armoured, PVC outer sheathed H.T. power cables as per IEC 60502-2 / IS 7098-2 offollowing sizes in ground/tray including fixing of strip number tags, fixing of saddles and saddle bars, protective tiles etc.including transportation from store/yard to site at the place of installation, unpacking, including all labour and materials, asper attached specification of this tender and directions of Engineer-in- charge. Before procurring the cable, Contractor tomake cable schedule as per site conditions and get approved by IOCL/Consultant.The item also includes cable Tag 2mm thick Aluminium with No. punched on it and shall be securely attached to the cable bynot less than two turns of 20 SWG GI wire conforming to IS 280. |
| 51 | 3C X 300 mm2 11 kV (E) Grade Cable |
| 52 | Supply of outdoor termination kit for 3C X 300 mm2 11 kV (E) Grade Cable. |
| 53 | Supply of indoor termination kit for 3C X 300 mm2 11 kV (E) Grade Cable. |
| 54 | Supply Jointing kit for 11/11kV 3Cx300 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed |
| 55 | LT CABLE STRAIGHT THROUGH JOINT |
| 56 | Supply of straight through joint of following 1.1 KV grade XLPE insulated armoured cable with M-Seal make jointing kit, and other jointing material, etc. all complete including supply of all materials as per specification & direction of Engineer In-charge. |
| 57 | 3.5 Core x 185 mm2 A2XFY |
| 58 | 3.5 Core x 150 mm2 A2XFY |
| 59 | 3.5 Core x 120 mm2 A2XFY |
| 60 | 3.5Cx 95 mm2 A2XFY |
| 61 | 3.5Cx 70 mm2 A2XFY |
| 62 | 3.5Cx 50 mm2 A2XFY |
| 63 | 3.5Cx 35 mm2 A2XFY |
| 64 | 4Cx 25 mm2 A2XFY |
| 65 | 4Cx 16 mm2 A2XFY |
| 66 | 4Cx 10 mm2 A2XFY |
| 67 | 4Cx 6 mm2 A2XFY |
| 68 | 4Cx 4 mm2 2XWY |
| 69 | 4Cx 2.5 mm2 2XWY |
| 70 | 3Cx 2.5 mm2 2XWY |
| 71 | 7C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 72 | 12C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 73 | LT POWER CABLE |
| 74 | LT Power Cables (FRLS): Supply of 1.1kV grade, XLPE insulated, stranded Cu / Al.Conductor, steel wire/strip (for multi core) armoured, for power cable, control cable and signal cable, PVC sheathed, FRLS power and control cables (conforming to IS:7098 and tender specification) along with Glanding & Cable termination,connection of Double compression nickel plated brass Cable gland (FLP/Weather proof gland as per requirement) and nickel plated lugs & termination, silicon based jointing kit as per cable schedule(will be provided detail engineering) of following sizes in ground/trenches/tray, pulling through pipes and its proper sealing etc. including fixing of strip number tags, fixing of saddles and saddle bars, protective tiles etc. including transportation from store/yard to site at the place of installation, unpacking,including all labour and materials, and completeness with all aspect as per attached specifications directions of Engineer-in-charge.The item includes cable Tag 2mm thick Aluminium with No. punched on it and shall be securely attached to the cable by notless than two turns of 20 SWG GI wire conforming to IS 280. The same shall be attached @ max. 30m or at bends whichever islesser.Note: a) Before procuring cable, successfull bidder is required to prepare detailed BOQ, cable schedule & Drum Schedule of Cables asper site mesaurement and get approved by IOCL/Consultant. No extra payment shall be made for wastages.b) Payment shall be paid separately for Supply of FLP/WP Industrial Glands & termination Glands shall be supplied with PVC hood. Diameter of cable under armour and above armour shall be checked prior to ordering of glands. Glands shall be complete with doubleseal cone-grip arrangements and check nuts. |
| 75 | 1C x 630 mm2 A2XFY |
| 76 | 3.5Cx 185 mm2 A2XFY |
| 77 | 3.5Cx 150 mm2 A2XFY |
| 78 | 3.5Cx 120 mm2 A2XFY |
| 79 | 3.5Cx 95 mm2 A2XFY |
| 80 | 3.5Cx 70 mm2 A2XFY |
| 81 | 3.5Cx 50 mm2 A2XFY |
| 82 | 3Cx 240 mm2 A2XFY |
| 83 | 3Cx 185 mm2 A2XFY |
| 84 | 3Cx 2.5 mm2 2XWY |
| 85 | 4Cx 25 mm2 A2XFY |
| 86 | 4Cx 16 mm2 A2XFY |
| 87 | 4Cx 10 mm2 2XWY |
| 88 | 4Cx 6 mm2 2XWY |
| 89 | 4Cx 4 mm2 2XWY |
| 90 | 4Cx2.5 mm2 2XWY (For MOV) |
| 91 | 2Cx2.5 mm2 2XWY |
| 92 | 7C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 93 | 12C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 94 | Supply of Double compression, weather proof (Non FLP), brass cable glands suitable for following XLPE/PVC , FRLS cable sizes & as per relevant IS for Indoor/outdoor use. |
| 95 | 1C x 630 mm2 A2XFY |
| 96 | 3.5Cx 185 mm2 A2XFY |
| 97 | 3.5Cx 150 mm2 A2XFY |
| 98 | 3.5Cx 120 mm2 A2XFY |
| 99 | 3.5Cx 95 mm2 A2XFY |
| 100 | 3.5Cx 70 mm2 A2XFY |
| 101 | 3.5Cx 50 mm2 A2XFY |
| 102 | 3Cx 240 mm2 A2XFY |
| 103 | 3Cx 185 mm2 A2XFY |
| 104 | 3Cx 2.5 mm2 2XWY |
| 105 | 4Cx 25 mm2 A2XFY |
| 106 | 4Cx 16 mm2 A2XFY |
| 107 | 4Cx 10 mm2 2XWY |
| 108 | 4Cx 6 mm2 2XWY |
| 109 | 4Cx 4 mm2 2XWY |
| 110 | 4Cx2.5 mm2 2XWY (For MOV) |
| 111 | 2Cx2.5 mm2 2XWY |
| 112 | 7C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 113 | 12C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 114 | Supply of FLP double compression brass Cable Gland for hazardous area brass cable glands suitable for following XLPE/PVC , FRLS cable sizes & as per relevant IS for Indoor/outdoor use. |
| 115 | 1C x 630 mm2 A2XFY |
| 116 | 3.5Cx 185 mm2 A2XFY |
| 117 | 3.5Cx 150 mm2 A2XFY |
| 118 | 3.5Cx 120 mm2 A2XFY |
| 119 | 3.5Cx 95 mm2 A2XFY |
| 120 | 3.5Cx 70 mm2 A2XFY |
| 121 | 3.5Cx 50 mm2 A2XFY |
| 122 | 3Cx 240 mm2 A2XFY |
| 123 | 3Cx 185 mm2 A2XFY |
| 124 | 3Cx 2.5 mm2 2XWY |
| 125 | 4Cx 25 mm2 A2XFY |
| 126 | 4Cx 16 mm2 A2XFY |
| 127 | 4Cx 10 mm2 2XWY |
| 128 | 4Cx 6 mm2 2XWY |
| 129 | 4Cx 4 mm2 2XWY |
| 130 | 4Cx2.5 mm2 2XWY (For MOV) |
| 131 | 2Cx2.5 mm2 2XWY |
| 132 | 7C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 133 | 12C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 134 | MULTI CABLE TRANSIT (MCT) Block |
| 135 | Multi Cable Transit (MCT) Blocks: Supply of MCT block with SS Frame with EPDM Modules, Stay plate, Compression wedge, Lubricant etc complete with all accessories for following area as per the respective cable schedule/sizes for cable entry Buildings (Control Room, PMCC, Admin Building, Invoice Room, Security Room, Driver's Rest Room & any other etc) with minimum 30% spare.MCT blocks for future cable entry along with frame and mounting accessories complete as per specification of tender. |
| 136 | MCT Block (for LT Power Cables- 24 incomer/outoging Cables + 30% Spare blocks ) |
| 137 | MCT Block (for LT Power cables -12 incomer/outoging Cables + 30% Spare blocks) |
| 138 | OUTDOOR LIGHT FITTINGS : |
| 139 | Supply of flameproof/weatherproof Luminaries (lighting fixtures) of approved makes as per the specification including receiving from store, transporting to erection site including handling, arrangement of transport vehicle, unpacking, inspection, checking of internal wiring, cable glanding and termination, crimping of lugs and connections at fixtures/ control gears, supply of all erection materials including necessary GI hardware, GI clamps, GI brackets, civil masonry materials, testing of following types of lighting fixtures with all their parts and accessories etc, including fixing of lamps, all work, labour and materials, complete as per drawings and specification of this tender and directions of Engineer in charge.The item also includes the design & submission of the design/LUX level report as per the provisions of OISD for the entire plantarea/sheds/buildings etc. including finalization of locations/coordinates of the high masts based on the selected lumanaires.The design must be submitted for approval from IOCL/PMC.(All Lighting fixtures shall be provided with required no. of double compression nickle plated brass cable glands, lugs andstopping plug.) |
| 140 | Outdoor area lighting, Weatherproof and Flame proof (Ex\\"d\\" suitable for Gas group IIA/IIB, T3, suitable for Zone 2) 110W LEDIndustrial flood light fixture suitable for 7 m Single/Double arm light pole, mountings enclosure with toughened glass, SS wireguard, stainless steel hardware, earthing terminal, installation hardware and all necessary accessories wired up to terminalbox, lamps & accessories, complete in all respects as per attached specifications / data sheet of the Tender. |
| 141 | Outdoor area lighting, Weatherproof 110W LED Industrial flood light fixture suitable for 7 m Single/Double arm light pole,mountings enclosure with toughened glass, SS wire guard, stainless steel hardware, earthing terminal, installation hardware andall necessary accessories wired up to terminal box, lamps & accessories, complete in all respects as per attached specifications/ data sheet of the Tender. |
| 142 | Outdoor type, Weatherproof and Flame proof (Ex\\"d\\" suitable for Gas group IIA/IIB, T3, suitable for Zone 2) 110 W LED well glasslight fixture, mountings enclosure with toughened glass, SS wire guard, stainless steel hardware, earthing terminal, installationhardware and all necessary accessories wired up to terminal box, suitable for mounted on structure including wiring lightfixture complete in all respects. |
| 143 | Outdoor type, Weatherproof and Flame proof (Ex\\"d\\" suitable for Gas group IIA/IIB, T3, suitable for Zone 2) 110 W LED flood lightlight fixture, mountings enclosure with toughened glass, SS wire guard, stainless steel hardware, earthing terminal, installationhardware and all necessary accessories wired up to terminal box, suitable for mounted on structure including wiring lightfixture complete in all respects. |
| 144 | LED Flood Light: Supply of high-quality integrated LED Flood Light with a minimum system lumen of53000 Lm and system wattage of nominal 400W with a nominal efficiency 130 lumen/watt. CCT of 5700K with SDCM of < 5 andCRI : 70. The housing should be of non-corrosive high-pressure die-cast aluminum to with stand extreme environments. It shouldhave corrosion resistant powder coating to pass NSS of 500 Hrs. with PF > 0.95. Lifetime of 75K hours @L70. Product should besuitable for continuous operation (10-12 Hrs. per day). The Ingress protection should be minimum IP 66 with an IK rating of 08.Optical and control gear compartments shall be maintainable/replaceable without impacting the LED units. The access to theoptical and the gear compartment should be separate. While accessing the gear compartment, the optical compartment shouldnot be accessible. The Luminaire should have a 20 KV /10 kA SPD duly bolted in theLuminaire. The SPD should be able to sustain a minimum 15 hits of 10kA rating i.e., Total of 45 hits across all the three modes as per IEEE62.41.2. The Luminaire should have a breather to ensure that air balance inside and outside of the Compartment .The luminaireshould be of Class B Serviceability. The wattage of each LED should be greater than 1 watt and less than 3 Watt. Only highpower Single white LED chip with ceramic based suitable for outdoor use is allowed. Multi Chip , array multi die , midpower,Integrated arrays and COBs are not permitted. The High-power LED used in the luminaire shall be SMD type.The luminaire should be capable of withstanding voltage stress of 440V for 8 Hrs., should have an auto shutdown @ 325V and have an auto recovery feature. The Drivers should be a potted driver not a printed circuit board without casing, mounted inside the luminaire. The Dimension of the luminaires should be minimum 595 x 100 x418 mm and have a breather ensuring stable optical and thermal management. |
| 145 | Supply of outdoor type, FLP type 60 W LED well glass light fixture,for Mounted on structure including wiring light fixture complete in all respects. ssuitable for out door, Hazardous Zone-2 area. |
| 146 | LIGHT POLE AND HIGH MAST |
| 147 | Double arm Polygonal / Octagonal street pole:Supply of 7 Meter high galvanised Polygonal / Octagonal Street Light Pole with double arm 1500mm long bracket arm made up of 48 O.D.pipe with EN 8 grade Galvanised foundation bolts and anchor plate having fixing arrangement for mounting 1 Nos. of LED luminaries as per enclosed technical specifications. The item also includes suitable fixing/clamping arrangement made up of GI on the body of the Light Pole for fixing of requisite flameproof or weatherproof junction boxes with terminals block with additional earthing terminals and end clamps etc. including 4 Nos double compression cable glands / Plug, lugs with PVC shrouds suitable size of Cable (XLPE, FRLS), complete with all accessories suitable for Hazardous Zone-2 area alongwith associated jobs etc. The payment for the Junction Box, light fixtures, cables shall be made seperately. |
