| 1 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 2 | 2x10 sq.mm |
| 3 | 4x10 sq.mm |
| 4 | Make:- finolex/Anchor/Plaza |
| 5 | Supplying and fixing 6 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 6 | Single Pole |
| 7 | Make:- L&T/Anchor/Schiender |
| 8 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 9 | 63 Amps |
| 10 | Make:- L&T/Anchor/Schiender |
| 11 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 12 | 6 way, Double door |
| 13 | 8 way, Double door |
| 14 | 12 way, Double door |
| 15 | Make:- L&T/Anchor/Schiender |
| 16 | Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 17 | 32 A- 100 A 18 KA |
| 18 | 160A-200 A 25 KA |
| 19 | Make:- L&T/Anchor/Schiender |
| 20 | Supplying and fixing of following ways surface/ recess mounting, 415 volts, TPN MCB distribution board with color coted wire set, 100 Amp insulated bus bar, neutral bar with shroud, earth war, cable type blanking plate and circuit identification lebel with provision for 4 Pole MCB/RCCB as incomer and SP MCB as outgoing as required. |
| 21 | 4 Way (4 +4+ 4), TPN, DB, double door |
| 22 | Make:- L&T/Anchor/Schiender |
| 23 | Supplying and fixing 63 amps rating, four Pole 415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 24 | 63 Amp |
| 25 | Make:- L&T/Anchor/Schiender |
| 26 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 27 | Earthing with Copper earth plate 600 mmx600 mmx 6 mm thick |
| 28 | Providing and fixing Copper tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For Vertical run) |
| 29 | Copper tape 20 mm X 3 mm thick |
| 30 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 31 | 8 SWG Copper Wire Please Enable Macros to View BoQ information |