| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.opper conductor single core cable etc as required. |
| 2 | Group C |
| 3 | (Make:-finolex,Anchor,Plaza) Legrand (Myrius), L&T(Entice), Schneider(Livia) |
| 4 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 5 | 2X4 sq. mm + 1X4 sq. mm earth wire |
| 6 | Make:-finolex / Anchor / Plaza) |
| 7 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 8 | 4X4 sq. mm + 2X4 sq. mm earth wire |
| 9 | Make:-finolex / Anchor / Plaza) |
| 10 | Supplying and fixing suitable size GI box with modular plate and cover in FRLS on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 11 | (Make: Anchor /L&T/Havells) |
| 12 | Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surface as required. |
| 13 | Armoured Cable 25 Sq.mm. (3.5 core) |
| 14 | Make:- finolex/ Anchor / Plaza) |
| 15 | 2.2.13 Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 16 | MCCB 32 A- 100 A 18 KA |
| 17 | (Make: Anchor /L&T/Havells) |
| 18 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 19 | 63 Amps |
| 20 | (Make: Anchor /L&T/Havells) |
| 21 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 22 | 63 Amp |
| 23 | (Make: Anchor /L&T/Havells) |
| 24 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 25 | 16 way, Double door |
| 26 | (Make: Anchor /L&T/Havells) |
| 27 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 28 | Single pole |
| 29 | (Make: Anchor /L&T/Havells) |
| 30 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 31 | 40 amps |
| 32 | (Make: Anchor /L&T/Havells) |
| 33 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 34 | Earthing with Copper earth plate 600 mmx600 mmx 6 mm thick |
| 35 | Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for horizontal run) |
| 36 | Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for vertical run) |
| 37 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 38 | 8 SWG Copper Wire |
| 39 | Providing and fixing of IP65 Bulkhead led fixture 10 W +/- 1 W Wall Mounted with minimum system lumen efficacy of 100 lm/W with Pressure Die Cast Aluminum housing, Polycarbonate Opal Diffuser and P.F.>0.95 with THD<10% ,CRI 80.The LED shall be tested with LM80-08 standard with Useful life of 50000 Hrs at L70 .The LEDs used in the luminaire shall have CCT of ANSI Bin 5700 K only with CRI of minimum 80.The Input voltage range shall be 140V to 280V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. |
| 40 | LED Bulk Head Light 10W |
| 41 | Make:- Wipro /Philips/Trilux Please Enable Macros to View BoQ information |