| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+) Less (-) Tender Inviting Authority: Chief Engineer, Civil Engineering Group, GSO, Kalpakkam. Name of Work: Electrification of Swimming Pool and associated works in Anupuram Township. Tender No: GSO/CTC/ESD/294/2026 Name of the Bidder/ Bidding Firm / Company : PART-II (FINANCIAL BID) Note : 1) This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. 2) Bidders are allowed to enter the Bidder Name and Values only.3) Rates quoted should be inclusive of GST @ 18% and any other taxes as applicable. NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Item.No. Item Description Item Code / Make Quantity Units Estimated RateinRs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE including all taxes in Figures to be entered by the Bidder inRs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Rates in words Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category Unit for Rate TOTAL AMOUNT Without Taxes in Rs. P TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Design, manufacturing, testing at manufacturer's works packing, transportation, delivery, unloading, storage, erection, testing and commissioning of the 415 Volts Switch Boards at site as per the Drawing No:- GSO/ESG/ESD/ATS/SP-LDP and detailed specification and as directed by Engineer-in-charge. |
| 3 | Load Distribution Panel consisting of following:a) 2 Sets of Incomer Feeders with 400 Amps, 4 Pole, MCCB with CBCT, Shunt Trip Coil, operating handle, interlocking facility and all control, measuring units etc., b) 4 Sets of Outgoing Feeders with 63 Amps, 3 Pole, MCCB with 20 HP Star Delta Starter with multifunction meter, Motor Protection Relay, operating handle etc.c) 1 Set of Outgoing Feeders with 6A, 4Pole MCB with 3 Set of 6A, Double Pole MCB along Motor Circuit Breaker with 0.25 to 0.4A range.d) 1 Set of Outgoing Feeder with 63 Amps, 4 Pole, MCCB with 32A, 4 Pole Contactor.e) 1 Set of Outgoing Feeder with 63 Amps, 3 Pole, MCCB with 1.0 HP DOL Starter with multifunction meter.f) 1 Set of Outgoing Feeder with 63 Amps, 3 Pole, MCCB with 5.0 HP DOL Starter with multifunction meter.g) 4 Sets of Outgoing Feeder with 63 Amps, 4Pole, MCCB.h) 1 Set of Outgoing Feeder with 125 Amps, 4 Pole, MCCB with multifunction meter. |
| 4 | Supply, embedment of 400 mm (H) X 500 mm (W) X 150 mm (D) made out of sheet steel, Powder Coated enclosure with 4 Sets of ON/OFF Push Buttons, LED indication lamps and Terminal connectors for controlling of swimming pool luminaires. |
| 5 | Assembling, installation, testing and commissioning of MCB DB enclosure already embedded in the wall including supply of Per phase isolation conversion kit suitable for Cat No:DETPI012DD or equivalent as per the detailed specification for the following size of MCB DBs. (Refer Sec VI, Clause No.15.3). |
| 6 | TPN, 12 Way Distribution Board |
| 7 | Supply fixing testing and commissioning of the following RCCBs on Distribution Boards as per the detailed specification. (Refer Sec VI, Clause No.14.2). |
| 8 | RCCB DP 40A sensitivity 30mA, TYPE Hpi |
| 9 | Supply Installation testing and commissioning of the following MCB on Distribution Boards as per the detailed specification. (Refer Sec VI, Clause No.14.2). |
| 10 | 6-32 Amps SP MCB (Type-C) |
| 11 | 6-32 Amps DP MCB (Type-C) |
| 12 | 6-32 Amps FP MCB (TYPE-C) |
| 13 | Wiring for lights / fans /sensors/ Timer /Power point with 1100V grade FRLS insulated copper conductor wires in existing concealed/ Exposed PVC / ERW / Flo-coated Metal conduits as per the detailed scope of work, including supply of Wires, switches/ sockets, termination of copper wires at either end by crimping including supply of PVC Sleeves/Ferrules, Copper Crimping Lugs and connecting the wires to various switches, sockets, etc. including testing and commissioning as per the detailed specification.(Refer Sec VI, Clause No.18) |