| 148 | Supply of 7 Meter high galvanised Polygonal / Octagonal Street Light Pole with Single arm 1500mm long bracket arm made up of 48 O.D.pipe with EN 8 grade Galvanised foundation bolts and anchor plate having fixing arrangement for mounting 1 Nos. of LED luminaries as per enclosed technical specifications. The item also includes suitable fixing/clamping arrangement made up of GI on the body of the Light Pole for fixing of requisite flameproof or weatherproof junction boxes with terminals block with additional earthing terminals and end clamps etc. including 4 Nos double compression cable glands / Plug, lugs with PVC shrouds suitable size of Cable (XLPE, FRLS), complete with all accessories suitable for Hazardous Zone-2 area alongwith associated jobs etc. The payment for the Junction Box, light fixtures, cables shall be made seperately |
| 149 | 30 Mtr. height High Mast Tower:Supply of 30 Mtr. height High Mast Tower (hot dip galvanized, base metal thickness not less than 4 mm), Outdoor type, with provision of 2x8 nos of 400 W NON FLP LED types of luminaires in two layers and its control gear box complete with accessories as per specifications/datasheet of Tender. The cost also includes supplying and providing trailing cable of suitable size & length from Switch Plug & Socket at the foot of high mast to the junction box at the top, motor, suitable size double compression Ni plated brass cable glands and lugs, PVC shrouds, etc. Note:a) The civil works required for high mast foundations are included in scope of this item.b) The item includes the S/I of raising lowering system comprising double drum winch, 6mm diameter SS wire rope, trailingcable, connector, integral power tool motor, manual handle, junction box, lightening finial (Lightening arrestor), including lowintensity LED type double dome aviation obstruction light.c) Tenderers should note that junction box shall be provided at the top of the high mast as per specifications. Rates forlighting fixtures and earth pits shall be paid separately.d) Bidder to provide design and drawing for High Mast Tower and foundation of high mast tower.e) The high Mast system shall be suitable for wind speed of the location as per IS-875, with head frame, winch mountingbracket, luminaries carriage suitable to install 16 nos. 400W LED FLD in asymmetrical arrangement. e) The scope includes the supply foundation bolts manufactured from EN 8 grade galvanised steel along with nuts, washers,anchor plate and common template.f) Provision of lowering/raising of light fixutures without removal of cable end termination, complete with accessories as perattached specification of this tender. |
| 150 | Flameproof Outdoor Feeder Pillar Panel:Supply of flameproof outdoor distribution board (Feeder Pillar Panel), made up of cast Aluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA with side cover, IP-65, stand mounted, with timer contactor, Auto manual selector switch and control mcb, 1 no. 32A TPN MCB incomer, single dial time switch, 22A TP contactor for the automatic switching of luminaries, power tool control with 2 no 9A contactors and raise lower push button, required cabling/termination from Panel to light fitting and required GI pipes, provision of Incoming, Outgoing and for Looping and FLP type industrial socket with associated civil works like foundation etc. |
| 151 | DCDB-Distribution Board |
| 152 | Supply of DCB Sub-DB,100V 50 Hz, 1 Ph, ,16 Amp DP MCB, as per SLD, sheet steel enclosure of approved make having MCB as incoming and DP MCB for out going circuit complete with wiring,indication lamp,copper busbar etc including all labour and materials as per specification and the direction of Engineer-in-charge.16A DP MCCB as incomer and 6 nos 6A DP MCB as outgoing. |
| 153 | HDPE CABLE CONDUIT |
| 154 | Supply of HDPE Pipe of Heavy Duty type, High compression strength, IP 67 rated (DWC) Double wall corrugated HDPE Conduits as per IS:14930/IS:16205. supply of clamps, spacers, sealants including all labour and materialscomplete as per drawings and directions of Engineer-In-Charge for the following sizes of HDPE Pipe in required length. |
| 155 | 50 mm NB |
| 156 | 100 mm NB |
| 157 | 150 mm NB |
| 158 | GI CABLE CONDUIT |
| 159 | Supply of B-class G.I. pipe conforming to IS: 1239 for cable protection inlcuding supply of clamps, spacers and all labour and materials complete as per drawings and directions of Engineer-In-Charge for the following sizes of GI Pipe in required length |
| 160 | 50 mm NB |
| 161 | 100 mm NB |
| 162 | 150 mm NB |
| 163 | CABLE TRAY |
| 164 | Supply of following Hot Dip Galvanized Ladder/Perforated Type cable trays (as per IS 2629) including bends, tee, crosses,horizontal, insert plate, tray supports and vertical splices etc. as required, including supply of all G.I hardwares, civil works and its materials, all labour and material as required as per standard drawings, specification and direction of Engineer-in-charge.Perforated/Ladder type- 2.5 mm thick sheet steel & galvanized (86 microns) of following sizes:- |
| 165 | 600 x 100 mm wide - Ladder Type |
| 166 | 300 x 100 mm wide-Ladder Type |
| 167 | 600 x 100 mm wide - Perforated Type |
| 168 | 300 x 100 mm wide-Perforated Type |
| 169 | 150 x 100 mm wide-Perforated Type |
| 170 | 50 x 50 mm wide-Perforated Type |
| 171 | 1.6 mm thick Hot dip G.I. Cover of minumum 2.5 M length suitable for Cable tray of following sizes including clamps for fixing the cover to cable tray with all accessories. Minimum thickness of galvanisation shall be 910 gm/m2 |
| 172 | Top tray cover for perforated 50 mm |
| 173 | Top tray cover for perforated 150 mm |
| 174 | Top tray cover for perforated 300 mm |
| 175 | Top tray cover for perforated 600 mm |
| 176 | INDUSTRIAL POWER SOCKET OUTLETS WITH INTEGRAL PLUG TOPS (WEATHERPROOF, FLAMEPROOF TYPE): Supply of Power Socket outlets shall be Flame proof “Ex-d” (suitable forhazardous area of gas group IIA/IIB, temperature class T3 and Zone-2), Industrial type, (IP 65) interlocked with MCB and ELCBand suitable for loop-in loop-out entries for armoured cable as specified, enclosed with Cast Aluminium alloy (LM-6 grade), withstainless steel hardware, endless neo print gasket, 2nos. of cable entry, stopping plugs, earthing terminals, installationhardware and all necessary accessories wired upto terminal box. Integral plug tops shall be also supplied with the power socketoutlets.All switch sockets shall be provided with Canopy of 14 gauge CRCA sheet with side cover and required no. of FLP doublecompression Ni plated brass cable glands and FLP stopping plug as per attached specification sheets. |
| 177 | 415 V AC, 3 phase, 63A, (3P+N+E), 50 Hz |
| 178 | 16A. 230 V AC, 1 phase(1P +N+E), 50 Hz, |
| 179 | INDUSTRIAL POWER SOCKET OUTLETS WITH INTEGRAL PLUG TOPS (WEATHERPROOF, NON-FLAMEPROOF TYPE):Supply of Power Socket outlets shall be Non-Flame proof, industrial type (IP65)interlocked with MCB and ELCB and suitable for loop-in loop-out entries for armoured cable as specified enclosed with CastAluminium alloy (LM-6 grade) with stainless steel hardware, endless neo print gasket, 2nos. of cable entry, stopping plugs,earthing terminals, installation hardware and all necessary accessories wired upto terminal box. Integral plug tops shall be alsosupplied with the power socket outlets.All switch sockets shall be provided with Canopy of 14 gauge CRCA sheet with side cover and required no. of doublecompression Ni plated brass cable glands and stopping plug as per attached specification sheets. |
| 180 | 415 V AC, 3 phase, 63A, (3P+N+E), 50 Hz |
| 181 | 16A. 230 V AC, 1 phase(1P +N+E), 50 Hz, |
| 182 | Supply of the following including the supply of necessary clamp , bolts and hardware,Breaking and repair of walls, if required, and including all labour and materials complete as per directions of Engineer-In-Charge, applicable standards and Indian Electricity rules. |
| 183 | Vitreous enamel caution boards (HINDI/ ENGLISH) as per IS 2551 |
| 184 | 11 kV |
| 185 | 440 V |
| 186 | Shock treatment chart ( laminated type) as per IS:5216 in bilingual language (Hindi & English) duly laminated on a hard back ground to be hung at various places |
| 187 | Single Line Diagram consisiting of new and existing system complete in glass frame. |
| 188 | Discharge rod telescopic fiber glass heavy duty with necessary earthing facilities & wires. |
| 189 | Supply of Insulating Mats 1.1kV grade (as per IS:15652 - 2006) of 1000mm width, required for maintenance of electrical equipment in station as required including cutting to required shape in running length and including all labour and materials etc. complete and as per directions of Engineer-In-Charge, as per applicable Indian or International standards and Indian Electricity Rules. |
| 190 | Supply of Rubber mat 11kv grade(as per IS15652/IEC61111) of (2 or 2.5mm thick X 0.9 or 1Mtr) required for maintenance of electrical equipment in station as required including cutting to required shape in running length and including all labour and materials etc. complete and as per directions of Engineer-In-Charge, as per applicable Indian or International standards and Indian Electricity Rules. |
| 191 | 11 KV grade hand gloves, ISI mark,as per IS 13774 & IEC |
| 192 | 415 V grade hand gloves, ISI mark,as per IS 13774 & IEC |
| 193 | Supplying, transporting of steel and structure conforming to property class 4.6 or higher of I.S:1367 at all height as per approved fabrication drawings of all types of structural steel work in rolled steel joints, channels, angles, tees, flats, plates, lattice members built up / compound sections in columns, portals, girders, beams, bracings, trusses, purlins, rafters, staircase, steps, hand-railings, walkway, cat ladder with cages, toe plates, side walling, trestles, Conveyor gantries grating, chequred plate etc. including gusset plates, anchor plates etc., including site and shop fasteners, riveting, bolting, welding at shop or work site at all heights etc. & including applying approved coats of primers, undercoat and finish painting as per Technical specification. Complete as per drawing and direction of Owner / Consultant. (All material supply is in contractor’s scope including paints ) |
| 194 | Fire extinguishers CO2 type in 4.5kg capacity complete with handle , fixing bracket etc. |
| 195 | Supply of Cable Route markers |
| 196 | Supply of Cable Route markers (30m interval) for HT Cable (11kV grade), CI material, 150mm Dia. Round with 5mm-6mm thickness, two holes for mounting, 3mm embossed lettering as appropriate, bolted/welded to 35mm x 35mm x 6mm angleiron, 600mm long and fixing the same in ground, including painting with all accessories all civil works, labour and materialscomplete as required and as per directions of Engineer-In-Charge. |
| 197 | Supply of Cable Route markers (30m interval) for LT Cable (415V grade), CI material, 150mm Dia. Round with 5mm-6mm thickness, two holes for mounting, 3mm embossed lettering as appropriate, bolted/welded to 35mm x 35mm x 6mm angleiron, 600mm long and fixing the same in ground, including painting with all accessories all civil works, labour and materialscomplete as required and as per directions of Engineer-In-Charge. |
| 198 | TRANSFORMER |
| 199 | Supply of 3150 kVATransformer Oil Type copper winding: 3150 kVA (ONAN), 415V, 11/0.433 KV, Dyn11, Z =8%, OCTC +/- 10% @2. 5% , including transportation from store/yard to site at the place of installation, unpacking, positioning in place, site assembly of loosely furnished accessories, including connection of auxiliary circuits, including fixing of nuts and bolts etc.,consisting of all accessories, mandatory spares, erection & commissioning spare and recommended spares for 2 years operation and maintenance, including all labour and materials along with weather proof double compression Ni plated brass cable glands and cable lugs for outgoing cables and all other accessories for Transformer, complete in all respects as specified in technical specification, data sheet & Overall SLD of this tender and directions of Engineer-in-Charge.The supply includes first fill of transformer oil and all consumables. Transformer shall be complete with minimum accessories asfollows: Complete set of gaskets, Silica Gel Breather, set of valves, Buchholz relay, complete winding temperature indicatingequipment (WTI), Oil Temperature Indicating equipment (OTI), Pressure relief device with trip contacts, bushing of each type,CTs of each type for 51G & 64R as per attached Electrical Overall SLD and Oil Level Gauge etc. as per specification. CTs shall be provided as per SLD. (INCLUSIVE OF HEAT RUN TEST ) |
| 200 | Supply of 3150 kVA Transformer : 3150 kVA (ONAN), 415V, 11/0.433 KV, Dyn11, Z =8%, OCTC +- 10% @2. 5% tapping from HT VCB consisting of all accessories, mandatory spares, commissioning spare and recommended spares for 2 years operation and maintenance,complete in all respects as specified in technical specification, data sheet & SLD. |
