| 1 | E.I. Work (Part A) |
| 2 | DSR Item No.1.10Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 3 | Group C |
| 4 | DSR Item No.1.17 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 5 | 3 x 2.5 sq. mm |
| 6 | DSR Item No.1.21Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 7 | 25 mm |
| 8 | DSR Item No.1.32Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 9 | DSR Item No.2.4Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 10 | 4 way (4 + 12), Double door |
| 11 | DSR Item No.2.10Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 12 | Single pole |
| 13 | Triple pole and neutral |
| 14 | DSR Item No.2.15Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 15 | DSR ITEM NO. 5.1Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt) as required. |
| 16 | DSR ITEM NO. 5.8Supplying and laying 25 mm X 5 mm G.I Supplying and laying 25 mm X 5 mm copper strip at 0.50 meter below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 17 | Supply and laying of following PVC/XLPEinsulated and PVC sheathed copper Cond. Un Arm. & Served cable working voltage upto 1100 Volt. Grade of following size to be laid in existing trench / pipe. The job includes the cost of making connections with suitable size of copper Lugs / thimbles, testing, commissioning etc. as required to the entire satisfaction of Engineer in Charge. The cable should be of Grandlay/ Polycab/ Havells/ Finolex/ RR Kables/ KEI/ RPG/ Universal make only. |
| 18 | 35 Sq.mm 3.5 Core PVC Ar. Aluminum Conductor Cable |
| 19 | S/E of LED Bulk Head Luminaries weather proof frosted light with PMMA/ PC reflector and silicon gasket to be installed on surface. The LED fitting should have minimum system Lumen output minimum 1000 Lumen at 100 lm/ watt (minimum) and the driver of the fitting should be workable on 140-260 Volt. The colour temperature of LED should be minimum 5000 degree Kelvin. The fitting should be of Philips/ Bajaj/ Wipro/ Havells/ Jaquar/ Crompton/ Panasonic/ Surya/ Trilux make only. The fitting should be of IP-65/66. The LED should have a life of 50000 burning Hours. The fitting should have THD<15% and power factor 0.9 or above. The job includes the cost of testing, commissioning and making connection with copper wire from adjacent light point, other petty material and labour etc. as required to complete the same to the entire satisfaction of Engineer In Charge. Please Enable Macros to View BoQ information |