| Sl. No. | Item Description |
| 1 | Total Amount of BoQ 2 |
| 2 | Amount after unconditional Rebate |
| 3 | Total of BoQ 3 and BoQ 4 |
| 4 | Total Amount of BoQ3 (Item Rate) |
| 5 | Total Amount of BoQ4 (Percentage Rate) |
| 6 | NSR-HVAC WORK SHIKAR BUILDING |
| 7 | Note: The HVAC contractor shall provide fire shunt relay contact in main HVAC panel and all AHU panels/DBs along with auto / manual mode selector switch in the outgoing feeder for AHU Fan, Ventilation & Pressurization fan etc. to take fire input signal (Potential Free Contact) to trip /switch off them. Cost shall be included in the panel price quoted by him. |
| 8 | NS 1 Air Cooled Heat Pump for Generating Hot Water |
| 9 | Supply , installation , testing & commissioning of AHRI/Eurovent Certified Micro Processor Controlled Reversible Air Cooled Scroll Heat Pump delivering actual capacity as per the following parameters duly installed at site. The Heat Pump should be complete with multiple hermatic scroll compressors , Electronic Expansion Valve, 4 way reversible valve, V shaped Air Cooled Condenser coil with Copper tube/ aluminum fins having, Axial fans with IP54 protection and stepless fan speed regulator for condensation control, Shell & Tube Heat Exchanger on evaporator, anti-vibration rubber mounts with factory assembled with Electrical panel with disconnect switch mounted on the Heat Pump including the disconnect switch suitable for 50 Hz, 3 phase 415 volts, AC supply. The vibration isolators & victaulic coupling for Heat Pump shall be shipped alongwith Heat Pump from your works. The Heat Pump should have Auto Defrost Cycle for low ambient operation. |
| 10 | Refrigerant circuit to include liquid line drier filter with replaceable solid cartridge, liquid line sight glass, EEV, high pressure safety valve, high & lower pressure transducers, high and low pressure switches, etc. The Heat Pump shall be suitable for operation on Environment friendly refrigerant R410A/ R134A and shall come factory charged with refrigerant |
| 11 | Heating Capacity Range : 300 KW |
| 12 | Designed Air entering in condenser : 7°C for Winter |
| 13 | Hot water 'In' : 40°C |
| 14 | Hot water 'Out' : 45°C |
| 15 | Chiller Fouling Factor (FPS) : 0.0001 |
| 16 | Heating COP : >3.3 (Including Condenser Fans) |
| 17 | NS-1.1 300 kW (1W+AS) |
| 18 | NS 2 Primary Chilled Water Pump with Flow meter & VFD |
| 19 | Supply, installation, testing and commissioning of PN16 rated Vertical Inline Split Coupled (with rigid aluminium alloy coupling between pump shaft and motor shaft) touch screen VFD single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications. Casing (Volute) - Ductile Iron/ CI.Impeller - 316 Stainless Steel - Statically and Dynamically BalancedCasing Gasket - Confined Non Asbestos FiberPump Shaft - SS 316.Flush Line - Braided Stainless SteelMechanical Seal - Outside BalancedMotor Type - Permanent Magnet SynRM Motor , Efficiency Class IE4,Pump. |
| 20 | All the VFD should display the dynamic head & flow rate of the pump using inputs from ultrasonic flow meter and digital pressure gauge or using sensorless algorithms,( 1 flow meter and 2 pressure gauges to be supplied for each VFD driven pump). Pump manufacturer to supply Ultrasonic flow meter and digital pressure gauges along with the pumps supplied or can display individual flow and head of each pump using sensorless algorithms.VFD screen should be touch screen All pump shall be provided with embedded software and hardware for wireless remote performance managements with an initial one-year subscription for IOT service as described below.a) Web access to monitor data (flow, head, vibration, pump in hand, dead head, & other important electrical data)b) Analyzed out in the form of alerts for preventive maintenance.c) Energy Report & raw data available to downloadTriple duty valve and suction Guide to be supplied by contractor of same OEM make of which the pumps are supplied for system unit responsibility |
| 21 | NS-2.1 Primary Water Pump ( 2W+1S ) Water Flow Rate: 850 USgpmHead : 45mt WC |
| 22 | Triple duty valve and suction Guide to be supplied by contractor of same OEM make of which the pumps are supplied for system unit responsibility |
| 23 | NS 3 Microprocessor Based Pump Logic Controller for Primary water pumps |
| 24 | Separate ( not as apart of VFD )Microprocessor based variable pump logic controller in IP 54 protection, to control following nos. Pumps. Suitable to operate on sensorless /Transmitters, interfacing amongst all components and compatibility of I/O signals etc Should be Modbus RTU/ BACnet enabled for communicating with BMS & RS-485 serial communication with Pump VFD. The staging of pumps should be based on efficiency (not on capacity) to ensure minimum operating cost.Power Rating: 230 V/ 1 ph/ 50 Hz.Display: Minimum 4.3\\" backlit LCD Hand-Off-Automatic(H-O-A) control Secure front cabinet door with lock and key UL Listed and CSA Approved Remote or local start/stop mode of operation. 2-level (field and factory) password security Remote zone signals, zone faults, zone setpoint and active control zone |
| 25 | NS 4 CONDENSOR WATER PUMPS with flow meter & VFD |
| 26 | Supply, installation, testing and commissioning of PN16 rated Vertical Inline Split Coupled (with rigid aluminium alloy coupling between pump shaft and motor shaft) touch screen VFD single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications.Casing (Volute) - Ductile Iron/ CI.Impeller - 316 Stainless Steel - Statically and Dynamically BalancedCasing Gasket - Confined Non Asbestos FiberPump Shaft - SS 316.Flush Line - Braided Stainless SteelMechanical Seal - Outside Balanced Motor Type - Permanent Magnet SynRM Motor,Efficiency Class-E4. All the VFD should display the dynamic head & flow rate of the pump using inputs from ultrasonic flow meter and digital pressure gauge or using sensorless algorithms,( 1 flow meter and 2 pressure gauges to be supplied for each VFD driven pump). Pump manufacturer to supply Ultrasonic flow meter and digital pressure gauges along with the pumps supplied or can display individual flow and head of each pump using sensorless algorithms.VFD screen should be touch screen All pump shall be provided with embedded software and hardware for wireless remote performance managements with an initial one-year subscription for IOT service as described below.a) Web access to monitor data (flow, head, vibration, pump in hand, dead head, & other important electrical data)b) Analyzed out in the form of alerts for preventive maintenance.c) Energy Report & raw data available to download |
| 27 | Condenser Water Pump ( 2W+1S ) Water Flow Rate: 1200 USgpmHead : 30 m WC |
| 28 | Triple duty valve and suction Guide to be supplied by contractor of same OEM make of which the pumps are supplied for system unit responsibility |
| 29 | NS 5 CHILLER PLANT MANAGER |
| 30 | Supply,installation,testing& commission control\optimise Chillers, CHW Pumps, Cond Pumps, Cooling Tower Fans, On/Off Valves and Sensorless Load (Primary Variable) Controller and 04 temperature Sensors, 01 No outside humidity sensor. (Best in Efficiency and Pay Back).The intelligent plant automation controller shall be designed for a Water cooled chiller plant. The logic controller shall be specifically designed to control up to 3 water cooled chillers, up to 3 cooling towers fans variable speed drives, up to 3 cooling tower isolation valves, up to 3 condenser pumps (with options for single or dual pumps, if dedicated to the chillers), up to 3 variable speed distribution pumps (with options for single or dual pumps, if dedicated to the chillers), up to 3 chiller isolation valves (if the pumps are headered), 1 system by-pass valve to maintain minimum flow and up to 3 zone demand sensors (which can either be differential pressure or temperature sensors), also sensorless algorithm.The controller shall include a 10.4 inch backlit touch screen, shall have a lockable IP55 cabinet. Integrated Plant controller should be programmed with Sensor less Algorithm. The controller shall able to communicate to BMS with Modbus/ BACnet/ Lonworks protocol. The quantity of chillers, pumps, valves and demand sensors to be controlled shall be independently configurable on-site at the graphic user interface by selection from pull down menus, without requiring reprogramming or software download. Plant controller shall be compatible with Remote plant diagnostics & health monitoring system. |
| 31 | Functionalities |
| 32 | Manual or automatic system control (H-O-A selection) |
| 33 | Remote or local start/stop mode of operation |
| 34 | Field and factory level password security |
| 35 | Alarm and event logging of 2000 events |
| 36 | Data trending with display screen |
| 37 | Internal circuit breaker protection |
| 38 | Automatic or manual pump alternation |
| 39 | End-of-curve pump run-out protection |
| 40 | 3 standard alarms: (1) drive, motor, or pump failure, (2) system fault, (3) zone signal fault |
| 41 | Standard serial communication to VFD's |
| 42 | Logic outputs for chiller 2-way automatic ON/OFF isolation valves |
| 43 | Logic output for chiller 2-way automatic modulating bypass valve digital inputs for pump differential pressure switches. |
| 44 | Digital inputs for pump differential pressure switches on all variable speed primary pumps |
| 45 | Control of single, dualARM or Twin pumps |
| 46 | Output for remote alarm / horn signal |
| 47 | Input for silencing of remote alarm/horn |
| 48 | Automatic sequencing of Chillers |
| 49 | Pump speed, cooling valves and bypass valve PID control loop, adjustable |
| 50 | Sensorless pumps control mode |
| 51 | Cooling valves control mode (ASHRAE 90.1) |
| 52 | Separate operating status display of primary pump status, pump speed(s) and drive status |
| 53 | Separate operating status display of chiller status, demand limit, power, temperatures |
| 54 | Separate operating status display of isolation and bypass valves |
| 55 | Separate input screens for; set-points, differential pressure sensors, flow and kW monitors |
| 56 | Separate status display screens for; pump status, zone status, system status, plant status |
| 57 | Multi-colour schematic active display of mechanical room hydraulic circuit indicating operating status. |
| 58 | Manual control screen for fixed speed, by-pass, or selected variable speed settings |
| 59 | Secure front cabinet door with lock and key |
| 60 | Diagnostic test of CPU, RAM, and Flash memory |
| 61 | Sequencing, isolation valve, and modulating control for chillers in a variable primary flow application |
| 62 | Serial communications port to the VFD(s) |
| 63 | Best Efficiency Point Staging |
| 64 | End of Curve detection using flow meter |
| 65 | NS 6 Closed Type Pressurized Expansion Tank(Chilled Water) ASME STAMPED |
| 66 | Supply, installation, testing and commissioning of closed expansion tank of M.S. construction duly coated with weather protection paint, with interchangeable EPDM-BUTYL rubber membrane. The expansion tank shall be complete with safety relief valve and pressure gauge. The tank will be of pressure rating to suit the system pressure and will be sized to adequately compensate for water expansion due to operating temperature variations. For chilled/hot water application, it will be insulated with 50 mm thick insulation to the specifications and cladded with 26G-aluminum cladding. Contractor need to quote as per actual requirement with backup calculation. |
| 67 | The expansion tank shall be supplied along with pressurization unit. The pressurization unit shall consist of two nos.(1 working+1 stand-by) high pressure pumps of suitable pressure rating mounted on M.S. frame, complete with interconnecting piping, isolation valves, NRV, Y-strainer, Pressure gauge, pressure transmitter, auto-logic panel(IP 55) with dry-run protection, electrical MCB and interconnecting wiring. |
| 68 | The unit shall be housed in powder-painted canopy suitable for external installation,contractor shall submit the size calculation document before procurement. |
| 69 | NS-6.1 Minimum 4000 Liters approx. capacity tank (for chilled water system). |
| 70 | NS 7 Air/Dirt Separator for Close loop Chilled water system |
| 71 | Supply installation testing and commissioning of Deaerator-dirt separator. Flanged connections, complete with Brass drain valve 1” F (from DN 50 to DN 150), 2” F (from DN 200 to DN 300). complete with a set of concentric metal mesh surfaces to create the swirling motion required to facilitate the release of micro-bubbles and dirt to the surfaces. Epoxy resin coated steel body. Brass automatic air vent valve body. Stainless steel internal element. PP float. Brass float guide and stem. Stainless steel float lever and spring. EPDM hydraulic seals. Medium water and non-hazardous glycol solutions excluded from the guidelines of EC directive 67/548; maximum percentage of glycol 50%. Maximum working pressure 10 bar. Working temperature range 0–110°C. Particle separation rating down to 5µ. Working temperature range 0–100°C. Floor brackets as per site requirement. Third Party test report is required to be submit by contractor from manufacturer for 5µ Particle separation (TNO) |
| 72 | NS-7.1 Connection size 300 mm (for chilled water line) |
| 73 | NS 8 Air/Dirt Separator for Open loop Condenser Water Line |
| 74 | Supply installation testing and commissioning of dirt separator. Flanged connections, complete with Brass drain valve 1” F (from DN 50 to DN 150), 2” F (from DN 200 to DN 300). complete with a set of concentric metal mesh surfaces to create the swirling motion required to facilitate the dirt to the surfaces. Epoxy resin coated steel body. Stainless steel internal element. PP float. Brass float guide and stem. Stainless steel float lever and spring. EPDM hydraulic seals. Maximum working pressure 10 bar. Working temperature range 0–110°C. Particle separation rating down to 5 µ.Working temperature range 0–100°C. Floor brackets as per site requirement. Third Party test report is required to be submit by contractor from manufacturer 5µ Particle separation (TNO) |
| 75 | NS-8.1 Connection size 300 mm |
| 76 | NS 9 Vacuum Degassers |
| 77 | Supply & Installation testing & commissioning of Vacuum Degasser shall be installed in a bypass line to CHW header. It shall be able to degass a minimum of 1 CMH of water at system working pressure. Vacuum degasser shall be complete with Vacuum tube with high capacity automatic air vent with ingress preventer, Multistage centrifugal pump, Make-up water and system inlet water connections with motorized valves to enable degasser operation even at low system pressure. (Manual preset flow control valves at inlet and outlet are not acceptable), Pressure transmitter to regulate pressure / vacuum in the vacuum tube, built in flow meter to measure degassed and make-up water volumes, Microprocessor based, BMS compatible, control panel with IP54 protection, All Components, i.e. pump, vacuum tube, valves, interconnecting piping and control panel mounted on a compact steel frame. The unit shall be selected as per system's highest working pressure, proposed system shall be in line with details given in DBR & NIT. |