| 201 | Supply of 250 kVA,copper winding Cast resin Dry type transformer (Indoor), with 415Volt,50Hz input and 415 Volt output, along with Weather proof double compression Ni plated brass cable gland and cable lugs for all incoming and outgoing cables, insulation class H temperature class limited to class B, including transportation from store/yard to site at the place of installation, unpacking,positioning in place, site assembly of loosely furnished accessories, including connection of auxiliary circuits, including fixing ofnuts and bolts etc., consisting of all accessories, mandatory spares, erection & commissioning spare and recommended sparesfor 2 years operation and maintenance, including all labour and materials, complete in all respects as specified in technicalspecification, data sheet & Overall SLD of this tender and directions of Engineer-in-Charge . Transformer shall be complete with minimum accessories as follows: Complete set of gaskets, winding temperature indicatingequipment (WTI), bushing of each type etc. as per Specification/Data sheet/SLD.( INCLUSIVE OF HEAT RUN TEST ) |
| 202 | 110V DC system (Battery, Battery charger and DC DB) |
| 203 | Supply of 5 kVA 110V DC Battery Charger & DCDB System (IP-31) comprising110V DC Battery Bank for 30 mins back-up, Chargers, Battery isolator/MCCB of suitable rating & DC Distribution Board etc.which includes installation of metal stands, placing of batteries on stands on cell insulators, fixing the cell, interconnecting thebattery cells, cell booster and charging the battery cells as per attached specification of this tender .Suitable size of doublecompression glands shall be supplied with Battery Charger and DCDB. Vendor shall supply suitable battery of AH ratingcalculated as per duty cycle/load details attached with datasheet and submit the sizing calculation accordingly.Location: PMCCNOTE :Supervision of laying & termination of all inter-panel/ inter-cubicle cabling including cabling up to Battery Bank andinter-tier cabling of Battery Bank shall be in the scope of Supplier . However, supply, laying and termination of the cables shallbe done by the contractor. |
| 204 | DCDB :110V DC, 63A, Cu bus bar, DC DB shall be indoor TypeIncomer - 63A DC, DP MCCB Outgoing - 15 Nos. 16A DC, DP MCB, 6 Nos of 6 A DP MCB |
| 205 | Supply of 11 kV(UE) grade, stranded, multicore, Al. Conductor, conductor scrren, XLPE insulated, Insulation screen, PVC inner sheath, steel wire armoured, PVC outer sheathed H.T. power cables as per IEC 60502-2 of following sizes in ground/tray including fixing of strip number tags, fixing of saddles and saddle bars, fixing of route markers, protective tiles etc. including transportation from store/yard to site at the place of installation, unpacking, including all labour and materials, as per attached specification of this tender and directions of Engineer-in- charge.Before procurring the cable, Contractor to make cable schedule as per site conditions and get approved by IOCL/Consultant. |
| 206 | 3C X 300 mm2 11 kV (UE) Grade Cable |
| 207 | Supply of outdoor termination kit for 3C X 300 mm2 11 kV (UE) Grade Cable. |
| 208 | Supply of indoor termination kit for 3C X 300 mm2 11 kV (UE) Grade Cable. |
| 209 | Jointing kit for 11/11kV 3Cx 300 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed |
| 210 | 3C X 400 mm2 11 kV (UE) Grade Cable |
| 211 | Supply of outdoor termination kit for 3C X 400 mm2 11 kV (UE) Grade Cable. |
| 212 | Supply of indoor termination kit for 3C X 400 mm2 11 kV (UE) Grade Cable. |
| 213 | JUNCTION BOXES FOR PUMP MOTOR (WEATHER PROOF, FLAME PROOF): Supply of following 415V, 3P, Industrial type, Weatherproof, Flame proof IP 65 suitable for Wall / Column / Structure mounting Including cabling from JB to terminal box of motorAll JBs shall be made up of cast Aluminium alloy (LM6 grade). JBs shall confirm to attached specification/data sheet. Junction Boxes shall be complete with busbar, support insulator, suitable for tentative cable sizes as indicated below & shall be supplied along with FLP type double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (2 runs of Incoming cable size 3C x 300 sqmm /2 runs of Outgoing Cable shall be 3C x 95 sqmm, XLPE insulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables.) |
| 214 | Supply of Double compression, weather proof (Non FLP), brass cable glands suitable for following XLPE/PVC , FRLS cable sizes & as per relevant IS for Indoor/outdoor use. |
| 215 | 3.5Cx 400 mm2 A2XFY |
| 216 | 3.5Cx 95 mm2 A2XFY |
| 217 | 3.5Cx 35 mm2 A2XFY |
| 218 | 3.5Cx 25 mm2 A2XFY |
| 219 | 3.5Cx 16 mm2 A2XFY |
| 220 | 3.5Cx 10 mm2 A2XFY |
| 221 | 3.5Cx 6 mm2 A2XFY |
| 222 | Supply of five-star rated split air conditioners, 2 TR capacity, complete with indoor and outdoor units, inverter compressor, cordless remote controller, programmable timer / controller logic arranged such that only two air conditioners can operate simultaneously, with automatic changeover to allow operation of the next two units, including all standard accessories, interconnecting piping kit, control wiring, mounting hardware, vibration pads, and OEM standard protections, suitable for continuous operation on 230 V, 50 Hz supply, complete in all respects, for supply only. |
| 223 | Supply of indoor type,surface/recess type 36 W LED fixture with including wiring light fixturecomplete in all respects Suitable for indoor |
| 224 | Design, Supply of indoor type,surface/recess type 110V DC light 36 W LED fixture with suitable size of JB including wiring light fixture complete in all respects. Suitable for indoor |
| 225 | PART B: INSTALLATION, TESTING & COMMISSIONING OF ELECTRICAL ITEMS: |
| 226 | VCB PANEL |
| 227 | Installation, testing & commissioning of 11 kV,630 A, 40 KA for 1 sec, two incomer and buscouple ras per sld,in door type metal clad rawout type comprising of metering and protection system including numerical relay,auxiliary relay, CTs, PTs , indication lamp, switches along with operating mechanism, all accessories, auxiliaries etc complete in all respects as specified in technical specification, data sheet SLD |
| 228 | LV SWITCHBOARDS / DISTRIBUTION PANELS / DISTRIBUTION BOARD/BUSDUCT |
| 229 | Installation, testing & commissioning of sheet steel enclosed, floor mounted, compartmentalised, free standingswitch-boards, including transportation from store/yard to site at the place of installation, unpacking, assembly, includingmounting and wiring of loose parts supplied by equipment vendor, interconnection of shipping sections and requisite inter-panel wiring between shipping sections, including supply of foundation base material frame & its fixing by welding onfoundation insert plates or angles embedded in the foundation, (The base frame supply cost shall be included in steelfabrication, however, fixing cost shall be included in this item cost.), placing on foundation channel, aligning,plumbing,leveling, positioning,bus bar bolting between transportation sections, bolting / tack welding with foundation channelsof various shipping section of panels including supply of GI bolts, nuts and washers etc., assembling of shipping sections,connection of inner panel busbars, checking of terminal connection for tightness and proper wiring, including all labour andmaterials, as per attached specification of this tender and directions of Engineer-in-Charge. Panel shall be with hinged doors, with neoprene gasket, 2 Nos earth terminal shall be provided at the Panel frame withextension link for earthing connections, with pad locking arrangement & along with Weather proof double compression Niplated brass cable glands and lugs for all incoming and outgoing feeders. Incoming & outgoing feeders with ACB/MCCB,CTs/PTs, Relays/ Contactors, meters, space heaters, MFM, selector switches, indication lamps etc.as per applicable SLDs. The Panel will have IP-42 rating degree of protection or otherwise specified in respective item. Colour shade of final paint shallbe RAL 7032 or as approved by IOCL.The item is inclusive of the stenciling/ lettering of the LT/HT Panel Boards/Control Panels/LDBs & PDBs/Motors etc. Suitabledouble compression glands to be supplied with all switchboards and panels. |
| 230 | PMCC-01-5000 Amp with Dual Incomer415V PMCC : Installation, testing & commissioning of CRCA sheet steel enclosed, floor mounted, free standingPMCC Switch Board, 415V, 50 Hz, 3 Ph, 4 Wire, 5000 Amp, 65kA for 1 sec. AL. bus bar including transportation from store/yardto site at the place of installation, unpacking, assembly, including mounting and wiring of loose parts supplied by equipmentvendor, interconnection of shipping sections and requisite inter-panel wiring between shipping sections, including installationon foundations or steel structures, aligning, leveling, grouting, testing and calibration of relays and meters etc., including alllabour and materials, as per attached specification and Single Line Diagram of this tender and directions of Engineer-in-Charge. (Location: Substation/PMCC) |
| 231 | PMCC-02 -Dual Incomer with 4000 Amp415V PMCC : Installation, testing & commissioning of double front PMCC panel of rating 4000 Amp (Dual Incomer) CRCA sheet steel enclosed, floor mounted, free standing PMCC Switch Board, 415V, 50 Hz, 3 Ph, 4 Wire, 65 kA for 1 sec. AL. bus bar including transportation from store/yard to site at the place of installation, unpacking,assembly, including mounting and wiring of loose parts supplied by equipment vendor, interconnection of shipping sections and requisite inter-panel wiring between shipping sections, including installation on foundations or steel structures, aligning,leveling, grouting, testing and calibration of relays and meters etc., including all labour and materials, as per attached specification and Single Line Diagram of this tender and directions of Engineer-in-Charge. (Location: Substation/PMCC) |
| 232 | Emergency Distribution Board - 1000A with two Incomers415V EDB : Installation, testing & commissioning of emergency distribution board of rating 1000 Amp (DualIncomer) CRCA sheet steel enclosed, floor mounted, free standing Emergency Switch Board, 415V, 50 Hz, 3 Ph, 4 Wire, 1000Amp,35 kA for 1 sec.. AL. bus bar including transportation from store/yard to site at the place of installation, unpacking, assembly,including mounting and wiring of loose parts supplied by equipment vendor, interconnection of shipping sections and requisiteinter-panel wiring between shipping sections, including installation on foundations or steel structures, aligning, leveling,grouting, testing and calibration of relays and meters etc., including all labour and materials, as per attached specification andSingle Line Diagram of this tender and directions of Engineer-in-Charge. (Location: Substation/PMCC) |
| 233 | AUTOMATIC POWER FACTOR CORRECTION PANEL (APFC PANEL)Installation, testing & commissioning of CRCA sheet steel enclosed, floor mounted, free standing indoor APFCPanel 415 V,TPN 50 kA for 1.0sec, with detuned filter of 700 kVAR in steps of (3 X 100 kVAR, 2 X 75 kVAR, 2 X 50 kVAR & 2X 20 kVAR. 3 X10kVAR, 5 x 4 kVAR ) with automatic correction of Power Factor. ACBs shall be darwout type with single front type indoor with operating mechanism, all accessories, auxiliaries and all other necessary components for smooth operation including transportation from store/yard to site at the place of installation, unpacking, assembly, including mounting and wiring of loose parts supplied by equipment vendor, including installation on foundations or steel structures, aligning, leveling, grouting, testing and calibration of relays and meters etc., including all labour and materials, etc complete in all respects as specified in technical specification,data sheet & SLD of APFC of this tender, and directions of Engineer-in-Charge |
| 234 | POWER DISTRIBUTION BOARD (PDB)-400 Amp415V EDB : Installation, testing & commissioning of power distribution board of rating 400 Amp (DualIncomer) CRCA sheet steel enclosed, floor mounted, free standing Emergency Switch Board, 415V, 50 Hz, 3 Ph, 4 Wire, 400Amp,25 kA for 1 sec.. AL. bus bar including transportation from store/yard to site at the place of installation, unpacking, assembly,including mounting and wiring of loose parts supplied by equipment vendor, interconnection of shipping sections and requisiteinter-panel wiring between shipping sections, including installation on foundations or steel structures, aligning, leveling,grouting, testing and calibration of relays and meters etc., including all labour and materials, as per attached specification andSingle Line Diagram of this tender and directions of Engineer-in-Charge. (Location: Substation/PMCC) |
| 235 | MOV-DBInstallation, testing & commissioning of CRCA sheet steel enclosed, floor mounted type MOV-DB ,415V, 50 Hz, 3 Ph, 4 Wire,63 Amp, TPN, 25 kA for 1 sec. AL. bus bar, IP 55,outdoor & weatherproof type, CRCA sheet,distribution board with incomer MCCB including transportation from store/yard to site at the place of installation, unpacking,assembly, including mounting and wiring of loose parts supplied by equipment vendor, including installation on foundations or steel structures, aligning, leveling, grouting, testing and calibration of relays and meters etc., including all labour and materials, as per attached specification and Single Line Diagram of this tender and directions of Engineer-in-Charge.I/C : 63A, 4P MCCB, Outgoing : 18 nos. 16A 4P MPCB. |