| 14 | Wiring for Power Points with 2 Runs of 4.0 Sq.mm Copper wires for Phase, Neutral and 1 Run of 2.5 Sq.mm Copper wires for Earth from MCB Distribution Board to Single Phase Metal Clad Socket. |
| 15 | Wiring for Power point with 3 Runs of 2.5 Sq.mm Copper wires for Phase & Neutral and Earth from MCB Distribution Board to Power point through Control Switch Box including 16A modular switch, 6/16 Amps combined shuttered type Socket and 6A modular switch & 3 pin, 6A shuttered type Socket, Modular Plate |
| 16 | Wiring for Power point with 2 Runs of 1.5 Sq.mm copper wire for Phase & Neutral and 1 Run of 2.5 Sq.mm copper wire for Earth from MCB Distribution Board to Power point through Control Switch Box including 6A modular switch 3 pin, 6A shuttered type Socket, Module Plate |
| 17 | Wiring for Light/Sensor/Fan Points with 2 Runs of 1.5 Sq.mm copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm copper wire for Earth from MCB Distribution Board to Primary light/sensor/fan point through Control Switch Box including 6Amps modular switch. |
| 18 | Wiring for Fan point with 2 Runs of 1.5 Sq.mm copper wire for Phase & Neutral and 1 Run of 2.5 Sq.mm copper wire for Earth from MCB Distribution Board/Switch Box to Fan point through Control Switch Box including 6A modular switch and step type Fan regulator suitable for BLDC Fans. |
| 19 | Wiring for Exhaust fan point up to 3Mtr height with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm Copper wire for Earth from MCB Distribution Board to Power point through Control Switch Box including supply of 3 pin 6A shuttered type Socket, 2Nos. 2 Modular plate and 1 No 6A modular switch. |
| 20 | Wiring for Power point with 3 Runs of 2.5 Sq.mm Copper wires for Phase & Neutral and Earth from Control Switch Box to control switch box including 6A modular switch & 3 pin 6A, shuttered type Socket and 16A modular switch & 6/16A combined shuttered type Socket, Modular plate. |
| 21 | Wiring for Power point with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm copper wire for earth from Control Switch Box to control switch box including 6A modular switch & 3 pin 6A, shuttered type Socket, Modular plate. |
| 22 | Wiring for Light point with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm Copper wire for Earth from Switch box to switch box and further to Light point including 1 No 6A modular switch |
| 23 | Wiring for Exhaust fan point up to 3Mtr height with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm Copper wire for Earth from Switch box to Switch Box and further Power point including supply of 3 pin 6A shuttered type Socket, 2 Nos. 2 Modular plate and 1 No 6A modular switch. |
| 24 | Wiring for Light point with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm Copper wire for Earth from Switch box to Light point including 1 No 6A modular switch |
| 25 | Wiring for fan point with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm Copper wire for Earth from Switch box to Fan point including 1 No 6A modular switch and 1 No step type Fan regulator suitable for BLDC fan. |
| 26 | Wiring for Exhaust fan point up to 3Mtr height with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm Copper wire for Earth from Switch board to Power point including supply of 3 pin 6A shuttered type Socket, 2Nos. 2 Modular plate and 1 No 6A modular switch. |
| 27 | Wiring for Light point with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm Copper wire for Earth from Light point to Light point /sensor/contactor |
| 28 | Wiring for geyser indication point with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm for earth from geyser Point to Indicator Lamp including supply of Indicator lamp and modular plate. |
| 29 | Wiring and termination for Telephone point with 1 Run of 0.5 mm dia, 250 V grade PVC insulated, twin twisted, two pair, tinned copper wire from Telephone Junction Box to Telephone points in concealed conduit/ PVC Trunking including supply of wire and 2 Nos. 1 module Jack type Telephone Socket with Shutter with Modular plate.(Refer Sec VI, Clause No.18) |