| 78 | For Total Chilled Water Flow Rate for Working Chillers, 4990 LPM |
| 79 | NS 10 Automatic Tube Cleaning System(ATCS) |
| 80 | Supplying, Installation, Testing and commissioning of suitable Automatic Condenser Tube cleaning system.The System shall include Injection Pump, Collection Pump, Ball Trap, Programmable Logic Controller(PLC) Panel, Multicolour HMI, Electrically operated Control Valves,Necessary Valves & Fitting, electrical control wiring & power cabling etc.to make the system complete for 3 Nos. Chillers |
| 81 | 1 set of skid containg 2 pumps,2 No. Ball traps & 2 No. Ball collectors. Complete as required |
| 82 | NS 11 Floor Mounted Air Handling Unit (With VFD) |
| 83 | Supply, Installation, Testing and commissioning of Eurovent certified factory built floor mounted chilled water double skin Air Handling Units made of 48±2 mm Panel with thermal break profile consisting of pre coated/ preplasticized G.I. casing of thickness 0.8mm outside layer and 0.8mm inside layer with polyurethane foam with Zero ODP (Ozone Depletion Substance) insulation factory injected between them by injection moulding machine with framework for each section should be bolted together with soft rubber gasket in between to make the joints airtight, complete with SISW Direct Drive PLUG Fan with EC motor (IE-4 / IE-5) suitable for 415 ± 10% V, 50Hz, 3 Phase AC. Fan shall be AMCA Certified for Air & Sound) section, 6row deep cooling coil(AHRI Certified) section with aluminium finned copper tubes with SS-304 end plates (tube thickness not less than 0.5mm). Filter sections with 50 mm thick washable synthetic type air pre-filters (EU-4 / MERV-8) & fine-filters (EU-8 / MERV-14). Drain Pan of AHUs must be made of Stainless Steel of Suitable thickness(20 G) duly insulated with required thickness & density of insulating material & diamond cut drain slope, limit switch, LED lamp, necessary vibration isolation arrangement, complete as required and as per specifications, drawings and of following capacities.The rpm adjustment through BMS,unit shall be BMS compatible with modbus protocol.Filter bypass should be minimum F 8In addition to the EC motor, the unit shall be supplied with internal control wiring and a marshalling box to facilitate ease of installation. |
| 84 | 2no.units shall be factory tested for Casing Leakage test & CFM vs Static type. Casing should be with CL1 certification from AHRI. |
| 85 | Fans shall be selected for minimum power consumption, maximum efficiency & minimum sound level. The efficiency of fan shall be minimum 70%. Sound level at 1m distance from AHU shall not exceed 65 dBA. |
| 86 | Face velocity across filters & coil shall be maximum 2.54 m/s (500 FPM). |
| 87 | NS-11.1 22000 CFM / 60mmwg SP |
| 88 | NS-11.2 19000 CFM / 60mmwg SP |
| 89 | NS-11.3 18000 CFM / 60mmwg SP |
| 90 | NS-11.4 16000CFM / 60mmwg SP |
| 91 | NS-11.5 13500CFM / 60mmwg SP |
| 92 | NS-11.6 9500CFM / 60mmwg SP |
| 93 | NS-11.7 6500CFM / 60mmwg SP |
| 94 | NS-11.8 4500CFM / 60mmwg SP |
| 95 | NS-11.9 3000CFM / 60mmwg SP |
| 96 | NS 12 Floor Mounted Treated Fresh Air Unit suitable for outdoor application at Terrace |
| 97 | Supply, Installation, Testing and commissioning of Eurovent certified factory built floor mounted chilled water double skin Air Handling Units made of 48±2 mm Panel with thermal break profile consisting of pre coated/ preplasticized G.I. casing of thickness 0.8mm outside layer and 0.8mm inside layer with polyurethane foam with Zero ODP (Ozone Depletion Substance) insulation factory injected between them by injection moulding machine with framework for each section should be bolted together with soft rubber gasket in between to make the joints airtight, complete with SISW Direct Drive PLUG Fan with EC motor (IE-4 / IE-5) suitable for 415 ± 10% V, 50Hz, 3 Phase AC. Fan shall be AMCA Certified for Air & Sound) section, 8row deep cooling coil(AHRI Certified) section with aluminium finned copper tubes with SS-304 end plates (tube thickness not less than 0.5mm). Filter sections with 50 mm thick washable synthetic type air pre-filters (EU-4 / MERV-8) & fine-filters (EU-8 / MERV-14). Drain Pan of AHUs must be made of Stainless Steel of Suitable thickness(20 G) duly insulated with required thickness & density of insulating material & diamond cut drain slope, limit switch, LED lamp, necessary vibration isolation arrangement, complete as required and as per specifications, drawings and of following capacities.The rpm adjustment through BMS,unit shall be BMS compatible with modbus protocol.Filter bypass should be minimum F 8In addition to the EC motor, the unit shall be supplied with internal control wiring and a marshalling box to facilitate ease of installation. |
| 98 | 2no.units shall be factory tested for Casing Leakage test & CFM vs Static type.Machine shall be EUROVENT CERTIFIED CASING PARAMETERS COMPLYING TO EN 1886 |
| 99 | Fans shall be selected for minimum power consumption, maximum efficiency & minimum sound level. The efficiency of fan shall be minimum 70%. Sound level at 1m distance from AHU shall not exceed 65 dBA. |
| 100 | Face velocity across filters & coil shall be maximum 2.54 m/s (500 FPM). |
| 101 | NS -12.1 13000 CFM /60.0 mmwg SP |
| 102 | NS -12.2 4500 CFM / 60.0 mmwg SP |
| 103 | VFD for Cooling Tower |
| 104 | NS 13 Supply, installation, testing & commissioning of VFD designed for HVAC applications with built-in PID controller, control panel (keypad & display) , IP-65 enclosure (for outdoor applications) & IP-20 enclosure (for indoor applications) for use on AHU fans. The display should be in alpha-numeric characters and programming facility should be in user-friendly HVAC terminology. VFD’s shall have built-in harmonic filters with THDI less than 5%. Each VFD panel to be provided with digital display showing electrical parameters like voltage, current and power consumption. Each VFD shall be installed in a dedicated external/internal enclosure and the inter connecting wires between driver and MCC shall be included. Necessary transformer, power adapters, sensors, relay etc. as required for satisfactory operation shall be in the scope of VFD supplier. It should be BMS Compatible. |
| 105 | NS-13.1 10.0 KW MOTOR RATING SUITABLE FOR OUT DOOR APPLICATION |
| 106 | NS-14.0 HI WALL SPLIT UNITS |
| 107 | Supply, Installation, testing and commissioning of Air-cooled DX type Hi-wall split air conditioners each comprising an outdoor unit(s) consisting of hermetically sealed compressor suitable for operation on 230V, 50Hz, 1 Phase AC supply, air cooled condenser, condenser fan along with Cooling thermostats etc. with outer casing and indoor fan coil unit consisting of centrifugal fans, fan motor, DX cooling coil, outer casing, filter, control and power panel with remote etc. entire cabling and wiring from indoor to outdoor, insulation and with full charge of refrigerant gas and oil, supports, canvas connection etc. complete as per drawings. The indoor and outdoor units shall be with structural steel supports, angles, rods etc. The quoted price shall also include 24G soft copper refrigerant piping with 13 mm \\"O\\" class factory backed nitrile rubber with aluminum foil from outdoor unit to indoor unit complete with insulation, refrigerant charging, PVC drain piping with 6mm thick nitrile rubber insulation, supports, clamps, fittings, connections, sleeves, supports, MCB, stabilizer etc. from main panel to the unit. The refrigerant used shall be CFC/HCFC free R-410 A. Also, EER should be in compliant with ECBC + Building requirements. |
| 108 | NS-14.1 1.5 TR Unit for server room |
| 109 | NS-14.2 1.8 / 2.0 TR Unit for UPS room |
| 110 | NS-15.0 Thermostat for Fan Coil Units- Snap acting Type (Cooling & Heating Both) |
| 111 | NS-15.1 Supply, installation, testing and commissioning of automatic control for Fan Coil Units for four pipe system consisting of snap acting digital cooling/heating thermostat, which will have provision of setting of room temperature, setting of fan speed (High, Medium, Low). The quoted price of thermostat shall include the cost of 20mm MS conduits, control cabling, MS Box etc. as required. It shall include all accessories ,mountings, wiring between thermostat & unit, terminations etc.(BMS Compatibility to be provided). |
| 112 | NS-16.0 Thermostat for AHU (Proportional type)(Cooling & Heating Both) |
| 113 | Supply, installation, testing and commissioning of latest generation digital display type BMS compatible cooling/heating thermostat with controller for cool / heat application suitable for two/four pipe system for various air handling Units. The thermostat shall have provision of setting of space temperature and display of the same. The quoted price of thermostat shall include the cost of 20mm MS conduits, control cabling, MS Box etc. as required. The cost quoted shall be excluding the control valves. It shall include all accessories ,mountings, wiring between thermostat & unit, terminations etc.(BMS Compatibility to be provided). |
| 114 | NS-17.1 Thermostat for AHU |
| 115 | NS-18.0 Electronic Air Cleaner for AHU |
| 116 | Supply installation testing and commissioning of EAC Shall be suitable to reduce harmful pollutants like particulate matter (PMx), PM 2.5, allergens, smoke, bacteria, pathogens etc. based on below principle technology viz; Impingement, Polarization and Agglomeration for passive air purification. It should be a slim structured unit specifically designed for integration in Return Air path of ceiling suspended indoor units and AHUs. EAC shall be equivalent to Merv-14 or Higher efficiency for AHU and Ductable Units with low pressure drop. It should have 3x working principles and it should be aluminum based or powder coated steel casing and should be self-contained. The EAC shall have UL certified core components. The Basic Media of Electric Filter shall Carry Class 2 Fire Rating Listing by UL for filter Media Pad Component. The units shall meet ANSI/ASHRAE 52.2/ISO16890 standards and have valid test report to verify filtration efficiency. The Supplier shall carry UL2998 certificate for testing against Zero Ozone Emission either as Whole unit or included components. The filter shall be capable of effectively reducing haze particles, smoke, mold spores, and airborne bacteria, and shall be supported by test reports from NABL-accredited laboratories verifying its performance. The Electronic Air Cleaner shall preferably be GreenPro certified by CII–IGBC (Confederation of Indian Industry – Indian Green Building Council . |
| 117 | Floor Mounted AHU |
| 118 | NS-18.1 22000 CFM / 60mmwg SP |
| 119 | NS-18.2 19000 CFM / 60mmwg SP |
| 120 | NS-18.3 18000 CFM / 60mmwg SP |
| 121 | NS-18.4 16000CFM / 60mmwg SP |
| 122 | NS-18.5 13500CFM / 60mmwg SP |
| 123 | NS-18.6 9500CFM / 60mmwg SP |
| 124 | NS-18.7 6500CFM / 60mmwg SP |
| 125 | NS-18.8 4500CFM / 60mmwg SP |
| 126 | NS-18.9 3000CFM / 60mmwg SP |
| 127 | NS-19.0 Active Purification System (Bi-Polar Ionization) For AHU |
| 128 | Supply, Installation, Testing and commissioning of Bipolar Ionisation System. The Bipolar Ionization System must be a combination of Needle Point Model for AHU (Needle Point should have Nitinol (nickel titanium) Needles and Carbon Fiber Brush Model for Cassettes and HI Wall AC units. The System should produce positive and negative ions for creating a Bio Climate rich in ions and hence neutralizing harmful pollutants including pathogens, Volatile Organic Compounds and Particulate Matter. The Carbon Brush self-balancing ionizer should be installed at the fan inlet of fan coil units, VRF cassettes, ductless splits , NeedlePoint Ionizer shall be installed at AHU and Ductable HVAC System. |
| 129 | Product should have UL 867 and UL 2998 certification (for zero ozone emission). The OEM shall have Efficacy test report on COVID from any Internationally/Nationally recognised Laboratory. The technology shall also have UL 2043 for Fire and Smoke safety certificate , ISO 16000 for safety against any Organic Byproduct and CSA C22.2#187 , CARB certification. |
| 130 | Manufacturers shall provide Test report from Internationally/Nationally recognized Lab for proven efficacy on below pathogens with minimum kill rates for the following pathogens given the allotted time and in a space condition:a) SARS-CoV-2 (COVID-19) Human Strain b) MS2 Bacteriophage (Surrogates COVID-19)c) Omicron Variant of SARS-CoV-2d) H1N1e) Total Bacterial Count Reduction rate of more than 90% from NABL Accredited Labf) Yeas & Mold/Total fungal count Reduction rate of more than 90% from NABL Accredited Lab |
| 131 | NS-19.1 22000 CFM / 60mmwg SP |
| 132 | NS-19.2 19000 CFM / 60mmwg SP |
| 133 | NS-19.3 18000 CFM / 60mmwg SP |
| 134 | NS-19.4 16000CFM / 60mmwg SP |
| 135 | NS-19.5 13500CFM / 60mmwg SP |
| 136 | NS-19.6 9500CFM / 60mmwg SP |
| 137 | NS-19.7 6500CFM / 60mmwg SP |
| 138 | NS-19.8 4500CFM / 60mmwg SP |
| 139 | NS-19.9 3000CFM / 60mmwg SP |
| 140 | NS-20.0 Supply, Installation, Testing & commissioning of IAQ Monitor to remotely measure the levels of PM 2.5, VOCs, CO2, Temperature, Humidity on a real time basis. The IAQ Monitor shall be capable of getting connected with Wi-Fi. The Monitor should be capable of sending the indoor air quality information on display Screen / Mobile/Workstation as per Client's requirement. The Monitor should indicate the quality of air through changing the colours on the display screen as per the NAAQS standards and should meet the WELL building standards. The monitor should be a 3 tier architecture including sensor Hardware, secure cloud infrastructure, monitoring apps including dashboard, android/IOS. Quoted price shall be inclusive of all necessary arrangement as required to make the unit proper functional. The System should provide Soft Assistance in form of Notifications and Alerts for Periodic Preventive Maintenance. |
| 141 | NS-21.0 Cabinet Type Inline Fans |
| 142 | Supplying, installation, testing and commissioning of INLINE FANS direct/belt driven. The cabinet shall be double skin, internally acoustically lined and constructed of galvanized steel. All outdoor application fan shall be of IP 55 rating. The fan shall be DIDW with forward curve impeller fitted with maintenance free external rotor motor. The motor shall be suitable for 220±10%/415±10%(as required).Cost to include necessary switching / Starter panel (suitable for out door applications) along with, including cabling ,wiring & earthing as required volt single phase 50 cycles AC Supplying. All units shall be complete as required with duct flexible connector and volume control damper. Complete inline fan shall have min. stated static pressure. The fan shall have low sound level exceeding not more than 40 DBA at three meter distance. |