| 236 | BUSDUCTInstallation, testing & commissioning of BUS DUCT of 5000A, TPN, Non-segregated, 415V, 50 Hz, 65 kA for 1 sec., TPN, Al Bus Duct, Horizontal bends and Vertical bends with CRCA sheet steel enclosure including necessary equipment connection flanges, wall entrance seals, transformer/ equipment adaptor box, elbows, offsets, wall supports, flexible connectors, phase crossover chamber (if any), inspection cover, supporting insulator,expansion joint, rubber bellow, aluminium flexibles, space heater, all supporting structure, seal of bushing and all other accessories., etc. including storing, transportation from store/yard to site at the place of installation, unpacking, positioning in place, site assembly of loosely furnished accessories, including connection of auxiliary circuits, including fixing of nuts and bolts etc. including all labour and materials, as per attached specificatiions of this tender and directions of Engineer-in-Charge. (Location: Substation) |
| 237 | Installation, erection, testing and commissioning of the 415 V VFD panel for 200 kW motor including placement, alignment, power and control cable termination, earthing, PLC and VFD parameter setting, interlocking with field devices, functional testing under no-load and load conditions, performance verification and final commissioning, in accordance with approved documents, complete in all respects, for installation only. |
| 238 | LIGHTING DISTRIBUTION BOARDS |
| 239 | Installation, testing, and commissioning of 415V/240V lighting/power DB, Surface/Recess mounting type sheetsteel enclosure of approved make having 4 Pole MCCB/MCB with current limiting 25 kA (LSIG)/RCCB/ELCB as incoming and SP/DP/TP MCB (10kA/16kA type) for out going circuit complete with wiring,indication lamp, ammeter etc includingtransportation from store/yard to site at the place of installation, unpacking, assembly, including mounting and wiring of looseparts supplied by equipment vendor, testing and calibration of relays and meters etc., all labour and materials as perspecification, Single Line Diagram of this tender and the direction of Engineer-in-charge. The Panel will have IP-42 rating for indoor and IP 65 for FLP & IP-55 for outdoor type or otherwise specified in respective item. Colour shade of final paint shall be RAL 7032 or as approved by IOCL. |
| 240 | Main Lighting Distribution Board (MLDB): Installation, testing & commissioning of CRCA sheet steel enclosed, floor mounted, free standing LightingBoard, 415V, 50 Hz, 3 Ph, 4 Wire, 400 Amp, 25kA for 1 sec. Cu. bus bar, single front, fixed type microprocessor based MCCBs,compartmentalized, Indoor, with Incomers and Outgoing feeders, Metering and protection, MCCBs (LSIG protection),distribution board with incomer,indicating lamps, main contactor & auxiliary contactors etc including transportation fromstore/yard to site at the place of installation, unpacking, assembly, including mounting and wiring of loose parts supplied byequipment vendor, interconnection of shipping sections and requisite inter-panel wiring between shipping sections, includinginstallation on foundations or steel structures, aligning, leveling, grouting, testing and calibration of relays and meters etc.,including all labour and materials, as per attached specification and Single Line Diagram of MLDB of this tender and directionsof Engineer-in-Charge. Panel shall be suitable for bottom cable entry for incoming / outgoing feeders. along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders |
| 241 | Flame Proof Indoor Lighting Distribution Board (ILDB):TLF & PHInstallation, Testing & Commissioning of 415V, 50 Hz, 3 Ph, 4 Wire, 32 A, 10 kA for 1 sec.Cu busbar, IP-65,Indoor Type, 'Ex-d' type suitable for Zone-2, Gas Group-IIA/ IIB/ IIC, Temperature Class-T3, Aluminium alloy (LM6) enclosure,wall or frame mounted, IP 65, Weatherproof ,Non-compartmentalised, Double door, Lighting Panels along with Flameproof proof double compression Ni plated brass cable glands and lugs suitable for bottom cable entry, incomer and outgoing feeders, with indication lamp, etc complete in all respect as per attached SLD, Specification, Data sheet of this tender.Incomer : 1 No. 32A, 4P RCBO (30mA sensitivity)Outgoing : 9 Nos. 16A, SPN MCBs |
| 242 | Indoor Lighting Distribution Board (ILDB):For Control & Customer Care RoomInstallation, Testing, & Commissioning of 415V, 50 Hz, 3 Ph, 4 Wire, 32A, 10 kA for 1 sec. Cu busbar, IndoorType, Floor/Wall mounted Lighting Panel IP42, CRCA sheet steel enclosure, wall or frame mounted, Non-compartmentalised, Double door, Weatherproof, along with Weatherproof double compression Ni plated brass cable glands andlugs and sheet steel canopy, suitable for bottom cable entry, incomer and outgoing feeders, with indication lamp, etccomplete in all respect as per attached SLD , Specification, Data sheet of this tender.Incomer : 1 No. 32A, 4P RCBO (30mA sensitivity)Outgoing : 9 Nos. 16A, SPN MCBs |
| 243 | Indoor Lighting Distribution Board (ILDB):For Store RoomInstallation, Testing, & Commissioning of 415V, 50 Hz, 3 Ph, 4 Wire, 16A, 10 kA for 1 sec. Cu busbar, IndoorType, Floor/Wall mounted Lighting Panel IP42, CRCA sheet steel enclosure, wall or frame mounted, Non-compartmentalised, Double door, Weatherproof, along with Weatherproof double compression Ni plated brass cable glands andlugs and sheet steel canopy, suitable for bottom cable entry, incomer and outgoing feeders, with indication lamp, etccomplete in all respect as per attached SLD , Specification, Data sheet of this tender.Incomer : 1 No. 16A, 4P RCBO (30mA sensitivity)Outgoing : 3 Nos. 6A, SPN MCBs |
| 244 | Flame proof Outdoor Lighting Distribution Board (OLDB):Installation, Testing & Commissioning of 415V, 50 Hz, 3 Ph, 4 Wire, 63 A, 10 kA for 1 sec. cu busbar, IP-65,Indoor Type, 'Ex-d' type suitable for Zone-2, Gas Group-IIA/ IIB/ IIC, Temperature Class-T3, Aluminium alloy (LM6) enclosure,wall or frame mounted, IP 65, Weatherproof with Canopy, Non-compartmentalised, Double door, Lighting Panels along withFlameproof proof double compression Ni plated brass cable glands and lugs suitable for bottom cable entry, incomer andoutgoing feeders, with indication lamp, etc complete in all respect as per attached SLD, Specification, Data sheet of thistender.The lighting shall be Incomer : 1 No. 63A, 4P MCCB (30mA sensitivity)Outgoing :2 Nos. 32A, TPN ,3 Nos. 16A, SPN MCBs (with timer) 2 Nos. 32A, TPN ,3 Nos. 16A, SPN MCBs (without timer) |
| 245 | Local control station (LCS) |
| 246 | Installation, testing and commissioning of following Industrial type LCS, Weatherproof, Flameproof “Ex-d”(suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2), IP 65, Local Control Station suitable forWall / Column / Structure mounting. All LCS shall be made up of Aluminium alloy (LM6 grade) with Canopy of 14 gauge CRCAsheet with side cover. LCS shall confirm to attached specification/data sheet. LCS shall be supplied along with FlameproofDouble compression, Ni plated brass cable glands & lugs as per attached specification of this tender. |
| 247 | FLP (Zone-1, IIA/IIB, T3) IP65 Local control station provided with recess type START STOP PB, Suppressed scale Ammeter & 1no. mushroom head stay put type emergency stop PB with Keys/lock & pin arrangement, Local remote switch (with additionalcontacts to give the status of Local remote switch to DCS/PLC) including flameproof double compression stainless steel cableglands & plugs, suitable for outdoor installation as required as per attached specifications of this tender. |
| 248 | Break glass type Emergency Trip Push Button (ETPB) for transformer: weather proof emergency stop push button(EPB) with ON-OFF LED indication break glass type enclosure, 3mm thick CRCA canopy, weatherproof double compression Nickel Plted Brasscable glands(2 nos.) and 1NO+1 NC contact. |
| 249 | JUNCTION BOX (JBs) |
| 250 | JUNCTION BOXES FOR PUMP MOTOR (WEATHER PROOF, FLAME PROOF): Installation, testing & commissioning of following 415V, 3P, Industrial type, Weatherproof, Flame proof “Ex-d”(suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2), IP 65 suitable for Wall / Column / Structuremounting including cabling from JB to terminal box for VFD pump motor connection.All JBs shall be made up of cast Aluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA sheet with side cover. JBs shall confirm to attached specification/data sheet. Junction Boxes shall be complete with busbar of suitable rating, support insulator, suitable for tentative cable sizes as indicated below & shall be supplied along with FLP type double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (2 runs of Incoming cable size 3C x 240 sqmm /2 runs of Outgoing Cable shall be 3C x 185/150 sqmm, XLPE insulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables.) |
| 251 | JUNCTION BOXES FOR LIGHTING FIXTURES (WEATHER PROOF, NON-FLAME PROOF): Installation, testing & commissioning of following 16A, 240V, 4-way, Ph-N, Industrial type, Weatherproof, IP 65suitable for Wall / Column / Structure/ Pole mounting. Including wiring from JB to Fixture with terminals block with additionalearthing terminals and end clamps etc. All JBs shall be made up of cast Aluminium alloy (LM6 grade). JBs shall confirm to attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be supplied along with Double compression cable glands, Ni plated brass cable glands, lugs & plugs, PVC shrouds. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPEinsulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. |
| 252 | JUNCTION BOXES FOR LIGHTING FIXTURES (WEATHER PROOF, FLAME PROOF): Installation, testing & commissioning of following 16A, 240V, 4-way, Ph-N, Industrial type, Weatherproof, IP 65suitable for Wall / Column / Structure/ Pole mounting. Including wiring from JB to Fixture with terminals block with additionalearthing terminals and end clamps etc. All JBs shall be made up of cast Aluminium alloy (LM6 grade) Flameproof “Ex-d” (suitable for hazardous area of gas groupIIA/IIB, temperature class T3 and Zone-2). JBs shall confirm to attached specification/data sheet. Junction Boxes shall besuitable for cable sizes tentatively as indicated below & shall be supplied along with Flameproof double compression, Ni platedbrass cable glands, lugs & plugs, PVC Shrouds. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPEinsulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. |
| 253 | CANOPY FOR JBS/LCS/FIELD EQUIPMENTS.Installation,testing & commissioning of of Sheet steel canopies made of 14 gauge CRCA sheet with side cover, PU painted to beprovided as applicable for junction boxes, local control stations and others electrical equipment's located outdoor.Note: This items is applicable as per site requirement and direction of Engineering-in charge. |
| 254 | JUNCTION BOXES FOR POWER SOCKETS (WEATHER PROOF, FLAME PROOF): Installation, Testing & Commissioning of following Industrial type, Weatherproof, IP 65 suitable for Wall /Column / Structure mounting JBs with terminals block with additional earthing terminals and end clamps etc. All JBs shall be made up of cast Aluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA with side cover, Flameproof “Ex-d”(suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2). JBs shall confirm to attachedspecification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be suppliedalong with Flameproof Double compression, Ni plated brass cable glands, lugs & plugs, PVC shrouds. However, exact cable sizesshall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPEinsulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. 16A, 415V,TPN, 6-way |
| 255 | JUNCTION BOXES FOR POWER SOCKETS (WEATHER PROOF, NON-FLAME PROOF): Installation, Testing & Commissioning of following Industrial type, Weatherproof, IP 65 suitable for Wall /Column / Structure mounting JBs with terminals block with additional earthing terminals and end clamps etc. All JBs shall be made up of cast Aluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA with side cover. JBs shall confirmto attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall besupplied along with Weatherproof Double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizesshall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPEinsulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. 16A, 415V,TPN, 6-way |
| 256 | EARTHING SYSTEM |
