| 1 | Dismantling of overhead lines comprising of copper / aluminium overhead conductor, G.I. wire, cross arms, insulators etc. as reqd. |
| 2 | Dismantling of pole / street light standard / strut embeded in cement concrete foundation etc. as reqd. |
| 3 | Erection of metallic pole of length above 8.0mts. and upto 10.0mts. in cement concrete (1:3:6) (1 cement : 3 coarse sand : 6 graded stone of 40mm. nominal size) foundation including excavation & refilling etc. as reqd. |
| 4 | Painting of swaged steel tubular pole of 10 mtr. length with one coat red-oxide & two coats of aluminium paint of good quality (reputed make). |
| 5 | Shifting of poles from different locations of mine to workshop / site and vice versa. |
| 6 | Supplying and erection of stay set complete (galvanised) with 19/20 mm dia x 1.8 metres long stay rod, anchor plate of size 45 cm x 45 cm x 7.5 mm, thimble, stay clamps, bow tightener, 7/ 4.00 mm dia G.I. stay wire and strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. |
| 7 | Supplying of channel iron 75mm. x 40mm. x 6mm. (7.14kg. per metre) cross arm for 4-wire overhead line complete with clamps, bolts and nuts etc. including drilling of holes for insulator pins etc. (as per drawing) and painting with primer and finish paint as reqd. |
| 8 | Supplying of channel iron 75mm. x 40mm. x 6mm. (7.14kg. per metre) VERTICAL cross arm for 4-wire overhead line complete with two nos. of 50mm x 6mm flat iron clamps projected & welded with 50mm x 50mm x 6mm anlge iron pieces, bolts and nuts including drilling of holes for insulator pins etc. and painting with primer and finish paint as reqd. |
| 9 | Erection of angle iron/channel iron cross arm on wood/RCC/PCC/steel tubular/rail pole etc. as reqd. |
| 10 | Supplying & erection of flat iron 40 mm. x 3 mm. for carrying G.I. wire complete with nut, bolt, washers etc. including drilling holes and painting with primer & finish paint as reqd. |
| 11 | Supplying & erection of 100 mm. x 65 mm. pin insulator with G.I. spindle and nuts etc. as reqd. |
| 12 | Supplying & erection of 75 mm. x 90 mm. shackle insulator with G.I. bolt, nuts and straps etc. as reqd. |
| 13 | Supplying & erection of 75 mm. x 90 mm. shackle insulator with G.I. spindle, nuts, bolts etc. as reqd. |
| 14 | Erection of all aluminium conductor of 7/1.96 mm to 7/3.10 mm dia. and above including binding etc. as reqd. |
| 15 | Earthing with G.I. earth plate 600mm. x 600 mm. x 6 mm. thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 mtr. long with charcoal / coke and salt as reqd. |
| 16 | Supplying & laying 25 mm x 5 mm G.I. strip at 0.50 metre below ground as strip earth electrode including connection / terminating with G.I. nut, bolt, spring, washer etc. as reqd. (Jointing shall be done by overlapping and with 2 sets of G.I. nut, bolt & spring washer spaced at 50 mm.). |
| 17 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of size upto 35 sq. mm. in the existing RCC / HUME / METAL pipe as reqd. |
| 18 | Laying of one number PVC insulated & PVC sheathed / XLPE power cable of 1.1KV grade of size upto 35 sq. mm. direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as reqd. |
| 19 | Supplying & fixing of 100 amps. TPN, switch disconnector fuse unit with ISI marked HRC fuses including testing, commissioning etc. as reqd. |
| 20 | Supplying & fixing of 100A, 415V, 4-pole MCCB having 30KA breaking capacity including testing, commissioning etc. as reqd. |
| 21 | Supplying & erection of cradle guard at 01 span length of O/H line with 8 SWG G.I. wire, 75mm x 40mm MS channel iron, 40mm x 6mm MS flat iron clamps, nuts, bolts & washers and painting with primer and finish paint as reqd. |
| 22 | Total impact of GST plus Labour Cess [@ 1 % (BOCW Cess to be deducted from the RA bill as per the value of the work progress)] for the purpose of CTC Please Enable Macros to View BoQ information |