| 30 | Wiring with 1 Run of 1.5 Sq.mm Copper wire |
| 31 | Wiring with 1 Run of 2.5 Sq.mm Copper wire |
| 32 | Supply and fixing following Modular front cover plate on existing modular metal/plastic boxes etc. as required. (Refer Sec VI, Clause No.15.7). |
| 33 | One/Two module |
| 34 | 3 Module |
| 35 | 4 Module |
| 36 | 6 Module |
| 37 | 1 Modular dummy plate |
| 38 | Supply, transportation, installation, testing and Commissioning of the following type of BOX type / Batten type / Surface mounted type / using ball & socket luminaire. (Refer Sec VI, Clause No.16.1). |
| 39 | Supply, transportation, installation, testing and Commissioning of 1200 mm long, 18 Watts (max), 2000 Lumen LED Batten with suitable clamps as per the detailed specification. (Refer Sec VI, Clause No.16.1 for installation) |
| 40 | Supply, transportation, installation, testing and commissioning of 9 Watts (max) 900 lumens, 2 feet long surface mounted LED Batten as per the detailed specification. |
| 41 | Supply, transportation, installation, testing and commissioning of 12 Watts (max), 1200 Lumen, surface mounting decorative LED flat panel Luminaires as per the detailed specification. |
| 42 | Supply, transportation, installation, testing and commissioning of 18 Watts (max), 2000 Lumen, surface mounting decorative LED flat panel Luminaires as per the detailed specification. |
| 43 | Supply, installation and testing 6 Watts (max), 600 lumen LED Bulkhead Luminaires with integrated driver unit made of aluminium with suitable connecting leads as per the detailed specification. |
| 44 | Supply, Installation, Testing and Commissioning of Supply, installation, testing and commissioning of 6W LED wall washer light fittings as per the detailed specification and scope of work. |
| 45 | Supply, Installation, Testing and Commissioning of Supply, installation, testing and commissioning of 250 Watts LED flood light luminaries at the height of 7-12 M high as per the detailed specification. (Refer Sec VI, Clause No.16.1). |
| 46 | Supply & Installation of 11meters high Hot dipped G.I flood light pole including painting with PU paint, foundation EP, heavy duty GI cable entry pipe in 1:3:6 PCC foundation, excavation and refilling etc as per drawing No.:IGC/ESD/4013/5004/1-R1 including supply of GFRP box as per Drawing No:IGC/ESD/2021/6001/3, 40 NB heavy duty GI pipe,40 NB heavy duty long bend, Clamp for 25 X 6mm Alu. flat , 1mtr 16mmDia SS rod with SS wire (2 runs) equivalent to 8SWG , 3C x 1.5 sqmm copper flexible cable, fixing fasteners etc as required.(Refer Sec VI, Clause No.13.1 & 13.2). |
| 47 | Supply and Installation of 3.75mtr Area lighting poles With PU painting (Pedestal type). (Refer Sec VI, Clause No.13.3 & 13.4). |
| 48 | Post top Lantern pole including supply and embedment of Cast Aluminium Junction Box with FRP cover as per the drawing No: IGC/ESD/2021/6001/1, 3.75mtr 50NB GI pole with PU painting, cable entry pipe, cable termination arrangements etc. including providing of 1:4:8 mudmat and 1:3:6 foundation PCC conforming to the detailed specification 1mtr 16mmDia SS rod with SS wire (2 runs) equivalent to 8SWG and as per Drawing No. IGC/ ESD/2021/6001/P2. (Refer Sec VI, Clause No.13.3 & 13.4). |
| 49 | Supply, assembling, installation, testing and commissioning of IP66 grade 3 Phase +Neutral, 32A industrial socket, suitable Plug Top as per the detailed specification and as directed by Engineer incharge |
| 50 | Supply, Installation, testing and commissioning of 1200 mm size of BLDC Ceiling Fans with suitable safety steel rope with 3 Core, 1.5 Sq.mm flexible copper cable including earth connection. |