| 143 | NS-21.1 Air Quantity : 150 CFM |
| 144 | Static Pressure : 20 mm wg |
| 145 | Motor rating : As Required |
| 146 | Duty : 6TH FLOOR PENTRY |
| 147 | NS-22.0 Supply, installation, testing & commissioning of Ceiling/Floor mounted Double skin construction,Airhandling fan section having a air intake section for ventilation / exhaust system. Each fan shall be complete with DIDW backward curved centrifugal blower (or Equivalent Performance Plug Fan), VFD compatible squirrel cage induction motor,having efficiency of IE-3 type, belt drive belt-guard and vibration isolators. The fan motor shall be suitable for 415±10% volts, 3 phase AC power supply.The fan outlet velocity shall not exceed 1800 FPM. Price shall also include double sleeve fire retardant flexible connection at the outlet.(Follow the specifications of the flexible connection as given in the sub head Airdistribution). |
| 148 | The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete Fan Section shall conform to standard specifications. The capacity of fan section shall be as follows. |
| 149 | Fan Location Space CFM mmWg SP Motor HP |
| 150 | NS-22.1 Terrace Toilet Exhaust 4500 50 3.0 |
| 151 | NS-22.2 Terrace Staircase Pressurisation 8500 40 5.0 |
| 152 | NS-22.3 Terrace Lift lobby Pressurisation 50000 40 28.0 |
| 153 | NS-22.4 Terrace Toilet Exhaust 6500 50 5.0 |
| 154 | NS-23.0 AXIAL FLOW FAN |
| 155 | Supply, Installation, Testing & Commissioning of Ceiling/ Floor Mounted Axial flow type exhaust fans complete with MS powder coated / GSS long casing (Motor should be totally accomdated inside the casing),aluminium alloy blades with aerofoil design with adjustable pitch blade. The complete fan assembly along with motor should be UL/CE Listed in accordance with BS EN120101-3:2015 by a notified body. The complete fan shall be able to operate at min. 250 Deg C for 2 Hours temp rating. The high temperature test certificate is to be submitted by fan manufacturer & same clearly indicate the make of motor used during the testing and the same make of motor should be supplied by the fan manufacture at the site. Motor shall be of 415 ± 10% volts, 50 Hz conforming to efficiency grade IE3(for car park-general exhaust fan , ventilation fan/normal case/D.G fan),IE2(for pressurization,additional supply & Smoke exhaust fan ) @ 1450 RPM for General Exhaust and Smoke Exhaust with high temperature resistance confirming to BSEN-12101-3; 2015. Sound level at 3mt distance from fan shall not be more than 80dBA, at room conditions.Capacity shall be as follows & as per detailed technical specifications complete with bird screen,factory fabricated fire retardant silicon coated round flexible duct connections, spring type anti vibration isolators,fan mounting arrangement with sound attenuator(If required). Fan Efficiency to be more than 70%. Fans shall be AMCA certified for air & sound performance. Fan selection should be on air density 1.2 Kg/cum. |
| 156 | HVAC Contractor to reconfirm the Fan Motor HP as per manufaturer recommendation. |
| 157 | Cost of Supporting arrangement should be included in the above cost of equipment installation. |
| 158 | The indicated static pressure motor rating and fan dia is only provisional. HVAC Contractor to calculate static pressure based on drawing & pressure drop of finalised equipment & submit for approval. |
| 159 | Fan Dia to be selected by the HVAC Contractor as per the Technical specification and site condition. |
| 160 | NS-23.1 Air Quantity : 15000 CFM |
| 161 | Static Pressure : 30 mm wg |
| 162 | Motor Rating : 3.0 HP (Suggested) |
| 163 | Insulation : Class H |
| 164 | Duty : FLOOR VENTILATION |
| 165 | NS-24 Condenser Water Pipe |
| 166 | Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS ‘C’ class along with necessary clamps, vibration isolators and fittings such as bends,tees etc..but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. |
| 167 | Note:- The Pipes size 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. |
| 168 | NS-24.1 600 mm dia |
| 169 | NS-24.2 500 mm dia |
| 170 | NS-24.3 400 mm dia |
| 171 | Insulated Valve |
| 172 | NS-25.0 Butterfly Valve(Manual) with C I body SS Disc, Nitrile rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot water circulation as specified |
| 173 | NS-25.1 400 mm dia |
| 174 | NS-25.2 300 mm dia |
| 175 | NS-26.0 Balancing Valve with built in measuring facility with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. |
| 176 | NS-26.1 400 mm dia |
| 177 | NS-26.2 300 mm dia |
| 178 | NS-27.0 NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16pressure rating for chilled / hot water circulation including insulation as specified. |
| 179 | NS-27.1 400 mm dia |
| 180 | NS-27.2 300 mm dia |
| 181 | NS-28 Y - Strainer of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. |
| 182 | NS-28.1 400 mm dia |
| 183 | NS-28.2 300 mm dia |
| 184 | NS-29.0 Providing and fixing in position the following Ball Valves with Strainer duly insulated as per specifications and drawings.Ball valve shall be screwed type brass/bronze lever operated, quarter turn ball valve (screwed type) of full flow with bronze /forged brass hard chrome plated ball with setting & gland of superior quality of preferably PN 16 rating. |
| 185 | NS-29.1 40 mm dia |
| 186 | NS-29.2 32 mm dia |
| 187 | NS-29.3 25 mm dia |
| 188 | NS-29.4 20 mm dia |
| 189 | NS-30 Providing and fixing in position the following Ball Valves without strainer duly insulated as per specifications and drawings.Ball valve shall be screwed type brass/bronze lever operated, quarter turn ball valve (screwed type) of full flow with bronze /forged brass hard chrome plated ball with setting & gland of superior quality of preferably PN 16 rating. |
| 190 | NS-30.1 40 mm dia |
| 191 | NS-30.2 32 mm dia |
| 192 | NS-30.3 25 mm dia |
| 193 | NS-30.4 20 mm dia |
| 194 | Valves Without Insulation |
| 195 | Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications . |
| 196 | NS-31 BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for condenser water circulation as specified |
| 197 | NS-31.1 400 mm Dia |
| 198 | NS-31.2 300 mm Dia |
| 199 | NS-32.0 NON - RETURN VALVE with dual check plate of C I body SS plates vulcanized nbr seal flanged end & pn 16 pressure rating as specified. |
| 200 | NS-32.1 400 mm Dia |
| 201 | NS-32.2 300 mm Dia |
| 202 | NS-33 Balancing Valve with built in measuring facility with C I body flanged construction with EPDM coated disc with long pitch & PN 16 pressure rating for condenser water circulation as specified. |
| 203 | NS-33.1 300 mm Dia |
| 204 | NS-33.2 200 mm Dia |
| 205 | NS-34.0 PICV For AHUs |
| 206 | Supplying, fixing, testing and commissioning of Pressure independent control valve (PICV) complete with quick-fit pressure/temperature ports. Size DN 15 (from DN 15 to DN 25).Main connections 1/2” M (from 1/2” to 1 1/4”) (ISO 228-1).Dezincification resistant alloy body and headwork. Control stem, piston and springs in stainless steel. Pressure regulator diaphragm,obturator and seals in EPDM. Asbestos-free fibre seals. Pre-adjustment indicator in PA6G30. Knob in PA6. Maximum working pressure 25 bar. Maximum differential pressure with actuator code 145013 (and 6565 series) installed 5 bar. Working temperature range -20–120°C. Nominal Dp control range 25–400 kPa. Accuracy ± 5 % of the setpoint. Flow rate regulation range 0,02–0,2 m3/h (0,02–0,2 m3/h, 0,08–0,4 m3/h, 0,08–0,8 m3/h, 0,12–1,2 m3/h,0,18–1,8 m3/h, 0,3–3 m3/h and 0,37–3,7 m3/h). The adjustment position does not affect the obturator stroke. Full stroke modulation.Flow rate pre-adjustment device with at least 10 reference positions and continuous adjustment. Leakage class V according to EN60534-4. Diaphragm pressure regulator. Complete with On - Off OR Modulating actuator |
| 207 | NS-34.1 25 mm Dia |
| 208 | NS-34.2 50 mm Dia |
| 209 | NS-34.3 65 mm Dia |
| 210 | NS-34.4 80 mm Dia |
| 211 | NS-34.5 100 mm Dia |
| 212 | NS-35 Providing, fixing, testing & commissioning of resilient rubber lined double arch vibration eliminators suitable for raw water up to 60 deg. C temperature to provide relief from stresses at pipe flanges. It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge.(PN 16 rating) |
| 213 | NS-35.1 200 mm dia |
| 214 | NS-35.2 150 mm dia |
| 215 | NS-35.3 100 mm dia |
| 216 | NS-36.0 Providing and fixing Auto air vents (Brass MOC) of following size |
| 217 | NS-36.1 20 mm dia |
| 218 | NS-37.0 Pot Strainer |
| 219 | Supplying, installation, testing and commissioning of Pot strainer. Pot Strainers body shall be fabricated out of MS plate IS 226. Thickness of sheet shall be as per size of the strainer chamfered pipes with flanges shall be provided at inlet /outlet connections of the strainer. A powerful magnet shall be provided in the body to arrest MS particles. Filter element of Pot Strainer shall be of non magnetic 18 gauge SS sheet properly reinforced to avoid damage of the element. A set of MS flanges with tongue and groove arrangement and neoprene rubber gasket shall be provided on the top cover and Pot Strainer flange with sufficient bolts and nuts to make the joint water light. The Pot strainer body shall be properly de-rusted and epoxy coated from inside and outside. |
| 220 | NS-37.1 300 mm dia |
| 221 | NS-37.2 200 mm dia |
| 222 | NS-38 Drain Pipings |
| 223 | Providing and fixing in position the following GI \\"B\\" class cut to required length and installed with screw joints including the necessary fittings (bends, tees, unions, sockets etc) duly insulated with 50 mm thick XLPE pre formed pipe section with aluminum cladding as per specifications. |
| 224 | NS-38.1 32 mm dia |
| 225 | NS-38.2 40 mm dia |
| 226 | NS-38.3 50 mm dia |
| 227 | NS-39.0 Flow switches |
| 228 | Providing and fixing in position approved make pedal type flow switches complete with copper control wiring between inlet and outlet of each chiller & decoupler line. These shall be BMS compatible. 150 DIA |
| 229 | NS-40 Louvers |
| 230 | NS-40.1 Supplying, installing, testing and commissioning of powder coated Anodized extruded aluminium construction fresh air louvers (louver with VCD , bird screen & rattle-free screen) complete as per specification. |
| 231 | NS-40.2 Supply, installation, testing & commissioning of galvanised steel construction Non Return Damper with in ducts wherever required as per approved shop drawings. |
| 232 | NS-42 Supply, installation, testing, fixing & commissioning of Air curtain, Centrifugal Type Non Recirculating. The Selection should be such that throw at the outlet of the Air Curtain is approx 21m/s. Outer Body shall be constructed in Aluminium Extruded Sections and powder coated. The Nozzle should have a uniform opening for a Laminar flow and Should have a Diverter which can Tilt the Angle of throw both inside and outside by at least 30 degrees. Fans shall be centrifugal, forward curved double inlet, lightweight Dynamically balanced made in Plastic ABS 300 by the process of Injection Molding. Blades shall be made in Aerodynamic design. Performance of Impeller shall be tested as per AMCA Standards and Guaranteed as per AMCA Publication 222-08, Application manual for Air Curtain.The Customer Entryway test requires a maximum mounting height declaration and a minimum air velocity of 3.05 m/s (600 fpm). Velocities are measured 0.9 m (3 ft) from the floor. The air cutain shall be complete as per specifications & as required. |
| 233 | DUCT THERMAL & ACOUSTIC INSULATION |
| 234 | NS-43.0 Supply and fixing of following thickness duly laminated 60 MICRON aluminium foil of mat finish closed cell nitrile rubber (class\\"O\\") insulation on existing duct after applying suitable adhesive for nitrile rubber.The joints shall be selaed with 50mm wide & 3mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required above. |
| 235 | NS-43.1 19 mm |
| 236 | NS-43.2 25 mm |
| 237 | NS-44.0 Supply, installation testing and commissioning of duct acoustic insulation inside the Duct.Ducts are included in Schedule of Quantities shall be provided with acoustic lining of thermal insulation for a distance of minimum 5 meters (or 30% of the duct length whichever is more).Insulation material: Nitrile Rubber open cell foam with Density 140 - 180 Kg/m3,with anti microbail property, passing Class 1 Fire Performance test as per BS 476 Part 7, Air Erosion test or 10,000 fpm air velocity as per ASTM C 1071-05 to be applied using manufacturer's recommended Rubber based Adhesive in a blend of solvents. |
| 238 | NS-44.1 15 mm thick duct acoustic lining |
| 239 | NS-45.0 Supplying & fixing of acoustic lining on wall and ceiling of AHU rooms with Open Cell nitrile rubber material with black glass cloth on visible side.The density of acoustic insulation material shall be within 140-180 Kg/m3.Noise Reduction Coefficient(NRC) 0.65 - 0.75. |
| 240 | NS-45.1 25 mm thickness |
| 241 | NS-46.0 Supplying & fixing of under deck insulation,50mm thick TF Quality expanded polystyrene (32 Kg/m3) or 30mm thick phenotherm. Underdeck surface of ceiling shall be cleaned and made dirt free. Insulation panels shall be pasted on this surface with BITUMINOUSE BASED ADHESIVE(ENFIX BA 60). 28g wire net shall be tightened around insulation so as to avoid any kind of sagging. |
| 242 | NS-46.1 25 mm thickness |
| 243 | FIRE DOOR |
| 244 | NS-47.0 Providing and fixing at terrace entering lobby 120 minutes fire rated steel Fire door and frame of Galvanized steel conforming to IS:277 of approved make, overall door assembly conforming to IS 3614 Part-1 & Part-2 & BS 476 Part 22 or EN 1634 as required . Fire doors should be tested at CBRI or ARAI for rating of 120 minutes. |
| 245 | Door frame shall be double rebate profile of size 143 x 57 mm made with minimum 1.6mm thick galvanized steel sheet. Frames shall be mitered and field assembled with self tabs. All provisions should be mortised, drilled and tapped for receiving suitable fire rated hardware. Suitable Rubber door silencers should be provided on the striking jamb. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frame should be grouted with cement & sand slurry necessary for fire doors on the clear masonry opening. |
