| 1 | Supply and erection of P.C.C. pole as per REC manual no 15/1979 (ammended upto date) and as per latest Discom specifications with factor of safety 2.5 including excavation of pit upto pole planting depth 1/6th of pole length. and back filling with stone aggregate/boulders and soil by ramming and watering etc complete as required. |
| 2 | 9.0 Mtr long PCC pole of 400 Kg Working Load |
| 3 | Supplying and drawing Aluminium conductor steel reinforced (ACSR) ISI marked(IS 398 part II-1996) on existing cross arms through insulator with all necessary T&P required including binding and twisting etc. complete in all respect as required. |
| 4 | 50 Sqmm of (6+1) 3.35 mm (Insulated Rabbit) for LT |
| 5 | Supply and fixing of 11 kV pin insulator confirming to IS:731:1971 with latest ammendment on existing bracket including all accessories like MS forged hot dipped GI Pin confirming to IS 2486(Part-I)/1993 & IS:2486 (Part-II)/1989 with latest amendment, and as per latest Discom specs. etc. as required. |
| 6 | Supply and fixing of 11kV, 400 Amp 3 pole, central pot rotating double break type isolator (IS:9921 part I toV) without earth blade operating mechanism with GI spring loaded reverse loop type fixed contact, solid hard drawn electolytic copper tubular moving contact with silver/ nickel plated at end points, 9 nos post insulator of 12 kV (IS:2554 & IS 5350 part III), hot dipped galvanising hard ware, nut, bolts etc complete in all respect as per Discom specification etc. as required. |
| 7 | Supply and fixing of 100 Amp, 11kV Horn gap fuse set IS 9385 on existing DP structure with 6 nos 24kV/22kV post insulator (IS:5350 part III), hot dipped hard ware,fuse wire of required size etc. complete in all respect as per Discom specification etc. as required. |
| 8 | Supply and fixing Substation structure for mounting 11/0.4 Kv Transformer on Double pole as per DISCOM specification complete in all respect as required including nuts and bolts etc (excluding the cost of poles) made of MS channel of 4 nos 100 x 50 x 6mm and 4 nos 75 x 40 x 6mm and MS flat 50 x 6mm etc. as required. |
| 9 | Supply and fixing of PG / T clamps on overhead lines/jumpers, made of aluminium alloy 4600 of IS 617-1994 (with latest amendment if any) with steel nut and bolts conforming to IS 1363-1992 & IS 1367/1979-80 (with latest amendments if any) all ferrous metal parts intended for outdoor use except those made of stainless steel shall be protected by hotdip galvanising in accordance with IS 2633-1986 complete in all respect as required. |
| 10 | PG Clamp for Rabbit Conductor |
| 11 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC pipe / Hume Pipe/ Stoneware Pipe/ PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. |
| 12 | 3 core 185.0 Sq.mm |
| 13 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 including testing etc. as required of following sizes. |
| 14 | 11 KV End Termination Kit Outdoor type |
| 15 | 3 core 120/150/185 Sq.mm |
| 16 | 11 KV Straight Through Joint Kit |
| 17 | 3 core 120/150/185 Sq.mm |
| 18 | Supply and fixing of 11kV Disc insulator and Hot dipped galvanized Hardware confirming to IS:731:1971 with latest ammendment and as per latest Discom Specs. on existing bracket including all accessories etc. as required. |
| 19 | T & C disc insulator 45 KN |
| 20 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 21 | 185.0 Sq. mm |
| 22 | 3.5 core |
| 23 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required. |
| 24 | 3.5 x 185.0 sq.mm |
| 25 | Supply & fixing of GI pipes confirming to IS : 1239 P - 1 ( 2004 ) with socket,elbow,tee, flanges duly screwed & welded including rubber washer, nuts & bolts of 8mm dia complete in all respect. ( If Pipe Laid Underground Excavation and refilling cost will be paid extra) |
| 26 | 100 mm dia. |
| 27 | Supply and erection of GI stay set confirming to pattern-1 of BS:16/1974 and as per latest Discom Specifications complete with stay rod with anchor plate fitted with cast iron cross head and steel bow, in cement concrete 1:3:6 including excavation of pit-re-filling etc complete as required. |
| 28 | Stay set of dia 20mm, 2.4m long stay rod and anchor plate 380 x 380 x 4.0 mm |
| 29 | Supply and fixing of following LT Supporting accessories with nut bolt & Clamps made out as per standard Discom's specifications with two coats of Red oxide and two coats of Aluminium paint etc. as required. |
| 30 | LT cross arm 600 mm long with clamp |
| 31 | LT cross arm 1200 mm long with clamp |
| 32 | Supply and fixing of LT porcelain pin insulator as per IS 1445-1997 and as per Discom's standard specifications,suitable for working voltage 1100 volts including all accessories like MS Forged GI LT Pin confirming to IS:7935/1975 (latest amended) Nut, Bolt etc. as required. |
| 33 | 100 mm x 70 mm |
| 34 | Supply and fixing of 'V' type cross arms with clamps as per latest Discom specifications made of MS angle (65X65X6)on the existing poles complete including all necessary nut and bolt, clamps with two coats of Red oxide and two coats of Aluminium paint etc. as required. |
| 35 | Supply and fixing of 11 / 33. KV Stay insulator as per IS:5300/1969 and as per Discom's standard specifications etc. as required. |
| 36 | 140 x 85 x 25mm 33 KV Stay Insulator |
| 37 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. . |
| 38 | Supply and fixing of LT Distribution Kiosk confirming to IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per DISCOM specifications made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including Incoming Switch Disconnector Fuse unit, Aluminium Busbar with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS Channel frame of 75 mm x 40 mm grouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for required no. of outgoing. |
| 39 | 400 Amp. LT Distribution Kiosk for 250/315 KVA Transformer |
| 40 | 100 Amp. Distribution Kiosk of Size 500mm x 550 mm x 700 mm suitable for Underground cable |
| 41 | Supply and installation of spike of M.S. rod 20mm dia 3.0mtr. long for earthing of (tower/pole) drive into earth by mechanical means sturcture connection the spike with cross arm top hamper PCC pole, lattics tower to earth etc. complete as per technical specification of DISCOM. |
| 42 | Labour charges for Dismantling the structure with pole mounted transformer of different capacity along with distribution boards and re- erecting the transformer on newly erected structure along with distribution boards and including testing and commissioning (as well as cabling connection complete as required) |
| 43 | Labour charges for dismantling of existing PCC/MS electrical Pole including MS channel, V cross arm, 11KV insulator, LT insulator, guard wires, stay wires, one span of ACSR conductors and other electric items, coming along and in the alignment of the road, then removal and re-rolling of the PCC /MS Pole as well as other materials and handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and as per the direction of Engineer Incharge, clean the site good as per the requirement and dismantle material receipt duly signed by DISCOM Engineer submit the receipt to EIC as required. Please Enable Macros to View BoQ information |