| 257 | Installation, testing & Commissioning for complete earthing, earth electrodes/ pit, earth main ring, earthing ofelectrical equipment, instrument panels, field instruments, with heavy duty perforated GI pipe electrode / Copper PlateElectrode, providing suitable earth bus for interconnection, SS nut bolts to be used for Copper earthing and clamps of the GIearthing which are operated on regular basis i.e. clamp connections at top, providing a mixture of salt & charcoal, making RCC/Brick earth pit chamber and associated civil works as per standard Drg. etc. all complete as per specification & direction ofSite-In-charge.Item also includes Supply and fixing of Earth resistance display board of size 450 X 300 mm with 3mm thick AluminiumComposite Material (ACM)/ Aluminium Composite Panel (ACP) bolted to 25 X 25 X 5 mm (with 2 bolts MS angle section, 60 cmlong (minmum 200 mm embedded in ground). The rate shall also include supply and pasting of UV resistant vinyl sticker havingdetails as per Site-in-charge. |
| 258 | Earth Pits- Earth electrode with following sizes: 100 mm dia, 3.8 M long heavy duty perforated GI pipe electrode (Galvanisation is 610 gms/sq. mtr or as per IS-4759/ISO 1461.) as per IS:3043 |
| 259 | GI Strip (75 x 10) mm |
| 260 | GI Strip (50 x 6) mm |
| 261 | GI Strip (25 x 3) mm |
| 262 | Installation & Laying, testing & commissioning of GI wire / rope 10 Sq mm including nut bolt, washer,lugs and all balance earthing material as per the specification. |
| 263 | Installation & Laying, testing & commissioning of 8 SWG GI wire rope including nut bolt, washer,lugs and all balance earthing material as per the specification. |
| 264 | Installation & Laying,testing & commissioning of 25mm square copper strip/braided flexible cable |
| 265 | laying / fixing 1C x6 sq mm green colur copper flexible cable for earthing of fitting |
| 266 | laying / fixing 1C x 150 sq mm green colur copper flexible cable for earthing |
| 267 | Erection and commissioning of 16 Ways GI. Earthing Plate -Thickness 12 mm, LENGTH 1000 mm |
| 268 | Installation, testing & commissioning of lightning conductor finial made of 25 mm dia 1800 mm long GI tube having single prong at top with 85 mm dia 3 mm thick GI base plate including holes etc. complete as required. |
| 269 | Installation, testing & commissioning of 50 x 6 strip fixing saddles for ligtning protection complete with otheraccessories as required. |
| 270 | Installation, testing & commissioning of square tape clamp for ligtning protection complete with other accessories asrequired. |
| 271 | Installation, testing & commissioning of test link box for ligtning protection (for connection of each down conductor toearth pit) complete with other accessories as required. |
| 272 | HT CABLE & TERMINATION KIT |
| 273 | Installation, testing & commissioning of 11 kV(E) grade, stranded, multicore, Al. Conductor, conductor scrren, XLPE insulated, Insulation screen, PVC inner sheath, steel wire armoured, PVC outer sheathed H.T. power cables as per IEC 60502-2 / IS 7098-2 offollowing sizes in ground/tray including fixing of strip number tags, fixing of saddles and saddle bars, protective tiles etc.including transportation from store/yard to site at the place of installation, unpacking, including all labour and materials, asper attached specification of this tender and directions of Engineer-in- charge. Before procurring the cable, Contractor tomake cable schedule as per site conditions and get approved by IOCL/Consultant.The item also includes cable Tag 2mm thick Aluminium with No. punched on it and shall be securely attached to the cable bynot less than two turns of 20 SWG GI wire conforming to IS 280. |
| 274 | 3C X 300 mm2 11 kV (E) Grade Cable |
| 275 | Installation, testing and commissioning of outdoor termination kit for 3C X 300 mm2 11 kV (E) Grade Cable. |
| 276 | Installation, testing and commissioning of indoor termination kit for 3C X 300 mm2 11 kV (E) Grade Cable. |
| 277 | Installation, testing and commissioning Jointing kit for 11/11kV 3Cx300 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed |
| 278 | LT CABLE STRAIGHT THROUGH JOINT |
| 279 | Installation, testing and commissioning of Providing straight through joint of following 1.1 KV grade XLPE insulated armoured cable with M-Seal make jointing kit, and other jointing material, etc. all complete including supply of all materials as per specification & direction of Engineer In-charge. |
| 280 | 3.5 Core x 185 mm2 A2XFY |
| 281 | 3.5 Core x 150 mm2 A2XFY |
| 282 | 3.5 Core x 120 mm2 A2XFY |
| 283 | 3.5Cx 95 mm2 A2XFY |
| 284 | 3.5Cx 70 mm2 A2XFY |
| 285 | 3.5Cx 50 mm2 A2XFY |
| 286 | 3.5Cx 35 mm2 A2XFY |
| 287 | 4Cx 25 mm2 A2XFY |
| 288 | 4Cx 16 mm2 A2XFY |
| 289 | 4Cx 10 mm2 A2XFY |
| 290 | 4Cx 6 mm2 A2XFY |
| 291 | 4Cx 4 mm2 2XWY |
| 292 | 4Cx 2.5 mm2 2XWY |
| 293 | 3Cx 2.5 mm2 2XWY |
| 294 | 7C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 295 | 12C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 296 | LT POWER CABLE |
| 297 | LT Power Cables (FRLS): Installation, testing and commissioning , restoration of 1.1kV grade, XLPE insulated, stranded Cu / Al.Conductor, steel wire/strip (for multi core) armoured, for power cable, control cable and signal cable, PVC sheathed, FRLSpower and control cables (conforming to IS:7098 and tender specification) along with Glanding & Cable termination,connection of Double compression nickel plated brass Cable gland (FLP/Weather proof gland as per requirement) and nickelplated lugs & termination, silicon based jointing kit as per cable schedule(will be provided detail engineering) of following sizesin ground/trenches/tray, pulling through pipes and its proper sealing etc. including fixing of strip number tags, fixing of saddlesand saddle bars, protective tiles etc. including transportation from store/yard to site at the place of installation, unpacking,including all labour and materials, and completeness with all aspect as per attached specifications directions of Engineer-in-charge.The item includes cable Tag 2mm thick Aluminium with No. punched on it and shall be securely attached to the cable by notless than two turns of 20 SWG GI wire conforming to IS 280. The same shall be attached @ max. 30m or at bends whichever islesser.Note: a) Before procuring cable, successfull bidder is required to prepare detailed BOQ, cable schedule & Drum Schedule of Cables asper site mesaurement and get approved by IOCL/Consultant. No extra payment shall be made for wastages.b) Payment shall be paid separately for Supply of FLP/WP Industrial Glands & termination Glands shall be supplied with PVC hood. Diameter of cable under armour and above armour shall be checked prior to ordering of glands. Glands shall be complete with double seal cone-grip arrangements and check nuts. |
| 298 | 1C x 630 mm2 A2XFY |
| 299 | 3.5Cx 185 mm2 A2XFY |
| 300 | 3.5Cx 150 mm2 A2XFY |
| 301 | 3.5Cx 120 mm2 A2XFY |
| 302 | 3.5Cx 95 mm2 A2XFY |
| 303 | 3.5Cx 70 mm2 A2XFY |
| 304 | 3.5Cx 50 mm2 A2XFY |
| 305 | 3Cx 240 mm2 A2XFY |
| 306 | 3Cx 185 mm2 A2XFY |
| 307 | 3Cx 2.5 mm2 2XWY |
| 308 | 4Cx 25 mm2 A2XFY |
| 309 | 4Cx 16 mm2 A2XFY |
| 310 | 4Cx 10 mm2 2XWY |
| 311 | 4Cx 6 mm2 2XWY |
| 312 | 4Cx 4 mm2 2XWY |
| 313 | 4Cx2.5 mm2 2XWY (For MOV) |
| 314 | 2Cx2.5 mm2 2XWY |
| 315 | 7C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 316 | 12C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 317 | Installation, testing and commissioning of Double compression, weather proof (Non FLP), brass cable glands suitable for following XLPE/PVC , FRLS cable sizes & as per relevant IS for Indoor/outdoor use. |
| 318 | 1C x 630 mm2 A2XFY |
| 319 | 3.5Cx 185 mm2 A2XFY |
| 320 | 3.5Cx 150 mm2 A2XFY |
| 321 | 3.5Cx 120 mm2 A2XFY |
| 322 | 3.5Cx 95 mm2 A2XFY |
| 323 | 3.5Cx 70 mm2 A2XFY |
| 324 | 3.5Cx 50 mm2 A2XFY |
| 325 | 3Cx 240 mm2 A2XFY |
| 326 | 3Cx 185 mm2 A2XFY |
| 327 | 3Cx 2.5 mm2 2XWY |
| 328 | 4Cx 25 mm2 A2XFY |
| 329 | 4Cx 16 mm2 A2XFY |
| 330 | 4Cx 10 mm2 2XWY |
| 331 | 4Cx 6 mm2 2XWY |
| 332 | 4Cx 4 mm2 2XWY |
| 333 | 4Cx2.5 mm2 2XWY (For MOV) |
| 334 | 2Cx2.5 mm2 2XWY |
| 335 | 7C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 336 | 12C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 337 | Installation, testing and commissioning of FLP double compression brass Cable Gland for hazardous area brass cable glands suitable for following XLPE/PVC , FRLS cable sizes & as per relevant IS for Indoor/outdoor use. |
| 338 | 1C x 630 mm2 A2XFY |
| 339 | 3.5Cx 185 mm2 A2XFY |
| 340 | 3.5Cx 150 mm2 A2XFY |
| 341 | 3.5Cx 120 mm2 A2XFY |
| 342 | 3.5Cx 95 mm2 A2XFY |
| 343 | 3.5Cx 70 mm2 A2XFY |
| 344 | 3.5Cx 50 mm2 A2XFY |
| 345 | 3Cx 240 mm2 A2XFY |
| 346 | 3Cx 185 mm2 A2XFY |
| 347 | 3Cx 2.5 mm2 2XWY |
| 348 | 4Cx 25 mm2 A2XFY |
| 349 | 4Cx 16 mm2 A2XFY |
| 350 | 4Cx 10 mm2 2XWY |
| 351 | 4Cx 6 mm2 2XWY |
| 352 | 4Cx 4 mm2 2XWY |
| 353 | 4Cx2.5 mm2 2XWY (For MOV) |
| 354 | 2Cx2.5 mm2 2XWY |
| 355 | 7C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 356 | 12C x 2.5 mm2 Cu PVC insulated, FRLS PVC outer sheath, armored cable - control cable |
| 357 | MULTI CABLE TRANSIT (MCT) Block |
| 358 | Multi Cable Transit (MCT) Blocks: Installation, testing and commissioning of MCT block with SS Frame with EPDM Modules, Stay plate, Compression wedge, Lubricant etc complete with all accessories for following area as per the respective cable schedule/sizes for cable entry Buildings (Control Room, PMCC, Admin Building, Invoice Room, Security Room, Driver's Rest Room & any other etc) with minimum 30% spare.MCT blocks for future cable entry along with frame and mounting accessories complete as per specification of tender. |
| 359 | MCT Block (for LT Power Cables- 24 incomer/outoging Cables + 30% Spare blocks ) |
| 360 | MCT Block (for LT Power cables -12 incomer/outoging Cables + 30% Spare blocks) |
| 361 | OUTDOOR LIGHT FITTINGS : |
| 362 | Installation, Testing & Commissioning of flameproof/weatherproof Luminaries (lighting fixtures) of approvedmakes as per the specification including receiving from store, transporting to erection site including handling, arrangement oftransport vehicle, unpacking, inspection, checking of internal wiring, cable glanding and termination, crimping of lugs andconnections at fixtures/ control gears, supply of all erection materials including necessary GI hardware, GI clamps, GI brackets,civil masonry materials, testing of following types of lighting fixtures with all their parts and accessories etc, including fixing oflamps, all work, labour and materials, complete as per drawings and specification of this tender and directions of Engineer incharge.The item also includes the design & submission of the design/LUX level report as per the provisions of OISD for the entire plantarea/sheds/buildings etc. including finalization of locations/coordinates of the high masts based on the selected lumanaires.The design must be submitted for approval from IOCL/PMC.(All Lighting fixtures shall be provided with required no. of double compression nickle plated brass cable glands, lugs andstopping plug.) |
| 363 | Outdoor area lighting, Weatherproof and Flame proof (Ex\\"d\\" suitable for Gas group IIA/IIB, T3, suitable for Zone 2) 110W LEDIndustrial flood light fixture suitable for 7 m Single/Double arm light pole, mountings enclosure with toughened glass, SS wireguard, stainless steel hardware, earthing terminal, installation hardware and all necessary accessories wired up to terminalbox, lamps & accessories, complete in all respects as per attached specifications / data sheet of the Tender. |
| 364 | Outdoor area lighting, Weatherproof 110W LED Industrial flood light fixture suitable for 7 m Single/Double arm light pole,mountings enclosure with toughened glass, SS wire guard, stainless steel hardware, earthing terminal, installation hardware andall necessary accessories wired up to terminal box, lamps & accessories, complete in all respects as per attached specifications/ data sheet of the Tender. |
| 365 | Outdoor type, Weatherproof and Flame proof (Ex\\"d\\" suitable for Gas group IIA/IIB, T3, suitable for Zone 2) 110 W LED well glass light fixture, mountings enclosure with toughened glass, SS wire guard, stainless steel hardware, earthing terminal, installationhardware and all necessary accessories wired up to terminal box, suitable for mounted on structure including wiring lightfixture complete in all respects. |
| 366 | Outdoor type, Weatherproof and Flame proof (Ex\\"d\\" suitable for Gas group IIA/IIB, T3, suitable for Zone 2) 110 W LED flood light fixture, mountings enclosure with toughened glass, SS wire guard, stainless steel hardware, earthing terminal, installationhardware and all necessary accessories wired up to terminal box, suitable for mounted on structure including wiring lightfixture complete in all respects. |