| 246 | Door shutter shall be made with minimum 1.2 mm thick steel pressed formed to provide a 46mm thick fully flush double skin door shell with lock seam joints at stiled edges. The internal construction or in fill material of the door to meet desired fire rating with reinforcement/rails at top, bottom, middle and vertical stile. The infill material shall be resin bonded honeycomb core or approved equivalent. The door shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers etc complete. The edges should be interlocked with a bending radius of 1.4mm. and shall have door astragals of required profile and size provided on the meeting stile for both active and inactive leaf. The shutter is to be fixed with frame with SS ball bearing butt hinges 3mm thick. Frame shall be fixed with approved dash fasteners and concrete should be poured in hollow frame section etc. Vision panel wherever applicable should be of size at least 300 x 300mm provided as per manufacturers recommendation with a beading and screws from inside with no screws and fasteners on the surface. The glass for vision panel should be 6mm clear fire rated glass of approved make & relevant rating of the door to withstand thermal shock upto 800 degree C on hose stream test. Door frames and shutters to be finished with power coating (minimum 50 micron), all complete as per the specifications and directions of Engineer-In-Charge. (Vision panel and SS ball bearing hinges rate is inclusive of the item and other Hardware i.e. locks, door closer, handle, Panic bar, etc shall be paid for separately). |
| 247 | NS 48 Acessories |
| 248 | NS-48.1 Providing & fixing Fire rated door Closer of approved make certified for 2Hrs fire rating, all complete as per direction of Engineer in Charge. |
| 249 | NS-48.2 Providing & fixing Fire rated Panic Exit Device (Panic Bar) of approved make certified for 2Hrs fire rating for single leaf door, all complete as per direction of Engineer in Charge. |
| 250 | NS-48.3 Providing & fixing Fire rated Panic Exit Device (Panic Bar) of approved make certified for 2Hrs fire rating for double leaf door, all complete as per direction of Engineer in Charge. |
| 251 | NS-48.4 Providing & fixing Fire rated Lock with external leaver handle/panic trim for Operation From The Other Side Of The Panic Bar of approved make certified for 2Hrs fire rating, all complete as per direction of Engineer in Charge. |
| 252 | NS-48.5 Providing & fixing Fire rated Lock of approved make certified for 2Hrs fire rating, all complete as per direction of Engineer in Charge. |
| 253 | NS-48.6 Providing & fixing Stainless Steel 304 grade 300mm Long Flush Bolt with necessary screws as required in Double Leaf Doors all complete as per direction of Engineer in Charge. |
| 254 | NS-48.7 Supply of SS Ball Bearing Hinges of size 100 x 75 x 3mm complet with SS Screws of 3S2BB403030-MS Assa Abloy(Yale) Make ( 4 Nos per panel ) (Required For All Doors) as per the directions of Engineer-in-charge |
| 255 | NS-49.0 HVAC Plant Room Panel (Panel Must Be Totally type tested TTA type & as per IS 61439 part 1 & 2) |
| 256 | A INCOMER FROM MAIN LT PANEL |
| 257 | 2 No. of 1600A 4P electrically operated Drawout type ACB with Ics=Icu=Icw 50KA having Mircroprocessor based releases for O/L, S/C & E/F. |
| 258 | B METERING & INDICATION |
| 259 | 1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's |
| 260 | 1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB. |
| 261 | 1 no. indicating LED lamps for ACB On/Off/ Trip with protective SP MCB's. |
| 262 | 1 Set of CTs of the ratio 1500/5A with class 0.5 Accuracy for Metering, burden 15 VA |
| 263 | C BUSBAR |
| 264 | 1 Set of 1800A TPN Aluminium Bus Bar with colour coded PVC Sleeves |
| 265 | D BUSCOUPLER |
| 266 | 1 No. of 1600 A, 4P electrically operated Drawout type ACB with Ics=Ics=50KA having Mircroprocessor based releases for O/L, S/C & E/F protection. |
| 267 | 1 Set of Breaker ON-OFF-TRIP, Spring charged indication Lamps as required. |
| 268 | E OUTGOINGS |
| 269 | 3 Nos. 300A TP+NL MCCB, 50 kA breaking capacity (including 1 no spare) HEAT PUMP |
| 270 | 4 Nos. 630A TP+NL MCCB, 50 kA breaking capacity (including 1 no spare) CHILLERS |
| 271 | 4 Nos. 100A TP+NL MCCB, 50 kA breaking capacity (including 1 no spare) PRIMARY PUMPS |
| 272 | 4 Nos. 100A TP+NL MCCB, 50 kA breaking capacity (including 1 no spare) CONDENSER PUMP |
| 273 | 4 Nos. 63A TP+NL MCCB, 35 kA breaking capacity (including 1 no spare) COOLING TOWER |
| 274 | Supplying, Receiving, Fixing, Testing & Commissioning of HVAC Plant Room Panel as described above |
| 275 | NS-50.0 CONTROL PANELS FOR AXIAL FANS/FAN SECTION & AIR WASHERS |
| 276 | Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be provided by the electrical contractor. |
| 277 | All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. |
| 278 | All wiring and copper earthing of motors from the panel shall be included. |
| 279 | The panel shall include the following components & accessories. |
| 280 | a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. |
| 281 | b. DOL / SD starter as per HP gratings given. |
| 282 | c. Terminal block for power distribution as required. |
| 283 | d. Contractor, over load relay with built in single phasing protection. |
| 284 | e. Phase indicating lights and indicating light for `ON’ status. |
| 285 | f. 144 mm x 144 mm voltmeter and digital ammeter. |
| 286 | g. Time delay relay for delayed automatic restart of motor. |
| 287 | h. Wiring for micro switch for stopping the fan when fire damper closes (in required application). |
| 288 | i. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. |
| 289 | j. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. |
| 290 | k. All starters for Air washer pumps (as required) with cabling,wiring & earthing shall be included in their control panel for fans. |
| 291 | l. 220 / 24 V Transformer (as required by application) |
| 292 | The number of control panels shall be as follows. |
| 293 | NS-50.1 16 amps MCB, 1.5HP with DOL Starter |
| 294 | NS-50.2 16 amps MCB, 2HP with DOL Starter |
| 295 | NS-50.3 25 amps MCB, 3HP with DOL Starter |
| 296 | NS-50.4 25 amps MCB,5HP with DOL Starter |
| 297 | NS-50.5 32 amps MCCB, 7.5HP with DOL Starter |
| 298 | NS-50.6 40 amps MCCB, 10HP with Star-Delta Starter |
| 299 | NS-50.7 50 amps MCCB, 15HP with Star-Delta Starter |
| 300 | NS-50.8 80 amps MCCB, 20HP with Star-Delta Starter |
| 301 | NS-50.9 80 amps MCCB, 25HP with Star-Delta Starter |
| 302 | NS-51.0 AHU Panel (22000 CFM/19000 CFM AHU) |
| 303 | A INCOMER |
| 304 | 1 No. 32 A FP MCCB, 35 kA breaking capacity with thermal release and adjustable setting and with rotary handle. |
| 305 | B METERING & INDICATION |
| 306 | 1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's |
| 307 | 1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB. |
| 308 | 1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's. |
| 309 | 1 Set of CTs of the ratio 32/5A with class 0.5 Accuracy for Metering, burden 15 VA |
| 310 | C BUSBAR |
| 311 | 50A TPN Aluminium Bar with colour coded PVC Sleeves |
| 312 | D OUTGOINGS |
| 313 | 2 Nos. 25 A 4P MPCB (including 1 no spare) |
| 314 | 2 Nos. 10A DP MCB |
| 315 | 4 Nos. 16A SPN MCB c curve 10 KA (including 2 no spare) |
| 316 | Supplying,Receiving, fixing, testing & commissioning of AHU Panel-1 as described above |
| 317 | NS-52.0 AHU Panel (18000 CFM/16000 CFM/ 135000 CFM AHU) |
| 318 | A INCOMER |
| 319 | 1 No. 32 A FP MCCB, 35 kA breaking capacity with thermal release and adjustable setting and with rotary handle. |
| 320 | B METERING & INDICATION |
| 321 | 1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's |
| 322 | 1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB. |
| 323 | 1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's. |
| 324 | 1 Set of CTs of the ratio 32/5A with class 0.5 Accuracy for Metering, burden 15 VA |
| 325 | C BUSBAR |
| 326 | 50A TPN Aluminium Bar with colour coded PVC Sleeves |
| 327 | D OUTGOINGS |
| 328 | 2 Nos. 20 A 4P MPCB (including 1 no spare) |
| 329 | 2 Nos. 10A DP MCB |
| 330 | 4 Nos. 16A SPN MCB c curve 10 KA (including 2 no spare) |
| 331 | Supplying,Receiving, fixing, testing & commissioning of AHU Panel-1 as described above |
| 332 | NS-53.0 AHU Panel (9500 CFM/6500 CFM/ 4500 CFM / 3000 CFM AHU) |
| 333 | A INCOMER |
| 334 | 1 No. 25 A FP MCCB, 35 kA breaking capacity with thermal release and adjustable setting and with rotary handle. |
| 335 | B METERING & INDICATION |
| 336 | 1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's |
| 337 | 1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB. |
| 338 | 1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's. |
| 339 | 1 Set of CTs of the ratio 25/5A with class 0.5 Accuracy for Metering, burden 15 VA |
| 340 | C BUSBAR |
| 341 | 32A TPN Aluminium Bar with colour coded PVC Sleeves |
| 342 | D OUTGOINGS |
| 343 | 2 Nos. 20 A 4P MPCB (including 1 no spare) |
| 344 | 2 Nos. 10A DP MCB |
| 345 | 4 Nos. 16A SPN MCB c curve 10 KA (including 2 no spare) |
| 346 | Supplying,Receiving, fixing, testing & commissioning of AHU Panel-1 as described above |
| 347 | NS-54.0 MV Cable |
| 348 | Supply of following sizes of PVC sheathed PVC/XLPE insulated Aluminium conductor/copper conductor power/ multicore control armoured cable of 1.1 KV grade as required. |
| 349 | NS-54.1 3 ½ C - 400 sq mm Aluminium |
| 350 | NS-54.2 3 ½ C - 300 sq mm Aluminium |
| 351 | NS-54.3 3 ½ C - 150 sq mm Aluminium |
| 352 | NS-54.4 4C-4 sq mm Copper |
| 353 | NS-54.5 4C-6 sq mm Aluminium |
| 354 | NS-54.6 4C-10 sq mm Aluminium |
| 355 | NS-54.7 4C-16 sq mm Aluminium |
| 356 | NS-54.8 4C-50 sq mm Aluminium |
| 357 | NS-54.9 4C-70 sq mm Aluminium |
| 358 | NS-54.10 3C-4 sq mm Copper |
| 359 | NS-54.11 3C-6 sq mm Aluminium |
| 360 | NS-54.12 3C-10 sq mm Aluminium |
| 361 | NS-54.13 3C-16 sq mm Aluminium |
| 362 | NS-54.14 3C-25 sq mm Aluminium |
| 363 | NS-54.15 4 X 1.5 Sq.mm Copper |
| 364 | NS 55 Supplying and erecting approved make GRP / FRP Ladder/Perforated type Cable Tray Material – Corrosion Resistant Polyester Flame Retardant U.V. Stabilized Resin System - Manufactured from Pultruded Sections - Polyester Resin System, Glass Content : 55 – 60 % - Thickness- Rung Sq. Hollow Tube 25mm x 25mm - Fixing of Rung to Side Rail with Thermoplastic Pin & Epoxy Adhesive, Assembly Single Stroke 3 METER Length- Rung Spacing – 300mm - Length of Tray: 3000mm- Support Span – 2500mm, Deflection L/200 or < 10mm whichever is less - Specification Followed NEMA FG1 1993- UV Resistant - Flame Retardant – IS 6746 - Appendix K/UL 94, Very Low Flammability - Oxygen Index – Minimum 30% as per ASTM D 2863.Flame Spread (Extent of Burning) – 20mm as per Standard ASTM D 635 - Tensile Strength – 4000 – 8000 Kg/Cm2 as per Standard |
| 365 | ASTM D 638 - Flexural Strength – 2500 – 10000 Kg/Cm2 as per Standard ASTM D 790- Izod Impact Strength – 130 Kg/Cm2 as per Standard ASTM D 256- Compressive Strength – 2500 – 5000 Kg/Cm2 as per Standard ASTM D 695- Barcol Hardness – 50 – 65 |
| 366 | NS 55.1 (A) Width 150 mm, Side Member “C” Section : 75 x 25 x 25mm with 4mm Thickness, Loading 30Kg./METER With Concentrated Load 70Kg. at center of the span perforated type |
| 367 | NS 55.2 (B) Width 300 mm, Side Member “C” Section : 100 x 35 x 35mm with 4mm Thickness, Loading 60Kg./METER With Concentrated Load 70Kg. at center of the span perforated type |
| 368 | NS 55.3 (C) Width 450 mm, Side Member “C” Section : 100 x 35 x 35mm with 4mm Thickness, Loading 75Kg./METER With Concentrated Load 70Kg. at center of the span Ladder type |
| 369 | NS 55.4 (D) Width 600 mm, Side Member “C” Section : 100 x 35 x 35mm with 4mm Thickness, Loading 90Kg./METER With Concentrated Load 70Kg. at center of the span ladder t ype |
| 370 | NS 55.5 (E) Width 750 mm, Side Member “C” Section : 100 x 35 x 35mm with 4mm Thickness, Loading 120Kg./METER With Concentrated Load 70Kg. at center of the span ladder type |
| 371 | NS 56 Supply, installation testing and commissioning of Room/ Wall Mounting mounted co2 sensor for monitoring IAQ and actucating the AHU air supply.Sensor/Detector type -Non-dis persive infrared (NDIR).Carbon Dioxide LRL 0-2000 ppm.Signal Power Source 24 VDC/ 230VAC. |
| 372 | NS 57 Supplying of remote-controlled robots with cameras to inspect ducts, robots with brushes to dislodge dirt, and suction robots with high-powered vacuums to extract debris. The process includes robotic inspection and mechanical agitation to loosen contaminants, followed by vacuum extraction to remove them. Post-cleaning surveys and video documentation are provided to the client to make it complete and operational as per site condition and as per engineer in charge. |
| 373 | NS 58 Providing, laying, jointing, testing and commissioning of following sizes of Grooved Couplings & Grooved Fittings in pipes for Chiilled Water and Condensor Water Lines including all accessories.The Grooved Fittings shall be supplied by manufacturer of grooved Couplings.The Couplings should not need any torque to tighten upto 12\\". Tongue & Recess Couplings are not allowed. Angle Pad Design Grooved Couplings are allowed. The Minimum working pressure rating should be above 400 psi for these sizes upto 12\\".The Couplings from 14\\" and above should need AGS Groove,Welding is not allowed to join pipes |
| 374 | NSR SHIKHAR FIRE FIGHTING |
| 375 | NS 59 Providing and fixing of Fire Hose Cabinet size not less than 2.1 x 1.2 x 0.90 mtr made out of M.S. sheet not less than 1.5 mm thick having central opening and 4 mm thick glazed glass doors (Two nos.) suitably marked on the outside 'with the letters \\"FIRE HOSE\\" including necessary locking arrangement and painting in PO red colour suitable to accommodate, internal hydrant valve, 2 nos 15 mtr long Hose pipe, branch pipe, nozzle and fire man's axe. It shall be fixed inside the FHC Cabinet Complete as required . |
| 376 | NS 60 Providing and fixing standard firemans axe with heavy rubber handle. |
| 377 | NS 61 Providing and fixing dial type pressure gauge with isolation cock and copper pipe on main header Dial diameter 100 mm celebration 0-16 / sq. cm. |
| 378 | NS 62 Providing and fixing Fire Extinguishers (CO2 type powder ) 4.5 Kg Capacity complete with all accessories as per manufacturers specifications. |
| 379 | NS 63 Providing and fixing Fire Extinguishers (A, B, C type powder ) 6 Kg Capacity complete with all accessories as per manufacturers specifications. |
| 380 | NS 64 Providing and fixing Fire Extinguishers (A, B, C type powder ) 9 Kg Capacity complete with all accessories as per manufacturers specifications. |
| 381 | NS 65 Providing and fixing 25 mm dia Inspector Test Valve 25 mm with drain arrangement complete with all accessories as per manufacturers specifications. |
| 382 | NS 66 Providing and fixing Fe 36 modular Fire Extinguishers 10 Kg Capacity complete with all accessories as per manufacturers specifications. |
| 383 | NS 67 Supplying of chemical for cleaning internal rusting of fire fighting pipeing network and flushing all the fire fighting lines with anti rust chemical (like a biocide) as per manufacture standard.Repairing or replacing the leakages in the pipes after flusing and pressure testing of entire system to make it complete and operational as per site condition and as per engineer in charge. |
| 384 | LT Panel |
| 385 | NS 68 SITC of COMMUNCATION IN EXISTING LT PANEL (ONLY ACB/ MCCB ON/OFF/TRIP STATUS) |
| 386 | INCOMER FROM 1500KVA TRF |
