| 1 | Swaged steel tubular pole ( 410SP-2) of height 7 Mtr. onfirming to IS:2713 (Part II ) in three section with steel base size, bottom of the pole made of 50 mm dia MSB Clamp pipe welded to 300 mm long MS canopy of suitable dia at an angle of 102.5 suitable size of nuts and bolts including rating of one cost steel primer and two coat of read - oxide all complete as required. (Without Arm) |
| 2 | Double arm (1x2) Mtr long |
| 3 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. |
| 4 | a) Above 6.5 mtr and Upto 8.0 mtr |
| 5 | S.I.T.C of floowing rating LED Flood lighting luminarie with pressure die cast housing and toughened glass cover (IP 66 protection) in existing pole/pipe for supply voltage 100-270V AC, 50Hz. Luminarie shall be confirm to IS: 10322 part-5/section-5 and shall be complete with all neccssary accessories as required |
| 6 | a) 200W LED Flood light |
| 7 | S.I.T.C of floowing rating LED Street lighting luminarie with pressure die cast housing and toughened glass cover (IP 66 protection) in existing pole/pipe for supply voltage 100-270V AC, 50Hz. Luminarie shall be confirm to IS: 10322 part-5/section-3 and shall be complete with all neccssary accessories as required |
| 8 | a) 90 W LED Street light |
| 9 | Cable Junction box with MCB |
| 10 | S.I.T.C of following rating LED Post top lamp made in die cast aluminium housing with decorative clear/opal serylic diffuser on existing pipe including connection with 1.5sq.mm. copper conductor etc all complete as required. |
| 11 | 40/45W LED Post top lamp clear |
| 12 | 20/25W LED Post top lamp opel |
| 13 | Making concrete plinth of sizes 1'x1'x1.5' or as reqd. |
| 14 | 40 mm dia Medium class G.I pipes |
| 15 | Supplying and laying of XLPE insulated PVC sheathed aluminium armorued cable working voltage upto 1100 votls as per IS:7098 (prt I) of following sizses. |
| 16 | 10 sq mm 4 core for security lgiht |
| 17 | 10 sq mm 2 core (flood light) |
| 18 | 6 sq mm 2 core (for garden lgiht)620 |
| 19 | Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size not exceeding 35 sq mm directr in ground including excavation, and refilling the trench etc as rquired, but excluding sand cushioning and protective covering. |
| 20 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 21 | 6 sq mm aluminium lugs |
| 22 | 10 sq mm aluminium lugs |
| 23 | Providing and fixign cubical panel consisitng 1 no 400 Amp & 1 no 250 Amp MCCB incomer,, 1 no 400A Change over, 8 nos 100 amp MCCB outdoing 6 nos 63 Amp DP & 3 TPN MCB, Votmeter, Ammeter, cT Coil, Busbar, etc as reqd. |
| 24 | 80mm dia Earthing Electrode 2mtr. Length / 80mm dia Earthing Electrode 3mtr. Length / 50mm dia Earthing Electrode 2mtr. Length/50mm dia Earthing Electrode 3mtr. Length & Backfill Compound chemical 4 Bag(per bag 25 KG) |
| 25 | Supply and laying 8 SWG copper wire at 0.50 metre below ground level for conductor earth electrode, including solding etc. as required. |
| 26 | CGST @ 9% |
| 27 | SGST @ 9% |
| 28 | Labour Cess @1% Please Enable Macros to View BoQ information |