| 1 | Wiring for light point /exhaust fan point/ with 1.5 sq mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class pvc conduit, with piano type switch, phonlic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq mm FRLS pvc insulated copper conductor single core cable etc. as required.Group - C |
| 2 | Supplying and fixing metal box of 180 X 75 mm x 60 MM deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in fornt including providing and fixing 6 Pin 5/6 & 15/16 A socket outlet and 15/16 A piano type switch, connection painting etc as required. |
| 3 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, minature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) Single pole |
| 4 | Supplying and fixing following way, single pole and neutral, sheet steel MCB distribution board, 240 volt on surface / recess, complete with tinned copper bus bar, neutral bus bar interconnections, powder painted including earthing etc. as required (But without MCB/RCCB/Isolator)a) 8 Way, Double door |
| 5 | Supplying and fixing following rating, double pole, 240 V, Isolator in the existing MCB DB complete connections, testing and commissioning etc. as required.a) 63 A |
| 6 | Providing and installation of Exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fab,making good the damages, connections, testing and commissioning etc. as required:-a) Ex-Fan Light Duty , 300 mm sweep |
| 7 | Wiring for circuit/ submain wiring alongwith earth wire with the following size of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required.a) 2 X1.5 sq mm +1X1.5 sq mm earth wire |
| 8 | b) 2 X 4.0 sq mm +1X4.0 sq mm earth wire |
| 9 | c) 4 X 4 sq mm + 2 X 4 sq mm earth wire |
| 10 | Providing and laying of one No. aluminium conductor PVC insulated and PVC sheathed armoured XLPE power cable working voltage 1100 volts grade on surface etc. of the required sized.a) Armoured cable 35 Sq. mm. ( 3.5 core ) |
| 11 | Supplying and fixing of bulk head fitting of all sizes and shapes, containing one No. thread type CFL lamp holder (s), complete with all accessories but excluding CFL lamp including making connections, testing etc. as required.a) Bulk head fitting, CFL type (Category-A) |
| 12 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 13 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 14 | Providing and laying earth connection from earth electrode with 4.00 mm dia. copper wire in 15 mm dia. G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. Please Enable Macros to View BoQ information |