| 387 | 2500A, FP 50KA EDO ACB with Microprocessor Base for O/L, S/C & E/F Protection Release. 2 No. (Existing) |
| 388 | UNCO MODULE FOR ON/OFF/TRIP STAUS.2 No. |
| 389 | INCOMER FROM 380KVA D.G. SET-1 |
| 390 | 800A, FP 50KA EDO ACB with Microprocessor Base forO/L, S/C & E/F Protection Release. 1 No. (Existing) |
| 391 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 392 | INCOMER FROM 1250KVA D.G. SET-2&3. 1 No. |
| 393 | 2000A, FP 50KA EDO ACB with Microprocessor Base for O/L, S/C & E/F Protection Release. 2 No. (Existing) |
| 394 | UNCO MODULE FOR ON/OFF/TRIP STAUS.2 No. |
| 395 | BUSCOUPLER X 1 |
| 396 | 1000A, FP 50KA EDO ACB with Microprocessor Base for O/L, S/C & E/F Protection Release. 1 No. (Existing) |
| 397 | UNCO MODULE FOR ON/OFF/TRIP STAUS. 1 No. (Existing) |
| 398 | 2500A, FP 50KA EDO ACB with Microprocessor Base for O/L, S/C & E/F Protection Release. 1 No. (Existing) |
| 399 | UNCO MODULE FOR ON/OFF/TRIP STAUS. 1 No. |
| 400 | BUSBAR : |
| 401 | 3200A TPN Aluminium Bus Bar with colour coded PVC. 1 No. (Existing) |
| 402 | OUTGOING SECTION-1 |
| 403 | SMOKE VENTILATION PANEL |
| 404 | 400A 4P 50KA MCCB 1 No. (Existing) |
| 405 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 406 | MSIC LOAD |
| 407 | 400A 4P 50KA MCCB 1 No. (Existing) |
| 408 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 409 | SV PANEL-2 |
| 410 | 400A 4P 50KA MCCB 1 No. (Existing) |
| 411 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 412 | PUMP PANEL |
| 413 | 250A 4P 50KA MCCB 1 No. (Existing) |
| 414 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 415 | SPARE |
| 416 | 100A 4P 50KA MCCB 1 No. (Existing) |
| 417 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 418 | OUTGOING SECTION-2 |
| 419 | AC PANEL-1 |
| 420 | 1600A, FP 50KA EDO ACB with Microprocessor Base for O/L, S/C & E/F Protection Release 1 No. (Existing) |
| 421 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 422 | CAPACITOR PANEL-1 |
| 423 | 1000A, FP 50KA EDO ACB with Microprocessor Base for O/L, S/C & E/F Protection Release.1 No. (Existing) |
| 424 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 425 | RISING MAIN-1 |
| 426 | 1600A, FP 50KA EDO ACB with Microprocessor Base for O/L, S/C & E/F Protection Release.1 No. (Existing) |
| 427 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 428 | PUMP PANEL |
| 429 | 250A 4P 50KA MCCB with Microprocessoe baseO/L,S/C & E/F Protection Release.1 No. (Existing) |
| 430 | UNCO MODULE FOR ON/OFF/TRIP STAUS |
| 431 | SPARE |
| 432 | 250A 4P 50KA MCCB with Microprocessoe baseO/L,S/C & E/F Protection Release 1 No. (Existing) |
| 433 | UNCO MODULE FOR ON/OFF/TRIP STAUS |
| 434 | 400A 4P 50KA MCCB with Microprocessoe baseO/L,S/C & E/F Protection Release 1 No. (Existing) |
| 435 | UNCO MODULE FOR ON/OFF/TRIP STAUS |
| 436 | OUTGOING SECTION-3 |
| 437 | AC PANEL-2 |
| 438 | 1600A, FP 50KA EDO ACB with Microprocessor Base for O/L, S/C & E/F Protection Release 1 No. (Existing) |
| 439 | UNCO MODULE FOR ON/OFF/TRIP STAUS |
| 440 | CAPACITOR PANEL-2 |
| 441 | 1000A, FP 50KA EDO ACB with Microprocessor Base for O/L, S/C & E/F Protection Release 1 No. (Existing) |
| 442 | UNCO MODULE FOR ON/OFF/TRIP STAUS |
| 443 | RISING MAIN-2 |
| 444 | 1600A, FP 50KA EDO ACB with Microprocessor Base for O/L, S/C & E/F Protection Release 1 No. (Existing) |
| 445 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 446 | EXTERNAL LIGHTING |
| 447 | 250A 4P 50KA MCCB 1 No. (Existing) |
| 448 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 449 | LIFT PANEL |
| 450 | 250A 4P 50KA MCCB 1 No. (Existing) |
| 451 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 452 | SPARE |
| 453 | 100A 4P 50KA MCCB with Microprocessoe baseO/L,S/C & E/F Protection Release 1 No. |
| 454 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 455 | 6TH FLOOR LOAD PANEL |
| 456 | 800A FP ATS 1 No. (Existing) |
| 457 | 800A 4P EDO ACB 50KA Microprocessor Base O/L, S/C & E/F Protection Release.1 No. (Existing) |
| 458 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 459 | BUS BAR |
| 460 | 1000A TPN 415V, ALUMINIUM BUS BAR |
| 461 | OUTGOING |
| 462 | 630A FP 50KA MCCB 1 No. (Existing) |
| 463 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 464 | 400A 4P 50KA MCCB1 No. (Existing) |
| 465 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 466 | 400A 4P 50KA MCCB 1 No. (Existing) |
| 467 | UNCO MODULE FOR ON/OFF/TRIP STAUS 1 No. |
| 468 | SITC of above items complete as required as per site condition. |
| 469 | MV Cable |
| 470 | NS 69 Supply, laying, installation and testing of following sizes of PVC sheathed PVC/XLPE insulated copper conductor armoured cable of 1.1 KV grade include termination with copper lugs and glands and complete as required as per site conditions. |
| 471 | NS 69.1 4C- 6 sq mm Copper |
| 472 | NS 69.2 4C- 4 sq mm Copper |
| 473 | NS 69.3 4C-10 sq. mm Copper |
| 474 | NS 69.4 4C*16 sq. mm Copper |
| 475 | NS 70 Supply, installation, testing and commissioning of Layer 2 managed Gigabit switch, with SFP port if required fiber connectivity. The switch shall have 2 RSTP enabled ports to communicate with other switches to built a star topology network with redundancy on CAT6 armourded UTP cable within the building complete as per specifications with all necessary accessories such as Network rack, LIUs, Patch panel, patch cords etc complete in all respect, and as required for BMS DDC Panel Networking. |
| 476 | Field instruments |
| 477 | NS 71 Differential Pressure transmitter Water |
| 478 | NS 72 PH Analyser |
| 479 | NS 73 TDS Analyser |
| 480 | NS 74 Duct Static pressure Sensor |
| 481 | NS 75 Voltage Transducer |
| 482 | Cabling and Conduiting |
| 483 | NS 76 GI Flexible conduit for termination in the DDC Panels |
| 484 | Lighting Fixtures and DALI Acessories |
| 485 | NS-77 SITC of IP20 Recessed LED DALI Downlighter made of pressure die cast aluminum housing. The front cover of the luminaire shall be made of polystyrene/polycarbonate/PMMA. Fixture should have minimum efficacy at System level (Not Chip Level) ≥120 lumens/watt & Minimum system Lumen output of 1500 lm. The downlighter shall be mandatorily back-lit & not side-lit. LED used shall have life of 50000Hrs @ L70B50, CCT of 4000°K, SDCM≤5 & CRI≥80. The LEDs used shall be SMD type only . The luminaire shall have class B serviceability. The luminaire height shall be 40MM, with minimum & m cut-out dia of 150mm & the width of the lip shall be minimum 8mm. The luminaire shall be IK02 compliant. The luminaire brand name shall be embossed/engraved/Screen printed on the luminaire/accessory/Endplate/Rim/Frame & not put using sticker The LED luminaire driver shall have isolated topology with input voltage range of 140V to 270-V having PF ≥0.90 & iTHD ≤5%. The LED driver shall have in-built surge protection of 4KV (CM & DM). The driver should have Input low voltage cut-off at 110Vac (±15Vac) & Input High voltage cut-off at 320Vac (±15Vac). The driver should have protection against 440Vac for 8 hours. The driver shall have conformal coating. The output current ripple ≤5%. The driver shall have open & short circuit protection> the driver shall comply to EMI (9KHz-30MHz). The driver casing shall be made of CRCA. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322, \\"FAT\\" before dispatch as per IS 10322 & IK Test. The the successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer before supply of material. The LED Luminaire & it's driver both should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals LM79 as per 2019 standard issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accredited lab, BIS certificate for LED Luminaire & Driver. |
| 486 | NS-78 SITC of deep recessed & recessed mounted downlighter in Round Shape. The luminaire shall be a fixed type spot light. The luminaire shall be available with beam angle options of 26° & 36°. The luminaire shall have cut-out dia of 67 (± 3mm). The LEDs shall be COB type & shall have CCT 4000K, SDCM≤3, CRI≥90. The luminaire shall deliver minimum system lumen output of 560lumens & shall have minimum system efficacy of 80lm/w. The luminaire shall have class I safety & Class B serviceability. The luminaire housing shall be either white or black in colour with options for black & white reflectors. The LED luminaire driver shall have isolated topology with input voltage range of 140V to 270-V having PF ≥0.90 & iTHD ≤5%. The LED driver shall have in-built surge protection of 4KV (CM & DM). The driver should have Input low voltage cut-off at 110Vac (±15Vac) & Input High voltage cut-off at 320Vac (±15Vac). The driver should have protection against 440Vac for 8 hours. The driver shall have conformal coating. The output current ripple ≤5%. The driver shall have open & short circuit protection> the driver shall comply to EMI (9KHz-30MHz). The driver casing shall be made of CRCA. The luminaire brand name shall be embossed/engraved/Screen printed on the luminaire/accessory/Endplate/Rim/Frame & not put using sticker. The luminaire driver shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79 , Type test as per IS10322, \\"FAT\\" before dispatch as per IS 10322 & IK Test. The successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer before supply of material. The LED Luminaire & it's driver both should be BIS registered. Successful bidder shall submit the following reports issued by NABL accredited lab before supply of material for approvals: LM79, Type Test report for luminaire, surge protection test report & current ripple test report. The bidder shall also submit the LM80 report issued by LED manufacturer, BIS certificate for LED Luminaire & Driver. |
| 487 | NS-79 SITC of Recess 2X2 LED Luminaire made of CRCA with Single piece molded Polycarbonate diffuser, and customizable backplate for branding or to create an aesthetic matching to surroundings , . The diffuser shall be so designed that it does not protrude below the luminaire/ceiling & is able to give more volumetric light & higher vertical illumination. The luminaire shall be so designed that it emits light from the inner side walls of the luminaires & shall be hollow from center. Luminaire should be having L 595mm (± 3mm), W 595mm (± 3mm) & height 93mm (± 3mm) with minimum 3000 lm with a minimum efficacy of >=90 lm/W. It should have CCT of 4000K, CRI≥80. Luminaire should have Life of 50000hrs@L70B50 Lumen maintenance. Luminaire should be available with the option of different color tiles. The height or depth of the luminaire shall be 93mm (± 3mm). The LEDs used shall be SMD type only . The luminaire shall have serviceability of Class B. The luminaire shall be IP20 compliant. The LED luminaire driver shall be DALI-2 compliant driver & shall have rated voltage as 220V to 240V. The dimming should be amplitude modulation dimming. The driver efficiency shall be ≥85%. The driver should have following compliances iTHD≤ 20% (@full load), PF≥ 0.90 (@full load), output current ripple ≤ 4%, in-built surge protection of 2KV (CM) & Life of 50000hrs. The driver should be suitable for ambient temperature of -25°C to 50°C. The driver should have open load protection, short circuit protection and over power protection. The driver should be CE marked. The driver should be in metal casing. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79 as per 2019 standard, Type test as per IS10322, \\"FAT\\" before dispatch as per IS 10322 & IK Test. The the successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer before supply of material. The LED Luminaire & it's driver both should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals LM79 as per 2019 standard issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accredited lab, BIS certificate for LED Luminaire & Driver. |
| 488 | NS-80 SITC of IP20 Integral LED 4ft batten. The batten shall have housing made of Extruded Aluminium only & the front diffuser shall be made of polycarbonate/polystyrene (Diffuser-Non yellowing type). The end caps shall be made of polycarbonate which are fixed using M3 screws. The LED used shall have life of 50000Hrs @ L70B50, CCT of 6500°K, SDCM≤5 & CRI≥80. Luminaire shall be designed to deliver minimum system lumen output of 4000lm at a system efficacy of at-least 145 lumen/watt. The measured power consumption shall not be more than 20W & ensuring minimum system lumen output of 4000lm even at lower wattages. The electronic driver used shall have a power factor ≥0.95 (@full load) and THD ≤10% (@full load), suitable for an operating voltage range of 140-270V AC, Current, Internal surge protection should be minimum 2.5KV, electrical insulation class should be Class I & driver should be of Class B serviceability. The luminaire should be at least IP65 & IK08 rated. The minimum dimensions of the batten shall be Width = 47.2mm X Height = 63.3mm X Length = 1179mm (including gland). The luminaire brand name shall be embossed//screen printed on the luminaire/accessory/Endplate/Rim/Frame & not put using sticker. The luminaire driver shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79 as per 2019 standard, Type test as per IS10322, \\"FAT\\" before dispatch as per IS 10322 & IK Test. The successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer before supply of material. The LED Luminaire & it's driver both should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals LM79 as per 2019 standard issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accredited lab, BIS certificate for LED Luminaire & Driver. |
| 489 | NS-81 SITC of Magnetic track mounted grid light led module of 9W of black housing color with CCT of 4000K, Luminaire shall be available with Easy & Flexible for installation to meet various application requirements. Track shall be with Three beam angles [Narrow (16°), Medium (23°) and Wide (36°)] according to the application. Luminaire CRI should be CRI 90 R9>50, SDCM≤5. IP02, IK03. The LED luminaire driver shall be DALI-2 compliant driver & shall have rated voltage as 220V to 240V. Frequency should be 50-60Hz. The driver efficiency shall be ≥85%. The driver should have following compliances iTHD≤ 20% (@full load), PF≥ 0.9 (@full load), output current ripple ≤ 4%, in-built surge protection of 2KV (CM) & Life of 50000hrs. The driver should have open load protection, short circuit protection and over power protection. The driver should be in metal casing. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79 as per 2019 standard, Type test as per IS10322, \\"FAT\\" before dispatch as per IS 10322 & IK Test. The the successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer before supply of material. The LED Luminaire & it's driver both should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals LM79 as per 2019 standard issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accredited lab, BIS certificate for LED Luminaire & Driver. |
| 490 | NS-82 SITC of Magnetic Track of Black Housing colour. Track shall be Surface/suspended/recessed mounted. Track shall be available in multiple sizes and patterns. |