| 51 | Supply, installation, testing and commissioning of 400 mm Dia sizes of Wall Mounting Fans as per the detailed specification. (Refer Sec VI, Clause No.17.4). |
| 52 | Supply, installation, testing and commissioning of following sizes of Wall Mounting Exhaust Fans including supply of Aluminium grill bracket with Stainless Steel Bolts for mounting of Exhaust Fan & Aluminium grill bracket and 3 Core, 1.5 Sq.mm PVC insulated & FRLS sheathed copper flexible cable of required length as per the detailed specification. (Refer Sec VI, Clause No.17.2). |
| 53 | 230 mm dia Medium duty , Double ball bearing exhaust fan |
| 54 | Supply, transportation, installation, testing and commissioning of the following Sensors as directed by the Engineer-in-Charge. (Refer Sec VI, Clause No.16). |
| 55 | Occupancy & day light PIR sensor suitable for lighting load of 500W and coverage 7.0 mtr diameter. The unit Shall have provision to adjust ON time as well as day light level for switching ON. (Refer Sec VI, Clause No.16.3). |
| 56 | Supply and Installation of 1 No 6 A Bell push switch on modular plate and termination of wires to the switches as per the detailed specification.(Refer Sec VI (MNC), Clause No.5). |
| 57 | Supply, embedment and flush mounting following sizes of Metal one way enclosures for MCBs, RCCBs, RCBOs including chipping and finishing as per the detailed specification. .(Refer Sec VI, Clause No.15.5). |
| 58 | DP Cat No:507791/ FP Cat No:507793 Metal one way enclosure (M/s Legrand/BCH or equivalent make) |
| 59 | Supply, Installation, testing and commissioning of 6 inch dia, 230V, 50Hz industrial Gong Bell with suitable connecting leads as per the detailed specification and scope of work. |
| 60 | Supply, installation and testing of GI Pipe Earth Electrode as per IS: 3043 including RCC Chamber and RCC cover slab as per Drawing Nos. IGC/ESD/5060/1007/1 & IGC/ESD/5060/1008/1 are enclosed. (50 Kg. Each Bentonite & Charcoal shall be provided for each earth pit). (Refer Sec VI, Clause No.12.4). |
| 61 | Supply, Loading, Transportation, Unloading at site, Laying, Testing and Commissioning of 1.1 KV grade of following size of the cable through direct in ground including excavation, sand cushioning, protective covering with chamber burnt/cement bricks on sides & top, refilling the trench and providing RCC route indicator etc as required.(Refer Sec VI, Clause No.3) |
| 62 | 4C x 185 sqmm 1.1kV grade Aluminium conductor XLPE insulation flat wire armour FRLSH PVC outersheath |
| 63 | 4C x 16 sqmm 1.1kV grade Aluminium conductor HRPVC/XLPE insulation flat wire armour FRLSH PVC outersheath |
| 64 | 4C x 10 sqmm 1.1kV grade Aluminium conductor HRPVC/XLPE insulation flat wire armour FRLSH PVC outersheath |
| 65 | Supply, Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade following sizes of cables in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification.(Refer Sec VI, Clause No.3) |
| 66 | 4C x 185 sqmm 1.1kV grade Aluminium conductor XLPE insulation flat wire armour FRLSH PVC outersheath |
| 67 | 4C x 16 sqmm 1.1kV grade Aluminium conductor HRPVC/XLPE insulation flat wire armour FRLSH PVC outersheath |
| 68 | 4C x 10 sqmm 1.1kV grade Aluminium conductor HRPVC/XLPE insulation flat wire armour FRLSH PVC outersheath |
| 69 | Loading, Transportation, Unloading at site, Laying, Testing and Commissioning of PVC insulated & Sheathed, armoured control cables of following sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification..(Note: Cable will be issued free of cost by the department).(Refer Sec VI, Clause No.3) |
| 70 | Above 14 Core & Upto 37 Core 2.5 sqmm |
| 71 | End Termination of the following sizes of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. (Refer Sec VI, Clause No.10.1). |
| 72 | 3.5 x 185 sq.mm |
| 73 | 4 Core x 16 Sqmm |
| 74 | 4 Core x 10sqmm |