| 367 | LED Flood Light: Installation , Testing and commissioning of high-quality integrated LED Flood Light with a minimum system lumen of53000 Lm and system wattage of nominal 400W with a nominal efficiency 130 lumen/watt. CCT of 5700K with SDCM of < 5 andCRI : 70. The housing should be of non-corrosive high-pressure die-cast aluminum to with stand extreme environments. It shouldhave corrosion resistant powder coating to pass NSS of 500 Hrs. with PF > 0.95. Lifetime of 75K hours @L70. Product should besuitable for continuous operation (10-12 Hrs. per day). The Ingress protection should be minimum IP 66 with an IK rating of 08.Optical and control gear compartments shall be maintainable/replaceable without impacting the LED units. The access to theoptical and the gear compartment should be separate. While accessing the gear compartment, the optical compartment shouldnot be accessible. The Luminaire should have a 20 KV /10 kA SPD duly bolted in theLuminaire. The SPD should be able to sustain a minimum 15 hits of 10kA rating i.e., Total of 45 hits across all the three modes as per IEEE62.41.2. The Luminaire should have a breather to ensure that air balance inside and outside of the Compartment .The luminaireshould be of Class B Serviceability. The wattage of each LED should be greater than 1 watt and less than 3 Watt. Only highpower Single white LED chip with ceramic based suitable for outdoor use is allowed. Multi Chip , array multi die , midpower,Integrated arrays and COBs are not permitted. The High-power LED used in the luminaire shall be SMD type.The luminaire should be capable of withstanding voltage stress of 440V for 8 Hrs., should have an auto shutdown @ 325V and have an auto recovery feature. The Drivers should be a potted driver not a printed circuit board without casing, mounted inside the luminaire. The Dimension of the luminaires should be minimum 595 x 100 x418 mm and have a breather ensuring stable optical and thermal management. |
| 368 | Installation, testing & commissioning of outdoor type, FLP type 60 W LED well glass light fixture,for Mounted on structure including wiring light fixture complete in all respects. ssuitable for out door, Hazardous Zone-2 area. |
| 369 | LIGHT POLE AND HIGH MAST |
| 370 | Double arm Polygonal / Octagonal street pole:Installation and Commissioning of 7 Meter high galvanised Polygonal / Octagonal Street Light Pole with double arm 1500mm long bracket arm made up of 48 O.D.pipe with EN 8 grade Galvanised foundation bolts and anchor plate having fixing arrangement for mounting 1 Nos. of LED luminaries as per enclosed technical specifications. The item also includes suitable fixing/clamping arrangement made up of GI on the body of the Light Pole for fixing of requisite flameproof or weatherproof junction boxes with terminals block with additional earthing terminals including foundation and end clamps etc. including 4 Nos double compression cable glands / Plug, lugs with PVC shrouds suitable size of Cable (XLPE, FRLS), complete with all accessories suitable for Hazardous Zone-2 area alongwith associated jobs etc. The payment for the Junction Box, light fixtures, cables shall be made seperately. |
| 371 | Installation and Commissioning of 7 Meter high galvanised Polygonal / Octagonal Street Light Pole with Single arm 1500mm long bracket arm made up of 48 O.D.pipe with EN 8 grade Galvanised foundation bolts and anchor plate having fixing arrangement for mounting 1 Nos. of LED luminaries as per enclosed technical specifications. The item also includes suitable fixing/clamping arrangement made up of GI on the body of the Light Pole for fixing of requisite flameproof or weatherproof junction boxes with terminals block with additional earthing terminals including foundation and end clamps etc. including 4 Nos double compression cable glands / Plug, lugs with PVC shrouds suitable size of Cable (XLPE, FRLS), complete with all accessories suitable for Hazardous Zone-2 area alongwith associated jobs etc. The payment for the Junction Box, light fixtures, cables shall be made seperately |
| 372 | 30 Mtr. height High Mast Tower:Installation and testing and commissioning of 30 Mtr. height High Mast Tower (hot dip galvanized, base metalthickness not less than 4 mm), Outdoor type, with provision of 2x8 nos of 400 W NON FLP LED types of luminaires in two layersand its control gear box complete with accessories as per specifications/datasheet of Tender. The cost also includes supplyingand providing trailing cable of suitable size & length from Switch Plug & Socket at the foot of high mast to the junction box atthe top, Motor, suitable size double compression Ni plated brass cable glands and lugs, PVC shrouds, etc. Note:a) The civil works required for high mast foundations are included in scope of this item.b) The item includes the S/I of raising lowering system comprising double drum winch, 6mm diameter SS wire rope, trailingcable, connector, integral power tool motor, manual handle, junction box, lightening finial (Lightening arrestor), including lowintensity LED type double dome aviation obstruction light.c) Tenderers should note that junction box shall be provided at the top of the high mast as per specifications. Rates forlighting fixtures and earth pits shall be paid separately.d) Bidder to provide design and drawing for High Mast Tower and foundation of high mast tower.e) The high Mast system shall be suitable for wind speed of the location as per IS-875, with head frame, winch mountingbracket, luminaries carriage suitable to install 16 nos. 400W LED FLD in Symmetrical arrangement (0-360Deg). e) The scope includes the supply foundation bolts manufactured from EN 8 grade galvanised steel along with nuts, washers,anchor plate and common template.f) Provision of lowering/raising of light fixutures without removal of cable end termination, complete with accessories as perattached specification of this tender. |
| 373 | Flameproof Outdoor Feeder Pillar Panel:Installation and testing and commissioning of flameproof outdoor distribution board (Feeder Pillar Panel), madeup of cast Aluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA with side cover, IP-65, stand mounted, with timercontactor, Auto manual selector switch and control mcb, 1 no. 32A TPN MCB incomer, single dial time switch, 22A TP contactorfor the automatic switching of luminaries, power tool control with 2 no 9A contactors and raise lower push button, requiredcabling/termination from Panel to light fitting and required GI pipes, provision of Incoming, Outgoing and for Looping and FLPtype industrial socket with associated civil works like foundation etc. Note: Necessary Civil /Structural Works shall be paid seperately). |
| 374 | DCDB-Distribution Board |
| 375 | Installation, connection, testing, and commissioning of DCDB Sub-DB,110V 50 Hz, 1 Ph, ,16 Amp DP MCB, as per SLD, sheet steel enclosure of approved make having MCB as incoming and DP MCB for out going circuit complete with wiring,indication lamp,copper busbar etc including all labour and materials as per specification and the direction of Engineer-in-charge.16A DP MCCB as incomer and 6 nos 6A DP MCB as outgoing. |
| 376 | HDPE CABLE CONDUIT |
| 377 | Laying of HDPE Pipe of Heavy Duty type, High compression strength, IP 67 rated (DWC) Double wall corrugated HDPE Conduits as per IS:14930/IS:16205. Laying includes with GI pull wires inside the conduits &necessary ends to be filled with sealants, cutting, bending and similar works, supply of clamps, spacers, including all labour and materialscomplete as per drawings and directions of Engineer-In-Charge for the following sizes of HDPE Pipe in required length. |
| 378 | 50 mm NB |
| 379 | 100 mm NB |
| 380 | 150 mm NB |
| 381 | GI CABLE CONDUIT |
| 382 | Laying of B-class G.I. pipe conforming to IS: 1239 for cable protection inside concrete including cutting, bending and similar works and all labour and materials complete as per drawings and directions of Engineer-In-Charge for the following sizes of GI Pipe in required length |
| 383 | 50 mm NB |
| 384 | 100 mm NB |
| 385 | 150 mm NB |
| 386 | CABLE TRAY |
| 387 | Installation, Erection of following Hot Dip Galvanized Ladder/Perforated Type cable trays (as per IS 2629) including bends, tee, crosses,horizontal, insert plate, tray supports and vertical splices etc. as required, including supply of all G.I hardwares, civil works and its materials, all labour and material as required as per standard drawings, specification and direction of Engineer-in-charge.Perforated/Ladder type- 2.5 mm thick sheet steel & galvanized (86 microns) of following sizes:- |
| 388 | 600 x 100 mm wide - Ladder Type |
| 389 | 300 x 100 mm wide-Ladder Type |
| 390 | 600 x 100 mm wide - Perforated Type |
| 391 | 300 x 100 mm wide-Perforated Type |
| 392 | 150 x 100 mm wide-Perforated Type |
| 393 | 50 x 50 mm wide-Perforated Type |
| 394 | 1.6 mm thick Hot dip G.I. Cover of minumum 2.5 M length suitable for Cable tray of following sizes including clamps for fixing the cover to cable tray with all accessories. Minimum thickness of galvanisation shall be 910 gm/m2 |
| 395 | Top tray cover for perforated 50 mm |
| 396 | Top tray cover for perforated 150 mm |
| 397 | Top tray cover for perforated 300 mm |
| 398 | Top tray cover for perforated 600 mm |
| 399 | INDUSTRIAL POWER SOCKET OUTLETS WITH INTEGRAL PLUG TOPS (WEATHERPROOF, FLAMEPROOF TYPE): Installation, Testing & Commissioning of Power Socket outlets shall be Flame proof “Ex-d” (suitable forhazardous area of gas group IIA/IIB, temperature class T3 and Zone-2), Industrial type, (IP 65) interlocked with MCB and ELCBand suitable for loop-in loop-out entries for armoured cable as specified, enclosed with Cast Aluminium alloy (LM-6 grade), withstainless steel hardware, endless neo print gasket, 2nos. of cable entry, stopping plugs, earthing terminals, installationhardware and all necessary accessories wired upto terminal box. Integral plug tops shall be also supplied with the power socketoutlets.All switch sockets shall be provided with Canopy of 14 gauge CRCA sheet with side cover and required no. of FLP doublecompression Ni plated brass cable glands and FLP stopping plug as per attached specification sheets. |
| 400 | 415 V AC, 3 phase, 63A, (3P+N+E), 50 Hz |
| 401 | 16A. 230 V AC, 1 phase(1P +N+E), 50 Hz, |
| 402 | INDUSTRIAL POWER SOCKET OUTLETS WITH INTEGRAL PLUG TOPS (WEATHERPROOF, NON-FLAMEPROOF TYPE):Installation, Testing & Commissioning of Power Socket outlets shall be Non-Flame proof, industrial type (IP65)interlocked with MCB and ELCB and suitable for loop-in loop-out entries for armoured cable as specified enclosed with CastAluminium alloy (LM-6 grade) with stainless steel hardware, endless neo print gasket, 2nos. of cable entry, stopping plugs,earthing terminals, installation hardware and all necessary accessories wired upto terminal box. Integral plug tops shall be alsosupplied with the power socket outlets.All switch sockets shall be provided with Canopy of 14 gauge CRCA sheet with side cover and required no. of doublecompression Ni plated brass cable glands and stopping plug as per attached specification sheets. |
| 403 | 415 V AC, 3 phase, 63A, (3P+N+E), 50 Hz |
| 404 | 16A. 230 V AC, 1 phase(1P +N+E), 50 Hz, |
| 405 | Installation, testing and commissioning of the following including the supply of necessary clamp , bolts and hardware,Breaking and repair of walls, if required, and including all labour and materials complete as per directions of Engineer-In-Charge, applicable standards and Indian Electricity rules. |
| 406 | Vitreous enamel caution boards (HINDI/ ENGLISH) as per IS 2551 |
| 407 | 11 kV |
| 408 | 440 V |
| 409 | Shock treatment chart ( laminated type) as per IS:5216 in bilingual language (Hindi & English) duly laminated on a hard back ground to be hung at various places |
| 410 | Single Line Diagram consisiting of new and existing system complete in glass frame. |
| 411 | Installation & Laying of Insulating Mats 1.1kV grade (as per IS:15652 - 2006) of 1000mm width, required for maintenance of electrical equipment in station as required including cutting to required shape in running length and including all labour and materials etc. complete and as per directions of Engineer-In-Charge, as per applicable Indian or International standards and Indian Electricity Rules. |
| 412 | Laying of Rubber mat 11kv grade(as per IS15652/IEC61111) of (2 or 2.5mm thick X 0.9 or 1Mtr) required for maintenance of electrical equipment in station as required including cutting to required shape in running length and including all labour and materials etc. complete and as per directions of Engineer-In-Charge, as per applicable Indian or International standards and Indian Electricity Rules. |