| 491 | NS-83 SITC of flexible strip light for coves with a minimum nominal system lumen output of 2000lumens @ 16W to 17W per meter and System Efficacy of ≥120 lm/W.The LEDs shall be SMD type & shall have CCT 4000K, SDCM≤3, CRI≥80, Ra >=80; R9 >= 0 LED life class 30K Hrs @ L70B50. The strip light shall be IP20 & IK03 compliant. The strip light shall be supplied minimum in length of 5M rolls. The strip light shall have minimum 165LEDs per meter. The strip light shall be DALI dimmable. The LED luminaire driver shall be DALI-2 compliant driver & shall have rated voltage as 220V to 240V. The dimming should be amplitude modulation dimming. The driver efficiency shall be ≥85%. The driver should have following compliances iTHD≤ 20% (@full load), PF≥ 0.90 (@full load), output current ripple ≤ 4%, in-built surge protection of 2KV (CM) & Life of 50000hrs. The driver should be suitable for ambient temperature of -25°C to 50°C. The driver should have open load protection, short circuit protection and over power protection. The driver should be CE marked. The driver should be in metal casing. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79 as per 2019 standard, Type test as per IS10322, \\"FAT\\" before dispatch as per IS 10322 & IK Test. The successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer before supply of material. The LED Luminaire & it's driver both should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals LM79 as per 2019 standard issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accredited lab, BIS certificate for LED Luminaire & Driver. |
| 492 | NS-84 Supply, Installation, testing & commissioning of LED Bulkhead Luminaries, made of high-pressure die-cast Aluminium body with polycarbonate diffuser. Luminaries should be with minimum system efficacy of 110Lumen/Watt and minimum system lumen output of 1100lm.LED used shall have life of 50000Hrs @ L70B50, CCT of 6500°K, SDCM≤5 & CRI≥80. The luminaire driver shall comply to following parameters at 220V to 240V: PF≥0.90 (@full load), THD ≤ 10% (@full load) & in-built surge protection of 2.5KV. The input voltage range shall be 140V to 270V. The fixture should comply with the parameters as per IS10322. The luminaire shall have class C serviceability. The luminaire shall be IP66 & IK09 compliant. The luminaire brand name shall be embossed/engraved on the luminaire/accessory/Endplate & not screen printed or put using sticker. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79 as per 2019 standard, Type test as per IS10322, \\"FAT\\" before dispatch as per IS 10322 & IK Test. The successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer before supply of material. The LED Luminaire should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals: LM79 as per 2019 standard issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accredited lab, BIS certificate for LED Luminaire. |
| 493 | NS-85 SITC of 3 Channel DALI high frequency ballasts controller for T4/Flouroscent/ LED lamps with 3 no's of 20A Relay. Each DALI outputs allowing it to control up to 192 DALI devices with 3 channels. The DALI control signals can be programmed to operate automatically isolate the power circuit when all associated DALI channels are at 0%. The device is DIN-rail mountable integral DALI bus power supply, removing the need for an additional external device. Supply: 100-240V 50/60Hz Single Phase at 0.1A, Control Outputs: 3 x DALI Control Outputs, each supporting a full DALI universe of 192 channels including backward channel DALI Bus Power Supply, Internal 24V rated 250mA Control IO :1 x RS485 DyNet serial port / DMX, 1 x AUX programmable dry contact input. DC supply 12V @ 200 mA. |
| 494 | NS-86 SITC of Network Power Supply. Power: 15V DC 1.5 Amps regulated power supply, designed to supplement the network DC supply. Supply of 110-240V ±14% 50/60Hz Single Phase at 0.25A The switchmode design allows the device to be used with a wide range of supply voltages without the need for a manual selector setting. Size of six-unit DIN-rail mount enclosure that has a circuit breaker profile. This enables the device to be installed in all types of electrical equipment enclosures, including those with cover apertures specifically designed for circuit breakers. |
| 495 | NS-87 Supply, installation, testing and commissioning of Network Gateway to provide integration between the control systems and Ethernet networks. It is designed to provide remote control of sites and link multiple sites together, using the Internet or a corporate LAN as a backbone. The device supports the TCP/IP protocol, with static or DHCP assigned IP addressing. An integral webserver allows Browser based control scenarios and full control with iOS/Android Mobile and Tab devices. The interface incorporates a Programmable Logic Controller that can process comprehensive conditional and sequential logic and arithmetic functions and time based events and schedulings. Power: 15V DC supplied by the control system network at 200mA.Certification: CE, RCM, UL/cUL, FCC, ICES, RoHS. |
| 496 | NS-88 SITC of Antumbra Display keypad with Central Display to present multiple pages of functions & system Information. Keypad shall possess fully programmable options for Individual control / group control / Scene control / Tasks etc. Wall mounted on 2M (3 X 3 size) modular box. Front cover with Backlight, built in proximity and a built-in temperature sensor automatically adjusts air conditioning when integrated into the system. Loaded icons like presentation scenario, meeting scenario, master On/Off, Powersaving mode etc along with a LED indicator for each operations. Central LCD - Allows for system information to be shown such as temperature, time, channel level and current scene. Button function can change when navigating between the up to 16 pages. Operating on 12V DC @ 40-50mA from network. |
| 497 | NS-89 SITC of 12 Channel Multi types feed through power circuit design equivalent to 12 pole contactor & each pole should be controllable via system network. Each Switched loads should support 20A per channel upto max. of 180A per device with an inrush current of 500A. Device should support multiple wiring schemes - single phase & neutral Or three phase & neutral (Star) & should have service override switch can be accessible from the front panel. Supply Voltage: 100-240AC, system Output DC current 200mA which can support 10 button panels without any additional power supply.Device should also have dry contact Aux input . Compliance Certification: CE, RCM, UL/cUL, FCC, ICES-003, RoHS. |
| 498 | NS-90 Supply, Installation, testing & Commissioning of Digital Passive infrared (PIR) technology based occupancy sensor along with photocell operation, having high performance non regulating type, with 360 degree coverage, sensitivity options of low, high, medium and max with 10m diameter coverage area (with 7m minor and 3m major movement) having features like Power up state and setback senstivity, with operating temperature of range 0 to 40 deg C, with necessary fixing arrangements i/c programming / setting at site etc. complete as required, Certifications : CE, RCM, UL/cUL/ICES-003 & RoHS. |
| 499 | NS-91 Supply, Installation, Testing & Commissioning of System Manager Visualization Software tool (with same OEM) to Control, Monitor & Maintain. It provides users with full visibility of the lighting and energy management system status and performance, while enabling simple local or global system adjustments. Software Functions: Complete Control, Simple Scheduling, Manage routine maintainence, strike the balance, identity energy savings initiatives based on the current usage, tailored control for individual light fitting. |
| 500 | NS-92 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 501 | NS 92.1 2 Row of 14 Modular SPN DB with Metal Door as required. |
| 502 | Note: The make of items listed from NS 1 to NS 92 shall be best available in the market and shall be approved by Engineer-In-Charge. |
| 503 | NS 93 Buy Back of installed items excluding GST as per List at Schedule V, Section 5, Technical Specifications. Rates shall be quoted accordingly. |
| 504 | DSR-HVAC WORK SHIKAR BUILDING |
| 505 | Water Cooled Screw Chiller (with VFD) |
| 506 | DSR-2025/33.6 Supplying, Installation, Testing and Commissioning of following capacity floor-mounted VFD (Variable Frequancy Drive) Operated water cooled screw-type chiller machine complete with single/multi semi-hermatic mono/multi screw type compressor, with independent circuits, water-cooled Shell & Tube type condenser, Shell & Tube horizontal flooded type evaporator with carbon steel shell and seamless copper tubes with 19 mm nitrile rubber insulation i/c suitable foundation/mounting structure made of RCC/MS Structure i/c anticorosive paint, anti vibration pad, power control cable and connection inter connection etc. as per design approved by engineer-in-charge, common base frame, interconnected copper refrigerant piping and wiring, vibration Isolators, gauge panel, automatic safety controls, flow switch at evaporator and condenser and ozone friendly Chlorofluorocarbons (CFC)-free refrigerant gas R-134a. The refrigerant flow control shall use an electronic expansion valve. The chiller shall be designed for a Water Side working pressure of 150 psig and hydraulically tested at 1.5 times of design pressure . A number of properly spaced baffles shall be provided for maintaining optimum water velocity and heat transfer and the tubes shall be adequately supported. The chiller shall be Building Management System (BMS) compatible The system shall be in confirmation to IS : 16590 and CPWD Specification as amended upto date. BEE Star labeling and CPWD Specification as amended upto date and tested as per IS 16590. |
| 507 | Chilled water Leaving Temp. (6.67 °C)Chilled water Entering Temp. (12.2 °C)Evaporator fouling factor = 0.018 m2. °C/kWCondenser water Entering Temp. (32.2 °C)Condenser water Leaving Temp. (36.4 °C)Suitable for Seismic Zone and Altitude as per location/site.Microprocessor based controller. |
| 508 | DSR-2025/33.6.4 301TR-450TR BEE4 STAR RATED (3 NO 350 TR 2W+1S) |
| 509 | DSR-2025/35.2 DUCTABLE FAN COIL UNIT |
| 510 | Supplying, installation ,testing and commissioning of Ceiling Concealed Fan Coil Unit comprising of 3 rows deep chilled water cooling coil, centrifugal blowers, fractional horse power (FHP) motor, synthetic fibre filters, insulated & extended condensate drain pan along with L-type auxillary tray, casing, coil piping connections, condensate drain piping connections & wiring. Fan coil units shall be suitable for operation on 220 + 10% Volts, 50Hz, single phase power supply of following sizes & capacities. Complete as per CPWD specification and as directed by Engineer-in-charge. |
| 511 | DSR-2025/35.2.1 3.0 TR nominal capacity with 1200 CFM air quantity. |
| 512 | DSR-2025/35.2.2 2.5 TR nominal capacity with 1000 CFM air quantity. |
| 513 | DSR-2025/35.2.3 2.0 TR nominal capacity with 800 CFM air quantity. |
| 514 | DSR-2025/35.2.4 1.5 TR nominal capacity with 600 CFM air quantity |
| 515 | DSR-2025/35.2.5 1.0 TR nominal capacity with 400 CFM air quantity. |
| 516 | DSR-2025/30.1 INSULATED CHILLED WATER PIPING (resin bonded fiber glass / Mineral Wool INSULATION) |
| 517 | Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with 80 kg/cum density resin bonded fiber glass or 144 Kg/ cum density mineral wool (non Combustible) pipe section insulation covered with a layer of 120 gm/sqm polythene sheet (vapour barrier) and finally applying0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date ) at joints and repairing of damage to building etc. as per specifications and as required.Note: The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MSsheet for pipes of 400 mm dia and above. |
| 518 | DSR-2025/30.1.1 Chilled water piping of nominal size - 400mm dia. (75mm thick insulation) |
| 519 | DSR-2025/30.1.2 Chilled water piping of nominal size - 350mm dia. (75mm thick insulation) |
| 520 | DSR-2025/30.1.3 Chilled water piping of nominal size - 300mm dia. (75mm thick insulation) |
| 521 | DSR-2025/30.1.4 Chilled water piping of nominal size - 250mm dia. (75mm thick insulation) |
| 522 | DSR-2025/30.1.5 Chilled water piping of nominal size - 200mm dia. (75mm thick insulation) |
| 523 | DSR-2025/30.1.6 Chilled water piping of nominal size - 150mm dia. (50mm thick insulation) |
| 524 | DSR-2025/30.1.7 Chilled water piping of nominal size - 125mm dia. (50mm thick insulation) |
| 525 | DSR-2025/30.1.8 Chilled water piping of nominal size - 100mm dia. (50mm thick insulation) |
| 526 | DSR-2025/30.1.9 Chilled water piping of nominal size - 80mm dia. (50mm thick insulation) |
| 527 | DSR-2025/30.1.10 Chilled water piping of nominal size - 65mm dia. (50mm thick insulation) |
| 528 | DSR-2025/30.1.11 Chilled water piping of nominal size - 50mm dia. (50mm thick insulation) |
| 529 | DSR-2025/30.1.12 Chilled water piping of nominal size - 40mm dia. (50mm thick insulation) |
| 530 | DSR-2025/30.1.13 Chilled water piping of nominal size - 32mm dia. (50mm thick insulation) |
| 531 | DSR-2025/30.1.14 Chilled water piping of nominal size - 25mm dia. (50mm thick insulation) |
| 532 | DSR-2025/30.10 Condenser Water Pipe |
| 533 | DSR-2025/30.10.1 Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS ‘C’ class along with necessary clamps, vibration isolators and fittings such as bends,tees etc..but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. |
| 534 | Note:- The Pipes size 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. |
| 535 | DSR-2025/30.10.1.1 Condenser water piping of nominal size - 300mm dia. |
| 536 | DSR-2025/30.10.1.2 Condenser water piping of nominal size - 250mm dia. |
| 537 | DSR-2022/30.10.1.3 Condenser water piping of nominal size - 200mm dia. |
| 538 | Insulated Valve |
| 539 | DSR-2025/30.7 Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. |
| 540 | DSR-2025/30.7.1 BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation as specified |
| 541 | DSR-2025/30.7.1.1 BUTTERFLY VALVE (MANUAL) 200 mm |
| 542 | DSR-2025/30.7.1.2 BUTTERFLY VALVE (MANUAL) 150 mm |
| 543 | DSR-2025/30.7.1.4 BUTTERFLY VALVE (MANUAL) 100 mm |
| 544 | DSR-2025/30.7.1.5 BUTTERFLY VALVE (MANUAL) 80 mm |
| 545 | DSR-2025/30.7.1.6 BUTTERFLY VALVE (MANUAL) 65 mm |
| 546 | DSR-2025/30.7.1.7 BUTTERFLY VALVE (MANUAL) 50 mm |
| 547 | DSR-2025/30.7.2 Balancing Valve with built in measuring facility with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. |
| 548 | DSR-2025/30.7.2.1 BALANCING VALVE WITH BUILT IN MEASURING FACILITY 200 mm |
| 549 | DSR-2025/30.7.2.2 BALANCING VALVE WITH BUILT IN MEASURING FACILITY 150 mm |
| 550 | DSR-2025/30.7.2.3 BALANCING VALVE WITH BUILT IN MEASURING FACILITY 125 mm |
| 551 | DSR-2025/30.7.2.4 BALANCING VALVE WITH BUILT IN MEASURING FACILITY 100 mm |