| 75 | End termination of 1100 Volts Grade XLPE/PVC insulated, control cables of the following sizes using Single Compression, Heavy Duty, Siemens type Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Dowell's or equivalent make Copper crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for the completion of the work. (Refer Sec VI, Clause No.10.1). |
| 76 | 19C X2.5Sqmm |
| 77 | Supply, fabrication and installation of the following size of Hot dip Galvanised GI Flats including excavation and refilling as per the detailed specification. No cutting or drilling permitted after galvanisation.Refer Sec VI, Clause No.12.9). |
| 78 | 50 x 6 mm GI flat |
| 79 | Supply, fabrication and installation of the following size of Hot dip Galvanised GI Flats in Built in trenches on walls, poles, RCC Concrete and through embedded pipes as per the detailed specification. No cutting or drilling permitted after galvanisation. (Refer Sec VI, Clause No.12.9). |
| 80 | 50 x 6 mm GI flat |
| 81 | Supply and installation of 8 SWG G.I wire for earthing in built trenches and walls including termination using lugs, sleeves, bolts and nuts as per detailed specification and as directed by Engineer in charge |
| 82 | Excavation in hard soil including refilling with excavated earth and disposing surplus earth at places as directed with in a lead of 10 Mtrs. and initial lift up to 1.5 Mtrs. including neat banking as per detailed specification. (Refer Sec VI, Clause No.2) Total in Figures 0.0 0.0 INR Zero Only Quoted Rate in Figures Less (-) 0.0 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Government of IndiaDepartment of Atomic EnergyGeneral Services Organization Centralised Tender Cell TENDER DOCUMENT FOR Electrification of Swimming Pool and associated works in Anupuram Township. Tender No: GSO/CTC/ESD/294/2026 Part – II : Financial Bid (Section - VIII) INDEX S.No. Title Page No. |
| 83 | GENERAL INFORMATION FOR GUIDANCE OF TENDERERS |
| 84 | The schedule of quantities is to be read for the purpose of pricing in conjunction with the special conditions, general rules for the guidance of contractors, conditions of contract, specifications, scope of work (Section V), and General Specification (Section VI), drawings, schedule of supply of materials and the appendices for complete interpretation of this scope of work quantity wise. |
| 85 | The prices inserted in the schedule of quantities shall be inclusive of value of the work described including all cost and expenses, which may be required in and for the construction of the work described together with the general risks, liabilities and obligations not forth or implied in the documents on which the tender is to be based. |
| 86 | The quantities stated are to be considered approximate only and the unit prices entered in the schedule of quantities and prices shall apply only to the actual quantities measured in the completed work in accordance with the specifications. |
| 87 | Items of work described in brief are detailed under specification of Work.The scope of work will not be estimated from the brief description of this schedule. |
| 88 | Rate quoted must include all components required for meeting the specification and performance requirements of the item irrespective of whether they are specifically brought out in this schedule or not. |
| 89 | All the materials other than those shown in schedule of supply of materials in section VII are to be arranged by the contractor and his rates should account for the same. |
| 90 | Rates quoted for all items in this tender shall include cost of all materials. Department will not supply any materials other than materials stipulated in Section - VII of the tender and as such the rates quoted must be all inclusive. |
| 91 | If contractors need any clarification they are required to contact the ‘Head, CTC, GSO, Kalpakkam – 603 102, Chengalpattu district, Tamilnadu (Ph – 044 - 27481238 and 044-27480500 Extn. 84299,87345,85803,85532) during office hours. Please Enable Macros to View BoQ information |