| 1 | S.I.T.C of following rating approved make LED Bollard fitting with cylindrical shape of height 600 to 850mm power input-8/9watt with die cast aluminium housing opel with PC diffuser, IP:65/54 protection, conferming to IS:10322 part 5 etc all complete as required. (excluding plinth charge) |
| 2 | Making plinth 1'x1'x1.5' including labour charge with bricks snd cement including painting etc as red. |
| 3 | Supplying and drawing following sizes of FR PVC insulated copper conductor single core cable in existing surface / recessed steel / PVC conduit including dismantling as required |
| 4 | a) 3x1.5 sq mm |
| 5 | Supplying and laying of XLPE insulated PVC sheathed aluminium armorued cable working voltage upto 1100 votls as per IS:7098 (prt I) of following sizses. |
| 6 | a) 2x6 q mm (for Garden light) |
| 7 | b) 3.5 core 35 sq mm (for Panel to Fidder Panel for campus lgiht) |
| 8 | c) 2x10 sq mm (for Service cable for 2 nos Gazebo and staff qtr) |
| 9 | d) 2x6 sq mm (Service cable for 4 nos Power point) |
| 10 | e) 2x6 q mm (for LED flood light on building) |
| 11 | S.I.T.C of following rating LED Post top lamp made in die cast aluminium housing with decorative clear/opal serylic diffuser on existing pipe including connection with 1.5sq.mm. copper conductor etc all complete as required. |
| 12 | a) 25W LED Post top lamp clear (for Gate light) |
| 13 | S/F 100W LED Flood light (on building) |
| 14 | Providing and fixing following DP/TP&N sheet metal switch disconnector fuse unit in the existing metal board with rewireable type fuses, including drilling holes in metal board . making connections. etc. as required. |
| 15 | a) 32 Amp DP Main switch |
| 16 | Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size not exceeding 35 sq mm directr in ground including excavation, and refilling the trench etc as rquired, but excluding sand cushioning and protective covering. |
| 17 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 18 | S/F suitable sizes water proof sintex made distribution junction box with 1 nos MCB all complete with nut-bolt etc as red. (2 nos for gate light + 4 nos for power point + 10 nos for Flood light) |
| 19 | Earthing with G.I. earth pipe 4.5 mtr long . 40mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal and salt as required. |
| 20 | Supply and laying 8 SWG copper wire at 0.50 metre below ground level for conductor earth electrode, including solding etc. as required. |
| 21 | Fabrication, installation with 16 SWG MS sheet with one coat steel primer and two coat spray painting with approved shade making PCC plinth and foundation including fitting and fixign connection, transportation upto work site labour charge etc all complete as reqd. |
| 22 | 100 Amp MCCB 10 KA, fixed thermal setting- 1 Nos |
| 23 | 40 Amp DP MCB-7 nos |
| 24 | 63 Amp DP MCB-3 nos |
| 25 | LED indicator lap R/Y/B/G-3 nos |
| 26 | 50mm x 5mm copper strips (2.30 kg/ mtr)-6 kg |
| 27 | CGST @ 9% |
| 28 | SGST @ 9% |
| 29 | Labour Cess @ 1% Please Enable Macros to View BoQ information |