| 552 | DSR-2025/30.7.2.5 BALANCING VALVE WITH BUILT IN MEASURING FACILITY 80 mm |
| 553 | DSR-2025/30.7.2.6 BALANCING VALVE WITH BUILT IN MEASURING FACILITY 65 mm |
| 554 | DSR-2025/30.7.2.7 BALANCING VALVE WITH BUILT IN MEASURING FACILITY 50 mm |
| 555 | DSR-2025/30.7.2.8 BALANCING VALVE WITH BUILT IN MEASURING FACILITY 40 mm |
| 556 | DSR-2025/30.7.3 NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified. |
| 557 | DSR-2025/30.7.3.1 NON - RETURN VALVE of 200 mm dia |
| 558 | DSR-2025/30.7.3.2 NON - RETURN VALVE of 150 mm dia |
| 559 | DSR-2025/30.7.3.3 NON - RETURN VALVE of 125 mm dia |
| 560 | DSR-2025/30.7.3.4 NON - RETURN VALVE of 100 mm dia |
| 561 | DSR-2025/30.7.3.5 NON - RETURN VALVE of 80 mm dia |
| 562 | DSR-2025/30.7.4 Y - Strainer of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. |
| 563 | DSR-2025/30.7.4.1 Y - STRAINER of 200 mm dia |
| 564 | DSR-2025/30.7.4.2 Y - STRAINER of 150 mm dia |
| 565 | DSR-2025/30.7.4.3 Y - STRAINER of 125 mm dia |
| 566 | DSR-2025/30.7.4.4 Y - STRAINER of 100 mm dia |
| 567 | DSR-2025/30.7.4.5 Y - STRAINER of 80 mm dia |
| 568 | DSR-2025/30.7.4.6 Y - STRAINER of 65 mm dia |
| 569 | DSR-2025/30.7.4.7 Y - STRAINER of 50 mm dia |
| 570 | VALVES WITHOUT INSULATION |
| 571 | DSR-2025/30.11 Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. |
| 572 | DSR-2025/30.11.1 BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified. |
| 573 | DSR-2025/30.11.1.1 BUTTERFLY VALVE (MANUAL) 200 mm |
| 574 | DSR-2025/30.11.1.2 BUTTERFLY VALVE (MANUAL) 150 mm |
| 575 | DSR-2025/30.11.1.3 BUTTERFLY VALVE (MANUAL) 125 mm |
| 576 | DSR-2025/30.11.1.4 BUTTERFLY VALVE (MANUAL) 100 mm |
| 577 | DSR-2025/30.11.1.5 BUTTERFLY VALVE (MANUAL) 80 mm |
| 578 | DSR-2025/30.11.2 NON - RETURN VALVE with dual plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating as specified. |
| 579 | DSR-2025/30.11.2.1 NON - RETURN VALVE of 200 mm dia |
| 580 | DSR-2025/30.8 Providing and fixing in position industrial type pressure gauges with gun metal / brass valves complete etc. as required |
| 581 | DSR-2025/30.9 Providing & fixing in position industrial type mercury thermometers complete etc. as required. |
| 582 | DSR-2025/30.11.3 Supplying, fixing, testing and commissioning of following sizes Motorized Butter fly Valve with CI Body, SS Disc, O - ring and minimum PN-16 pressure rating , conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC , and upto 20mA electric signal and providing similar transduced feedback output to control system as required. |
| 583 | DSR-2025/30.11.3.1 350 mm dia |
| 584 | DSR-2025/30.11.3.2 300 mm dia |
| 585 | DSR-2025/30.11.3.3 250 mm dia |
| 586 | DSR-2025/30.11.3.4 200 mm dia |
| 587 | DSR-2025/30.11.3.5 150 mm dia |
| 588 | DSR-2025/30.11.3.7 100 mm dia |
| 589 | DSR-2025/30.11.4 Supplying, Installation, Testing and Commissioning of following sizes electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way modulating control valve in a single body. The actuator shall be capable of accepting upto 10VDC and upto 20mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum. |
| 590 | DSR-2025/30.11.4.10 20 mm dia |
| 591 | DSR-2025/30.12.2 Supplying, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/ round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, bends, transitions, reducers, end caps, collars etc as required complete in all respect in confirmation with IS : 655 and approved drawings and specifications of following sheet thickness complete as required. |
| 592 | DSR-2025/30.12.2.1 Site fabricated GSS sheet metal rectangular ducting as per IS 655- 2006 for 0.63 mm thick |
| 593 | DSR-2025/30.12.2.2 Site fabricated GSS sheet metal rectangular ducting as per IS 655- 2006 for 0.8. mm thick |
| 594 | DSR-2025/30.12.2.3 Site fabricated GSS sheet metal rectangular ducting as per IS 655- 2006 for 1.00 mm thick |
| 595 | DSR-2025/30.12.2.4 Site fabricated GSS sheet metal rectangular ducting as per IS 655- 2006 for 1.25 mm thick |
| 596 | DSR-2025/30.13 Supplying, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc in confirmation to SMACNA/IS and as per specifications complete etc. as required. |
| 597 | DSR-2025/30.15 Supplying, Fixing, installation, testing and commissioning of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers in confirmation to SMACNA/IS and as per specifications complete etc. as required. |
| 598 | DSR-2025/30.16 Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete in confirmation to SMACNA/IS and as per specifications complete etc. as required. |
| 599 | DSR-2025/30.20 Fire Dampers |
| 600 | DSR-2025/30.20 Fire Dampers |
| 601 | DSR-2025/30.20.1 Fire damper |
| 602 | DSR-2025/30.20.2 Actuator |
| 603 | DSR-FIRE FIGHTING WORK SHIKAR BUILDING |
| 604 | DSR-2025/27.6 Providing Laying Testing and Commissioning of C class Heavy duty MS Pipe Conforming to IS : 1239 / 3589 including Fittings like elbows , tees , flanges , tapers , nuts , bolts , gaskets etc in ground including welding excavation and Providing cement concrete blocks as supports anticorrosive treatment with coaltar / asphalts tape as per IS :10221 refilling the trench etc of following sizes complete as required . |
| 605 | DSR-2025/27.6.2 150 mm Dia |
| 606 | DSR-2025/27.7 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 607 | DSR-2025/27.7.1 25 mm dia |
| 608 | DSR-2025/27.7.2 32 mm dia |
| 609 | DSR-2025/27.7.3 40 mm dia |
| 610 | DSR-2025/27.7.4 50 mm dia |
| 611 | DSR-2025/27.7.5 65 mm dia |
| 612 | DSR-2025/27.7.6 80 mm dia |
| 613 | DSR-2025/27.7.7 100 mm dia |
| 614 | DSR-2025/27.7.8 150 mm dia |
| 615 | DSR-2025/27.9 Supplying and Fixing Single Headed Internal Hydrant Valve with instantaneous gunmetal coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS : 5290 ( Type A ) with blank gunmetal material cap and chain as required . |
| 616 | DSR-2025/27.9.1 Single Headed Gunmetal Material |
| 617 | DSR-2025/27.10 Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required |
| 618 | DSR-2025/27.10.1 Single Headed Gunmetal |
| 619 | DSR-2025/27.11 Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
| 620 | DSR-2025/27.11.3 65 mm dia |
| 621 | DSR-2025/27.11.4 80 mm dia |
| 622 | DSR-2025/27.11.5 100 mm dia |
| 623 | DSR-2025/27.11.6 150 mm dia |
| 624 | DSR-2025/27.13 Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 625 | DSR-2025/27.14 Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :. |
| 626 | DSR-2025/27.14.3 65 mm dia |
| 627 | DSR-2025/27.14.4 80 mm dia |
| 628 | DSR-2025/27.14.5 100 mm dia |
| 629 | DSR-2025/27.14.7 150 mm dia |
| 630 | DSR-2025/27.14.8 200 mm dia |
| 631 | DSR-2025/27.14.9 250 mm dia |
| 632 | DSR-2025/27.16 Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : |
| 633 | DSR-2025/27.16.1 Gun Metal |
| 634 | DSR-2025/27.17 Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.(a) 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585(b) 20 mm nominal internal dia gun metal globe valve & nozzle.(c) Drum and brackets for fixing the equipmets on wall.(d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
| 635 | DSR-2025/27.17.2 40 m |
| 636 | DSR-2025/27.18 Supplying and Fixing 63 mm dia Gunmetal Material Short Branch Pipe with 20 mm nominal internal diameter size nozzle conforming to IS : 903 suitable for instantaneous connection to interconnect hose pipe coupling as required |
| 637 | DSR-2025/27.18.1 Gun Metal |
| 638 | DSR-2025/27.19 Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required: |
| 639 | DSR-2025/27.19.1 2 way-100 mm dia M.S. Pipe |
| 640 | DSR-2025/27.19.2 4 Way 150 mm dia MS Pipe |
| 641 | DSR-2025/27.20 Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required. |
| 642 | DSR-2025/27.23 Providing & fixing flow switch in following size M.S pipe including connection etc as required . |
| 643 | DSR-2025/27.23.2 150mm dia |
| 644 | DSR-2025/27.26 Supplying, installation, testing & commissioning of deluge valve (to be used for water curtains) UL listed with wet pilot basic trim assembly for DVA with test and alarm, drip and drain valve with water motor gong complete as required. |
| 645 | DSR-2025/27.26.4 150mm dia |
| 646 | DSR-2025/27.27 Providing, installation, testing & commissioning of water curtain nozzle 15mm dia nickel chrome plated brass, BSPT, K-factor as per design consideration complete as required. |
| 647 | DSR-2025/27.21 Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 °C with required accessories : |
| 648 | DSR-2025/27.21.1 Pendent Sprinkler |
| 649 | DSR-2025/27.21.2 Upright Sprinkler |
| 650 | DSR-2025/27.21.3 Horizontal side wall sprinkler |
| 651 | FIRE FIGHTING PUMPS |
| 652 | DSR-2025/27.1 (a) Supplying, installation, testing and commissioning of Electric driven Main Fire Pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required :(b) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018.(d) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(e)Suitable cement concrete foundation duly plastered with anti vibration pads. |
| 653 | DSR-2025/27.1.4 2280 lpm at 88 m Head |
| 654 | DSR-2025/27.2 (a) Supplying, installation, testing and commissioning of diesel engine driven main fire pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump)(b) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.(d) M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required.(e) Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 655 | DSR-2025/27.2.4 2280 lpm at 88 m Head |
| 656 | DSR-2025/27.3 (a) Supplying, installation, testing and commissioning of electric driven pressurisation pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)(b) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018.(d) M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(e) Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 657 | DSR-2025/27.3.1 180 LPM at 88 m Head |
| 658 | DSR-2025/27.4 (a) Supplying, installation, testing and commissioning of electric driven terrace pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(b) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018.(d) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(e) Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 659 | DSR-2025/27.4.2 450 lpm at 35 m Head |
| 660 | DSR-2025/28.2 INTELLIGENT FIRE ALARM SYSTEM |
| 661 | DSR-2025/28.2.1 Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 662 | DSR-2025/28.2.1.1 Ten Loop Panel. |
| 663 | DSR-2025/28.2.1.2 Two Loop Panel. |
| 664 | DSR-2025/28.2.2 Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required. |
| 665 | DSR-2025/28.2.3 Supplying, installation, testing & commissioning of repeater panel with 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. |
| 666 | DSR-2025/28.2.4 Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 667 | DSR-2025/28.2.5 Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 668 | DSR-2025/28.2.6 Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
| 669 | DSR-2025/28.2.7 Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 670 | DSR-2025/28.2.9 Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. |
| 671 | DSR-2025/28.2.10 Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 672 | DSR-2025/28.2.11 Supplying, installation, testing & commissioning of addressable phone control module complete as required. |
| 673 | DSR-2025/28.2.14 Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 674 | DSR-2025/28.2.15 Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 675 | DSR-2025/28.2.16 Supplying, installation, testing & commissioning of addressable strobe complete as required. |
| 676 | DSR-2025/28.2.17 Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required. |
| 677 | DSR-2025/28.2.19 Supplying, installation, testing & commissioning of fire fighter phone jack complete as required. |
| 678 | CABLING & WIRING |
| 679 | DSR-2025/28.5.1 Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. |
| 680 | DSR-2025/28.5.2 Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. |
| 681 | DSR-2025/28.5.4 Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
| 682 | BMS WORKS - SHIKHAR BUILDING |
| 683 | CENTRAL CONTROL SERVER |
| 684 | DSR-2025/42.1 Supplying Installation Testing Commissioning of Central Control Server System comprising of Intel® Xeon® CPU E5-2640 x64 (or better) compatible with dual and quad core processors, Windows 11 (Professional, Enterprise, Ultimate, 64 bit), Windows Server 2013 R2 (Standard, Enterprise, 64 bit) 16 GB or more, Video card and monitor capable of displaying at 1024 x 768 resolution or better, Latest Microsoft Licence Version Operating System Loaded with MS OFFICE 2019 Professional, Word, EXCEL, Power Point, Outlook Express, Microsoft Team official version lifetime licences suitable for running BMS software complete etc. as required. |
| 685 | DSR-2025/42.2 PC SystemSupplying Installation Testing Commissioning of Client PC System comprising of PC Hardware with minimum11th Gen Intel® I7 processor CPU E5-2640 x64 (or better), compatible with dual and quad core processors minimum 3.1 Ghz and 8GB or higher RM,Hard Drive Space of 256 GB SSD or better, Video card and monitor capable of 1920 x 1080 pixel resolution or better with Ethernet adapter (10/100/1000 Mbps with RJ-45 connector) with 2 GB or higher Graphics card suitable for BMS System complete etc. as required. |
| 686 | DSR-2025/42.3 LaserJet printerSupplying Installation Testing Commissioning of LaserJet printer having printing resolution 1200 x 1200 dpi, (dot/inch) or better, 21 to 30 ppm printing speed (LaserJet) complete etc. as required |
| 687 | DSR-2025/42.4 LED DisplaySupplying, Installation, Testing and Commissioning of following size LED display (LED monitor) industrial grade with 3840x2160 resolution or better, USB playback, bluetooth and miracast connectivity, 4X HDMI 2.0, DP 1.2, HDR 10/10+, brightness: 500-nits. or better, Video wall mode should be available,contrast ratio: 1200:1, OPS slot, viewing angle (H/V):170°/ 170°, response time less than 12ms, Display control shall be on monitor screen and programmable with remote (remote shall be supplied with system), Key Board, Optical Mouse, etc. as required. |
| 688 | DSR-2025/42.4.2 42 inch or larger |