| 413 | Installation de-rusting, fabricating, erecting, hoisting and fixing in position with necessary welding and/or bolting with MS bolts conforming to property class 4.6 or higher of I.S:1367 at all height as per approved fabrication drawings of all types of structural steel work in rolled steel joints, channels, angles, tees, flats, plates, lattice members built up / compound sections in columns, portals, girders, beams, bracings, trusses, purlins, rafters, staircase, steps, hand-railings, walkway, cat ladder with cages, toe plates, side walling, trestles, Conveyor gantries grating, chequred plate etc. including gusset plates, anchor plates etc., including site and shop fasteners, riveting, bolting, welding at shop or work site at all heights etc. & including applying approved coats of primers, undercoat and finish painting as per Technical specification. Complete as per drawing and direction of Owner / Consultant. (All material supply is in contractor’s scope including paints )Providing and applying Anticorrosive treatment to structural steel surface & painting as per specifications. |
| 414 | Fire extinguishers CO2 type in 4.5kg capacity complete with handle , fixing bracket etc. |
| 415 | Installation of Cable Route markers |
| 416 | Installation, testing and commissioning and fixing of Cable Route markers (30m interval) for HT Cable (11kV grade), CI material, 150mm Dia. Round with 5mm-6mm thickness, two holes for mounting, 3mm embossed lettering as appropriate, bolted/welded to 35mm x 35mm x 6mm angle iron, 600mm long and fixing the same in ground, including painting with all accessories all civil works, labour and materials complete as required and as per directions of Engineer-In-Charge. |
| 417 | Installation, testing and commissioning and fixing of Cable Route markers (30m interval) for LT Cable (415V grade), CI material, 150mm Dia. Round with 5mm-6mm thickness, two holes for mounting, 3mm embossed lettering as appropriate, bolted/welded to 35mm x 35mm x 6mm angle iron, 600mm long and fixing the same in ground, including painting with all accessories all civil works, labour and materials complete as required and as per directions of Engineer-In-Charge. |
| 418 | TRANSFORMER |
| 419 | Installation, testing, commissioning, shop testing, packing, transportation, delivery at storage of 3150 kVATransformer Oil Type copper winding: 3150 kVA (ONAN), 415V, 11/0.433 KV, Dyn11, Z =8%, OCTC +/- 10% @2. 5% , including transportation from store/yard to site at the place of installation, unpacking, positioning in place, site assembly of loosely furnished accessories, including connection of auxiliary circuits, including fixing of nuts and bolts etc.,consisting of all accessories, mandatory spares, erection & commissioning spare and recommended spares for 2 years operation and maintenance, including all labour and materials along with weather proof double compression Ni plated brass cable glands and cable lugs for outgoing cables and all other accessories for Transformer, complete in all respects as specified in technical specification, data sheet & Overall SLD of this tender and directions of Engineer-in-Charge.The supply includes first fill of transformer oil and all consumables. Transformer shall be complete with minimum accessories asfollows: Complete set of gaskets, Silica Gel Breather, set of valves, Buchholz relay, complete winding temperature indicatingequipment (WTI), Oil Temperature Indicating equipment (OTI), Pressure relief device with trip contacts, bushing of each type,CTs of each type for 51G & 64R as per attached Electrical Overall SLD and Oil Level Gauge etc. as per specification. CTs shall be provided as per SLD. (INCLUSIVE OF HEAT RUN TEST ) |
| 420 | Installation, testing, commissioning of 3150 kVA Transformer : 3150 kVA (ONAN), 415V, 11/0.433 KV, Dyn11, Z =8%, OCTC +- 10% @2. 5% tapping from HT VCB consisting of all accessories, mandatory spares, erection & commissioning spare and recommended spares for 2 years operation and maintenance,complete in all respects as specified in technical specification, data sheet & SLD. |
| 421 | All works relating to statutory approvals of the installation from competent authority like Electrical Inspectorate, CEA, DGMS,etc. including carrying out of all required modifications in design / Manufacturer / Installation to meet the requirement of Indian Electricity rules and other statutory regulations in force, carrying out necessary paper work to obtain all necessary clearances for charging of installation, statuatory fees, all fess as per relevant national standards. of Bitumen Plant on behalf of IOCL. |
| 422 | Installation, testing, commissioning, shop testing, packing, transportation, delivery at storage of 250 kVA,copper winding Cast resin Dry type transformer (Indoor), with 415Volt,50Hz input and 415 Volt output, along with Weatherproof double compression Ni plated brass cable gland and cable lugs for all incoming and outgoing cables, insulation class Htemperature class limited to class B, including transportation from store/yard to site at the place of installation, unpacking,positioning in place, site assembly of loosely furnished accessories, including connection of auxiliary circuits, including fixing ofnuts and bolts etc., consisting of all accessories, mandatory spares, erection & commissioning spare and recommended sparesfor 2 years operation and maintenance, including all labour and materials, complete in all respects as specified in technicalspecification, data sheet & Overall SLD of this tender and directions of Engineer-in-Charge . Transformer shall be complete with minimum accessories as follows: Complete set of gaskets, winding temperature indicatingequipment (WTI), bushing of each type etc. as per Specification/Data sheet/SLD.( INCLUSIVE OF HEAT RUN TEST ) |
| 423 | 110V DC system (Battery, Battery charger and DC DB) |
| 424 | Installation, testing and commissioning of 5 kVA 110V DC Battery Charger & DCDB System (IP-31) comprising110V DC Battery Bank for 30 mins back-up, Chargers, Battery isolator/MCCB of suitable rating & DC Distribution Board etc.which includes installation of metal stands, placing of batteries on stands on cell insulators, fixing the cell, interconnecting thebattery cells, cell booster and charging the battery cells as per attached specification of this tender .Suitable size of doublecompression glands shall be supplied with Battery Charger and DCDB. Vendor shall supply suitable battery of AH ratingcalculated as per duty cycle/load details attached with datasheet and submit the sizing calculation accordingly.Location: PMCCNOTE :Supervision of laying & termination of all inter-panel/ inter-cubicle cabling including cabling up to Battery Bank andinter-tier cabling of Battery Bank shall be in the scope of Supplier . However, supply, laying and termination of the cables shallbe done by the contractor. |
| 425 | DCDB :110V DC, 63A, Cu bus bar, DC DB shall be indoor TypeIncomer - 63A DC, DP MCCB Outgoing - 15 Nos. 16A DC, DP MCB, 6 Nos of 6 A DP MCB |
| 426 | DISMANTLING |
| 427 | Dismantling of existing transformer of rating 1600 kVA, 11/0.433 kV to execute the complete package. |
| 428 | Dismantling of existing load breaker switch of rating 11 kV installed at electrical PMCC room |
| 429 | Dismantling of existing MCC-01 panel of dual incomer with buscoupler of rating of rating 415V, 50Hz, 2500A 50 KA for 1 Sec of 14.6 mtr tentative length installed at existing electrical PMCC room. |
| 430 | Dismantling of existing busduct of rating 415V, 50Hz, 2500A 50 KA for 1 Sec., TPN Aluminium Non Segregated phase Bus Duct of indoor type enclosure with end termination at transformer end, PMCC end, wall frame assembly, supporting insulator,expansion joint, rubber bellow, aluminium/copper flexibles, space heater, all supporting structure, seal of bushing and all other accessories. |
| 431 | Dismantling of existing MCC-302 panel dual incomer with buscoupler of rating of rating 415V, 50Hz, 1000A 50 KA for 1 Sec of 10.6 mtr tentative length installed at existing electrical PMCC room. |
| 432 | Dismantling of existing MCC-303 panel of dual incomer with buscoupler of rating of rating 415V, 50Hz, 1000A 50 KA for 1 Sec of 6.9 mtr tentative length installed at existing electrical PMCC room. |
| 433 | Dismantling of existing MCC-304 panel of dual incomer of rating of rating 415V, 50Hz, 1000A 50 KA for 1 Sec of 10.5 mtr tentative length installed at existing electrical PMCC room. |
| 434 | Dismantling of existing MCC-305 panel of single incomer of rating of rating 415V, 50Hz, 1000A 50 KA for 1 Sec of 3 mtr tentative length installed at existing electrical PMCC room. |
| 435 | Dismantling of existing MCC GRADE VG-10/C panel of single incomer with buscoupler of rating of rating 415V, 50Hz, 630A 50 KA for 1 Sec of 5.75 mtr tentative length installed at existing electrical PMCC room. |
| 436 | installation, testing and commissioning of 11 kV(UE) grade, stranded, multicore, Al. Conductor, conductor scrren, XLPE insulated, Insulation screen, PVC inner sheath, steel wire armoured, PVC outer sheathed H.T. power cables as per IEC 60502-2 of following sizes in ground/tray including fixing of strip number tags, fixing of saddles and saddle bars, fixing of route markers, protective tiles etc. including transportation from store/yard to site at the place of installation, unpacking, including all labour and materials, as per attached specification of this tender and directions of Engineer-in- charge.Before procurring the cable, Contractor to make cable schedule as per site conditions and get approved by IOCL/Consultant. |
| 437 | 3C X 300 mm2 11 kV (UE) Grade Cable |
| 438 | Installation, testing and commissioning of outdoor termination kit for 3C X 300 mm2 11 kV (UE) Grade Cable. |
| 439 | Installation, testing and commissioning of indoor termination kit for 3C X 300 mm2 11 kV (UE) Grade Cable. |
| 440 | installation, testing and commissioning Jointing kit for 11/11kV 3Cx 300 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed |
| 441 | 3C X 400 mm2 11 kV (UE) Grade Cable |
| 442 | Installation, testing and commissioning of outdoor termination kit for 3C X 400 mm2 11 kV (UE) Grade Cable. |
| 443 | Installation, testing and commissioning of indoor termination kit for 3C X 400 mm2 11 kV (UE) Grade Cable. |
| 444 | JUNCTION BOXES FOR PUMP MOTOR (WEATHER PROOF, FLAME PROOF): installation, connection, testing & commissioning of following 415V, 3P, Industrial type, Weatherproof, Flame proof IP 65 suitable for Wall / Column / Structure mounting Including cabling from JB to terminal box of motorAll JBs shall be made up of cast Aluminium alloy (LM6 grade). JBs shall confirm to attached specification/data sheet. Junction Boxes shall be complete with busbar, support insulator, suitable for tentative cable sizes as indicated below & shall be supplied along with FLP type double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (2 runs of Incoming cable size 3C x 300 sqmm /2 runs of Outgoing Cable shall be 3C x 95 sqmm, XLPE insulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables.) |
| 445 | Installation, testing and commissioning of Double compression, weather proof (Non FLP), brass cable glands suitable for following XLPE/PVC , FRLS cable sizes & as per relevant IS for Indoor/outdoor use. |
| 446 | 3.5Cx 400 mm2 A2XFY |
| 447 | 3.5Cx 95 mm2 A2XFY |
| 448 | 3.5Cx 35 mm2 A2XFY |
| 449 | 3.5Cx 25 mm2 A2XFY |
| 450 | 3.5Cx 16 mm2 A2XFY |
| 451 | 3.5Cx 10 mm2 A2XFY |
| 452 | 3.5Cx 6 mm2 A2XFY |
| 453 | Installation, testing and commissioning of five-star rated split air conditioners, 2 TR capacity, including fixing of indoor and outdoor units, erection of mounting frames, laying and dressing of refrigerant copper piping with insulation, interconnecting control and power cabling, drainage piping, vacuuming, refrigerant charging, integration and setting of the timer / controller logic to ensure that only two air conditioners operate at a time with automatic changeover, functional testing, performance checks and handover, complete in all respects, for installation only. |
| 454 | Installation, testing & commissioning of indoor type,surface/recess type 36 W LED fixture with including wiring light fixturecomplete in all respects Suitable for indoor |
| 455 | Installation, testing &commissioning of indoor type,surface/recess type 110V DC light 36 W LED fixture with suitable size of JB including wiring light fixture complete in all respects. Suitable for indoor |
| 456 | PART C: CIVIL ITEMS |
| 457 | EARTHWORK |
| 458 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30 cm in depth, 1.5m in width) including taking out and disposal of excavated earth within or outside site to unobjectionable place/ unloading to approved municipal dumping ground and lift upto 1.5m, as directed by Engineer-in-charge. Disposed earth to be levelled and neatly dressed. Extra for levelling & neatly dressing of disposed soil completely to be paid separately as per item no. MPLCN00600. |
| 459 | All kinds of Soil including soft rock, Slush muddy / marshy / slushy soil / marine clay |
| 460 | Extra for every additional lift of 1.5m or part thereof in excavation or banking excavated or stacked materials in all kinds of soil |
| 461 | Filling (Back filling and area filling) available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, within premises and lift upto 1.5m |
| 462 | Supply & filling of local earth (including royalty) by mechanical transport also including ramming & watering of the earth in layers not exceeding 20cm in depth in plot, trenches, plinth, sides of foundations etc. complete |
| 463 | Supplying and filling in plinth with sand within specified grading zone of fine aggregates specified in table 3.1, clause 3.1.3 of attached specifications under floors, etc. in layers not exceeding 20cm in depth, each deposited layer to be compacted by ramming including watering, consolidating and dressing complete. |
| 464 | Local Coarse Sand within grading zone II/III |
| 465 | Manufactured Sand within grading zone II/III |
| 466 | Dry stone pitching 22.5 cm thick including supply of stones and preparing surface complete with proper Compaction (with stone of size 100mm to 150mm size) as approved by EIC. |
| 467 | Carriage charge for disposal of earth by mechanical means, including loading, transporting, stacking, unloading to approved municipal dumping ground / unobjectionable place as per direction of Engineer- in-Charge beyond IOCL Premises for all leads and including all lifts. |
| 468 | Distance upto 1 km |
| 469 | Distance > 1 km< 3 km |
| 470 | Extra for levelling & neatly dressing of disposed soil completely as directed by engineer in charge |
| 471 | Plain Cement Concrete |
| 472 | Providing and laying in position cement concrete of specified grade excluding cost of centering & shuttering. All work up to plinth level: |
| 473 | 1:4:8(1 Cement :4 Coarse Sand :8 Graded stone aggregate of 40mm) |
| 474 | Shuttering and Formwork |
| 475 | Centering and shuttering including strutting, propping etc. and removal of form for : |
| 476 | Foundations,footings,bases of columns, etc. for mass concrete |
| 477 | Walls (any thickness) including attached pilasters, buttress, plinth and string courses etc. |
| 478 | Suspended floors,roofs,landings,balconies, access platform and Shelves (Cast in situ) |
| 479 | Lintels, beams plinth beams,girders bressumers and cantilevers |
| 480 | Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 481 | Steel Reinforcement |
| 482 | Supply of Steel reinforcement for R.C.C. including straightening, cutting, bending, placing in position and binding all complete at all levels |
| 483 | Thermo Mechanically Treated Bars of Fe- 500D grade or more, conforming to IS1786 |
| 484 | Ready Mix Concrete |
| 485 | Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work using cement content as per approved design mix manufactured in fully automatic batching plant & transported to site of work in transit mixer for all leads having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering, shuttering, finishing & reinforcement including cost of admixtures in recommended proportions as per IS:9109 to accelerate/ retard setting of concrete, improve workability without impairing strength & durability as per direction of Engineer-in-charge (Note :- Cement content considered in this item is @ 330 kg/cum. Less cement used as per design mix (if any) will be recoverable separately. No extra payment against extra cement if used shall be payable. |
| 486 | M25 RMC for All works UP TO PLINTH LEVEL |
| 487 | M25 RMC for All works ABOVE PLINTH UPTO FLOOR 5 LEVEL |
| 488 | Brick work |
| 489 | Providing and laying Brick work with common burnt clay F.P.S (non Modular) bricks of class designation 7.5: |
| 490 | Brick work in Cement mortar 1:6 (1 cement: 6 coarse sand ) IN FOUNDATION AND PLINTH |
| 491 | Brick work in Cement mortar 1:6 (1 cement: 6 coarse sand) in superstructure in all shapes & sizes in superstructure ABOVE PLINTH & UP TO FLOOR V LEVEL |
| 492 | Plaster & Pointing |
| 493 | Providing and laying cement plaster on surfaces with fine sand including curing etc. |
| 494 | 12 mm cement plaster of mix 1:6 (1 cement: 6 fine sand) |
| 495 | Providing and fixing 150 mm wide Chicken Wire mesh between junctions of column/beam and walls, fixed with U nails 150 mm centre to centre before plastering the junction. |
| 496 | Structural Steel Works |
| 497 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 498 | Providing & fixing hand rail of approved size, welding etc. to steel ladder railing,balcony railing & staircase railing and similar works including applying priming coat of approved steel primer. |
| 499 | G.I. pipes |
| 500 | Structural steel work in built up sections/ framed work in gratings, frames, guard bar, ladder, railings, brackets, gates and similar works including cutting,hoisting,fixing in position & applying a priming coat of approved steel primer etc. as required. |
| 501 | Supplying, providing, shop fabricated, steel pressed lock, erection of galvanised electro forged gratings comprising of shaped, grating and stair treads out of steel using 25x5mm/6mm flat bars and 6mm MS twisted Bars as per requirements duly welded/fixed/clamped to base frame and as shown in relevant drawings including galvanizing of gratings as per enclosed specifications.Note:- Finished size of grating laid shall be measured for the purpose of payment. Pitch of the main flat bars(25x5mm) shall be 33-35mm and the pitch of the 6mm twisted rod (cross members) shall be 100mm, the outer frame of grating of all sizes shall be 25x5mm/6mm FB or as per approved drawing. |
| 502 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/ 10 sqm of approved brand or manufacture |
| 503 | Applying priming coat with ready mixed red oxide zinc chromate primer of approved brand & manufacture on steel galvanised iron/steel works |
| 504 | Hume Pipes |
| 505 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : Light Duty. |
| 506 | 100 mm dia. R.C.C. pipe |
| 507 | 150 mm dia. R.C.C. pipe |
| 508 | Supplying, filling, spreading & levelling stone boulders of size range 5 cm to 20 cm, in weep hole/ oil pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 509 | GROUTING MATERIAL |
| 510 | Providing grouting in pockets/ bases etc (As per Technical specification), cost of grouting, including supply of materials shall be covered in the unit rates. Rates shall include cost of labor, supervision, deployment of tools & tackles, consumables, materials and other associated arrangements required to execute all the related activities. Grouting using Free flow non shrinkable grout material CONBEXTRA GP-2 or approved equivalent etc |
| 511 | Flooring |
| 512 | 52 mm thick cement concrete flooring with concrete hardener topping under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound is mixed @2 litre per 50kg of cement or as per manufacturers specifications. This includes cost of cement slurry, 2 mm thick PVC strip at desired spacing, cost of nosing in steps etc. complete. |
| 513 | FALSE CEILING |
| 514 | Providing & Fixing 15mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture spintone/cosmos / Hexa or equivalent) of size 595 x 595 mm in true horizontal level suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main 'T' runner suitably spaced at joints to get required length and of size 24x38mm made from 0.33mm thick (minimum) sheet, spaced 1200mm centre to centre, and cross \\"T\\" of size 24x28mm made out of 0.33mm (Minimum) sheet, 1200mm long spaced between main'T' at 600mm centre to centre to form a grid of 1200x600mm and secondary cross 'T' of length 600mm and size 24 x28mm made of 0.33mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600mm panel to from grid of size 600x600mm resting on periphery walls / partitions on Perimeter wall angle pre- coated steel of size(24x24X3000mm made of 0.40mm thick (minimum) sheet with the help of rawl plugs at 450mm centre to centre with 25mm long dry wall screws @ 230mm interval and laying 15mm thick densified edges calcium silicate ceiling tiles of approved texture (Spintone/Cosmos/hexa) in the grid including,cutting/ making opening for services like diffusers, grills,light fittings, fixtures, smoke detectors etc., wherever required, Main 'T' runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6mm ceiling with 12.5 mm dia and 50mm long dash fasteners, 4mm G.I. adjustable rods with galvanised steel level clips of size 85x30x0.8 mm spaced at 1200mm centre to centre along main'T', bottom exposed with 24mm of all T-sections shall be pre-painted with polyester baked paint for all heights,as per specifications,drawings & as directed by engineer-in- charge. Note :- Only calcium silicate false ceiling area will be measured from wall to wall. No deduction shall be made for exposed frames /opening (cut outs) having area less than 0.30 sqm.The calcium silicate tile shall have NRC value of 0.50(Minimum), light reflection > 85%, non - combustible as per B.S. 476 part IV, 100% humidity resistance & also having thermal conductivity<0.043 w/mK |
| 515 | Providing & fixing partition upto ceiling height consisting of G.I. frame & required board including providing & fixing of frame work made of special section power pressed/ roll form GI sheet with zinc coating 120gm/sqm(both side inclusive) consisting of floor and ceiling channel 50mm wide having equal flanges of 32mm & 0.50mm thick fixed to the floor & ceiling at the spacing of 610mm centre to centre with dash fastener of 12.5mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48mm wide having one flange of 34 mm and other flange 36mm and 0.50 mm thick fixed vertically within flanges of floor and ceiling channel and placed at a spacing of 610mm centre to centre by 6mm dia bolts and nuts, including fixing of studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300 mm centre to centre. The boards are to be fixed to the frame work with joints staggered to avoid through cracks, Galvanised M.S. fixing channel of 99 mm width (0.9 mm thick having two flanges of 9.5 mm each with Zinc Coating of 120gm/sqm (both sides inclusive) to be provided at the horizontal joints of two boards, fixed to the studs using metal to metal flat head screws, including jointing and finishing to a flush finish with recommended jointing compound, jointing tape, angle beads at corner (25 mmx 25 mm x 0.5 mm), joint finisher and two coats of primer suitable for board as per manufacture's specification and direction of engineer in charge all complete |
| 516 | 75 mm overall thickness partition with 12.5 mm thick double skin fire rated glass reinforced gypsum (GRG) plaster board conforming to IS: 2095: part 3:1996 (Board With BIS Certification Marks). |
| 517 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS:1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions,at top, bottom & sides with with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing/panelling, C.P. brass/stainless steel screws including fixing all complete as per drawing & the directions of Engineer-in-charge. (Cost of glazing or panels to be paid for separately) |
| 518 | Fixed Glazing with Powder coated aluminium (minimum thickness of powder coating 50 micron) sections |
| 519 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes etc for fixing required door fittings, all complete as per direction of Engineer-in-charge (Door handle, lock and stopper etc. to be paid separately). |
| 520 | GI PIPE BELOW FLOORS |
| 521 | Supply, fabrication, laying and testing of GI, BLACK, ERW, threaded pipes, heavy class conforming to IS 1239, PART I as per IOCL specifications including pipeline fittings like bends, tee etc as required and as directed for Underground pipeline with doping |
| 522 | 100 mm dia |
| 523 | CHEQUERED PLATES |
| 524 | Supplying & Fixing of following items for electrical safety etc |
| 525 | 6 mm thick chequered plate on cable trench inside swtich room, earthing pit including cutting, painting, lifting hooks, etc |
| 526 | Disposal of Dismantling & unwanted material: |
| 527 | Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars & disposal of unserviceable material outside site to an unobjectionable place as/ direction of Engineer-in-charge |
| 528 | Carriage charge for disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, stacking, unloading to approved municipal dumping ground/unobjectionable place as/direction of Engg- in-Charge beyond IOCL Premises for all leads and including all lifts |
| 529 | Distance upto 1 km |
| 530 | Distance > 1 km< 3 km |
| 531 | Additional charges per km beyond 20 km over item MPLCN27105 |
| 532 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50mm including strengthening with 2mm dia GI wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge using hot dipped galvanised wire of 4mm dia (The rate for civil works for excavation, brick masonry, PCC shall be paid separately) Please Enable Macros to View BoQ information |