| 689 | DSR-2025/42.5 Software for Building Management System : Supplying Installation Testing Commissioning of Necessary Software (UL listed) Packages containing Building Management with Capability of Collection, Storage, Processing and Controlling all the Data. Software shall support Open Standard Protocols like XML, BACnet, Modbus, Lon works etc. and without the use of Proprietary Protocols, with Enterprise Level Database Like MS SQL complete Lifetime Licenced & capable to collect, store & access all points from Fire Alarm Systems, IT Systems, Automation Systems,HVAC System, Lift, Energy management, Water Management System, etc. to create & monitor historical & event data, event management data, alarm management data & reporting data, Email Alerts for Critical alarms for all the systems. The scope includes additional software required by BMS software (to enable a standard Web browser) to be resident on the DDC/client machine (manufacture-specific browsers shall not be acceptable). User log-on identification and Password shall be required & a minimum three-layered security system(User interface Level, Application Level and Data Base Level) to be deployed for safety. The supplied computer software shall employ objectoriented technology (OOT) for representation of all data and control devices within the system. This datashall reside on a server for all database access (Systems requiring proprietary database and user interface programs shall not be acceptable).All components and controllers supplied under this -to- by a Master / Global / Host to pass data shall NOT beacceptable). Physical connection of BACnet/MOD BUS devices shall be via Ethernet at all levels. The License must be provided by default. The BMS software shall be complete in all respect to cater the following different numbers of points managed in the installation. |
| 690 | Special Note - The Software shall have 3D & HD vector dynamic graphics with Autocad import of plan with Zoom In & Zoom Out facility, Native 64 Bit System, Multi-Monitor Support-( Max 4 Nos), Multi-language support, BTL, UL, EN Certified System, BACnet Profile B-AWS (Advanced workstation) as per the BTL Listing, dot net platform, Certified OPC DA Server by OPC Foundation, Web-Based Server software shall permit use of Standard Web-Browsers such as Microsoft Internet Explorer, Netscape Navigator, etc. The Software shall comply to international standards and strive to deliver products that meet security standards such as ISA/IEC 62443, UL2900, ISO/IEC 27001, ISO/IEC62443 and OWASP. Cybersecurity audit trail, 4-eye principle, Seamless integration of certificates within customer IT infrastructure, Microsoft’s active directory-based authentication, Use of network infrastructure that supports physical network or VLAN segmentation, Placing the web server in a “demilitarized zone” (DMZ), End-to-end encryption, from client to server, End-to-end encryption between servers, Certificate-based data exchange, Encrypted backups. |
| 691 | DSR-2025/42.5.1 For Upto 500 point included |
| 692 | DSR-2025/42.5.2 For Upto2500 point included |
| 693 | DSR-2025/42.6 Touchscreen Color portable operator terminal Supplying Installation Testing Commissioning of following sizes Touchscreen Color portable operator terminal capable of connecting to one of the controllers on the communication bus and view parameters of the complete system. The terminal should be capable of viewing /changing parameters and trends, the specified parameters as per requirement etc. as required. |
| 694 | DSR-2025/42.6.2 7\\" Touch screen |
| 695 | DSR-2025/42.7 DDC CONTROLLERS |
| 696 | Supplying Installation Testing Commissioning of IP Based DDC controller capable of fully “stand- alone” operation i.e. In the event of loss of communication with other DDC’s or Control Station, they shall be able to function on their own. The controllers shall consistof dual/quad core 32 bit microprocessors with EPROM based operating system on BACNET. The network Topology shall not allow single point failure. Each DDC on field level shall have embedded TCP/IP (10/100Mbps) connectivity so that it can be hooked into the Local Area Network (LAN) provided by the client or on dedicated network . Each DDC can be accessed from the Graphical User Interface (GUI) or from a standard Web browser (WBI) by connecting the server alongwith inbuilt web browser. All controllers shall accept 230V+/- 10%, 50Hz Uninterrupted power supply provided by end user. Controller shall support DHCP addressing over Local Area Network (LAN) so that the static IP requirements get reduced however a single static IP shall be provided for system so that it can be hosted on to internet in consultation with end user. The microprocessor based DDC’s shall be provided with power supply, analoge to Digital and Digital to analoge converters with memory and capacity to accommodate input/output (I/O) hardware points (with or without an expansion board). EachDDC should have own board and shall accept 0-10 V / 4-20mA input signal having Minimum 20% spare capacity considered for expansion. Each DDC on field level should have minimum 128MB RAM & 64MB Flash memory. Following type of All controllers should be mandatorily BTL approved with B-BC profile complete etc. as required. |
| 697 | DSR-2025/42.7.1 DDC Controller-Type-I (Support upto 32 Points) |
| 698 | DSR-2025/42.7.2 DDC Controller-Type-II (Support upto 64 Points) |
| 699 | DSR-2025/42.7.3 DDC Controller-Type-III (Support upto 96 Points) |
| 700 | DSR-2025/42.7.4 DDC Controller-Type-IV (Support upto 128 Points) |
| 701 | EXPNSION IO MODULE |
| 702 | DSR-2025/42.8 Supplying Installation Testing Commissioning of following type of input output (IO) expansion modulecomplete etc. as required. |
| 703 | DSR-2025/42.8.1 I/O Module with 4 UIO channels |
| 704 | DSR-2025/42.8.2 I/O Module with 8 UIO channels |
| 705 | DSR-2025/42.8.4 I/O Module with 8 DI channels |
| 706 | DSR-2025/42.8.6 I/O Module with 8 DO channels |
| 707 | Enclosure for DDC |
| 708 | DSR-2025/42.9 Supplying Installation Testing Commissioning of following sizes Powder coated wall mounted lockable and secure enclosure for DDC panel made of 16 SWG sheet steel IP -55 rated with proper internal mounting accessories for DDC such as DIN Rails, terminal block for cable terminations, well dressed for all internal cabling, ferruling, tagging etc. The DDC panels shall have power supply and connections for other peripheral equipment, switchgear protections,isolation transformer, earthing, relays, fuses, auxiliary power output socket & lamp etc. as required. |
| 709 | DSR-2025/42.9.1 500mmX500mmX200 mm |
| 710 | DSR-2025/42.9.2 600mmX600mmX200mm |
| 711 | DSR-2025/42.9.3 800mmX1000mmX200mm |
| 712 | Integration Unit |
| 713 | DSR-2025/42.10 Supplying Installation Testing Commissioning following type 3rd party Integration unit to provide the interface between Ethernet LAN and the 3rd party field control devices or any other devices which need to be integrated. These shall also provide supervisory capability of functions over the devices connected to it. The purpose of using these units should be limited to integrate the devices only. The Unit must have two onboard Ethernet port, minimum 2/3 on board RS485 ports. The Integration unit should have inbuilt 4GB memory for program storage. The Unit must communicate over TCP/IP with communication speed of 0/100MBPS. The Integration unit should be capable of handling multiple protocol simultaneously such as Bacnet, Modbus, SNMP restricted to single protocol. All integrators should be mandatorily BTL listed. The integration unit shall be housed in suitablesize sheet steel enclosure made of 1.6mm thick CRCA sheet, lockable front door with glass,arrangement for cable entry and duly powder coated complete etc as required. |
| 714 | DSR-2025/42.10.1 Integrator for 500 Points |
| 715 | DSR-2025/42.10.2 Integrator for 1250 Points |
| 716 | DSR-2025/42.10.3 Integrator for 5000 Points |
| 717 | Field instruments |
| 718 | DSR-2025/42.11 Supplying Installation Testing Commissioning of following Field Devices including connection etc. as required |
| 719 | DSR-2025/42.11.1 Water Differential Pressure (DP) Switch for Pump Status. |
| 720 | DSR-2025/42.11.2 High/Low Level Switch for Tank Level Monitoring. |
| 721 | DSR-2025/42.11.3 Air DP Switch for Fan Run Status. |
| 722 | DSR-2025/42.11.4 Duct CO2 Sensor, 0-2000ppm, 0-10V/4-20mA Output. |
| 723 | DSR-2025/42.11.5 Outside Temp & Humidity Sensor with radiation shield.Measuring Range: Temp:- -15 to 50 deg C & RH 0-100%,Accuracy: +/- 1 degC +/- 3% |
| 724 | DSR-2025/42.11.6 Immersion Temp Sensor for CHW line. Measuring range: -30 to 110 deg C, Accuracy: +/- 1.3 Deg C |
| 725 | DSR-2025/42.11.7 Water Pressure Sensor . Accuracy:+/-0.3% FSL |
| 726 | DSR-2025/42.11.8 Duct type temperature sensor Measuring range: -30 to110 degC, Accuracy: +/- 1.3 degC |
| 727 | DSR-2025/42.11.9 Current sensing relay |
| 728 | DSR-2025/42.11.10 Wall Mount Temp. Sensor |
| 729 | DSR-2025/42.11.11 Wall/Ceiling Mount CO Sensor |
| 730 | DSR-2025/42.11.12 Differential pressure switch for filters & Blowers |
| 731 | DSR-2025/42.11.13 Bi-Level Switches (Hi/Low) |
| 732 | DSR-2025/42.11.14 Water Level Sensor |
| 733 | DSR-2025/42.11.15 Explosion proof level Switch |
| 734 | DSR-2025/42.11.16 Water Flow Switch |
| 735 | DSR-2025/42.11.17 Indoor Air Quality Sensor (CO2,T,H,PM,TVOC) |
| 736 | DSR-2025/42.11.18 Ultrasonic Water BTU Meter including digital display (Clamp-On) suitable for Pipe sizes dia upto 250mm |
| 737 | Cable Tray |
| 738 | DSR-2025/4.1 Supplying and installation following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 739 | DSR-2025/4.1.1 100 mm width X 50 mm depth X 1.6 mm thickness |
| 740 | DSR-2025/4.1.3 225 mm width X 50 mm depth X 1.6 mm thickness |
| 741 | Conduit |
| 742 | DSR-2025/1.20 Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 743 | DSR-2025/1.20.2 25 mm |
| 744 | MV Cable Laying |
| 745 | DSR-2025/10.7 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 746 | DSR-2025/10.7.1 Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 747 | DSR-2025/10.7.2 Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 748 | DSR-2025/10.7.3 Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 749 | DSR-2025/10.7.4 Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 750 | DSR-2025/10.8 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 751 | DSR-2025/10.8.1 Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 752 | DSR-2025/10.8.2 Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 753 | DSR-2025/10.8.3 Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 754 | DSR-2025/10.8.4 Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 755 | DSR-2025/11.1 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 756 | DSR-2025/11.1.31 3½ X 400 sq. mm (82mm) |
| 757 | DSR-2025/11.1.30 3½ X 300 sq. mm (70mm) |
| 758 | DSR-2025/11.1.26 3½ X 150 sq. mm (50mm) |
| 759 | DSR-2025/11.1.32 4 X 10 sq. mm (25mm) |
| 760 | DSR-2025/11.1.33 4 X 16 sq. mm (28mm) |
| 761 | DSR-2025/11.1.35 4 X 50 sq. mm (35mm) |
| 762 | DSR-2025/11.1.7 3 X 10 sq. mm (22mm) |
| 763 | DSR-2025/11.1.8 3 X 16 sq. mm (25mm) |
| 764 | DSR-2025/11.1.9 3 X 25 sq. mm (25mm) |
| 765 | DSR-2025/11.1.34 4 X 35 sq. mm (32mm) |
| 766 | Cables (BMS System) |
| 767 | DSR-2025/39.17 Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Cable in existing conduit/ on surface, Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with OperatingTemperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force : 11.5Kg etc. complete as required. |
| 768 | DSR-2025/39.17.1 1 Run of cable |
| 769 | DSR-2025/39.17.2 2 Run of cable |
| 770 | DSR-2025/39.17.3 3 Run of cable |
| 771 | DSR-2025/39.16 Supplying, Installation, Testing and commissioning of RJ45 Connector for CAT 6/6A Cables. RJ45 modular plug supports 4 twisted pairs, 8 positions, 8 connectors. Housing: PC, UL94V-2, transparent color, Use for 24- 26 AWG stranded wires etc. complete as required. |
| 772 | Wires and DB's for Lights |
| 773 | DSR 2025/1.10 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 774 | DSR 2025/1.10.3 Group C |
| 775 | DSR 2025/1.14 Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 776 | DSR 2025/1.14.1 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 777 | DSR 2025/1.14.2 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 778 | DSR 2025/1.14.9 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 779 | DSR 2025/1.14.10 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 780 | DSR 2025/1.17 Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 781 | DSR 2025/1.17.2 2 x 1.5 sq. mm |
| 782 | DSR 2025/1.21 Supplying and fixing of following sizes of medium class PVC conduit along with accessories insurface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 783 | DSR 2025/1.21.2 25 mm |
| 784 | DSR 2025/1.21.3 32 mm |
| 785 | DSR 2025/1.55 Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 786 | DSR 2025/1.55.3 Group C |
| 787 | DSR 2025/2.10 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 788 | DSR 2025/2.10.1 Single Pole |
| 789 | DSR 2025/2.10.3 Double pole |
| 790 | DSR 2025/2.10.5 Triple pole and neutral |
| 791 | DSR 2025/2.3 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 792 | DSR 2025/2.3.2 8 way, Double door |
| 793 | DSR 2025/2.4 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 794 | DSR 2025/2.4.1 8 way (4 + 24), Double door |
| 795 | DSR 2025/2.11 Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 796 | DSR 2025/2.14 Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 797 | DSR 2025/2.14.3 63A |
| 798 | DSR 2025/2.15 Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 799 | DSR 2025/2.15.3 63 A |
| 800 | DSR 2025/2.3 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 801 | DSR 2025/2.3.4 16 way, Double door |
| 802 | DSR 2025/39.18 Supplying, drawing, Testing and commissioning of Cat6A UTP 4 pair, 23 AWG solid copper cable in existing conduit/ on surface, U/FTP, LSZH, NonPlenum, Horizontal (solid) Cable suitable for high speed data networking application supporting upto 10Gbps over a 100 meter channel. The 4 Unshielded Twisted Pairs (UTP) cable with color coded insulation for easy indentification should have FLAME PROPERTIES i.e. Flammability Test - IEC 60332-1, Smoke Density - IEC 61034, LSZH standards compliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE 802.3an, RoHS. Delay Skew should be < 45NS. The outer Cable Diameter should be 7.5 + 2 mm. Cable should have been tested and verified by UL/ ETL etc. complete as required. |
| 803 | DSR 2025/39.18.1 1 Run of cable |
| 804 | CIVIL ITEMS - False Ceiling |
| 805 | DSR 2023-15.57Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in- charge. |
| 806 | DSR 2023-12.45.3 Providing and fixing false ceiling at all heights including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer’s specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with :12.5 mm thick tapered edge gypsum moisture resistant board |
| 807 | DSR 2023-26.27.3 Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595 mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance ≥ 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32 mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised@80gsm) 50 mm long 8 mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size 24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge.With 16 mm thick beveled tegular mineral fibre Antimicrobial false ceiling tile confirming to ISO 5 (class 100 ) specifications |
| 808 | Note: The make of items listed from Sl. No. 1 to 309 shall be best available in the market and shall be approved by Engineer-In-Charge. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail