Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Supplying and drawing Fire Resistant flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 2 | 2 x 1.5 Sq.mm Armoured With Outer Sheath in Red Color |
| 3 | SITC of floor mounted dust and vermin proof compartmentalised cubical type main fire pump house panel made out of CRCA sheet , required hardware ,duly treated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shade The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel ,hinged door with locking arrangement for equipment/switchgear . Thickness of sheet shall not be less than 1.6 mm up to 600 mm length / width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors and having accessories ( Group -I ) as below:Incomer320 Amp. TPN MCCB (adj.O/L) with Extended ROM, 35 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, Selector switches,CT, Indicating Lamps, 400 Amps Alum. Bus bar with with heat shrinkable sleeves.Out going(a) 200 Amp. TPN MCCB(adj.O/L) with Extended ROM, 35 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, Selector switches,CT, Indicating Lamps for 'ON', 'OFF', 'TRIP' 1 no. star Delta Starter of 75 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 2 Sets(b) 63 Amp. TPN MCCB (adj.O/L) with Extended ROM, 25 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, Selector switches, CT, Indicating Lamps for 'ON', 'OFF', 'TRIP' 1 no. Star Delta / DOL Starter of 5 - 15 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 1 Set© One no. Diesel Engine Auto Starting kit with Auto . Manual selector switch & 3 attempt starting device, timers, relays, Indicating lamp for High / Low Lub. Oil pressure, High water temperature and engine ON indication, Battery charger, suitable for 12 V / 24 V DC with trickle / boost selector switch, DC ammeter & voltmeter(d) System controller to control Operation Main Electric pumps, Diesel pump, jockey pump in sequence as per specs. Consisting of relays, timers, sensors, annuciation window for fault indication. |
| 4 | Supplying, installing, testing and balancing of extruded Aluminium powder coated Air Diffuser and complete with Flush, 20mm flanges with PVC/neoprene gasket, anti – smudge frame and removable inner core to facilitate the adjustable of air control damper, square/round/ rectangular as required.including fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 5 | Supply Air Diffuser with Volume Control damper |
| 6 | Return Air Diffuser without Volume Control damper |
| 7 | Supply and fixing aluminium foil faced 50 mm thick Rock wool insulation of density 36 kg/cu.m after applying two coats of cold setting adhesive (CPRX Compound) sealing all joints with self adhesive tape & finished with 26 G Aluminium cladding. complete in all respect. (For Outdoor applications-air conditioning ducts) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 8 | Supply & fixing of external thermal closed-cell Nitrile rubber Insulation material FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified 'Class O' in Fire Propagation as per BS 476 Part 6 in form of sheet on duct including cost of adhesive (CPRX Compound) complete as required. All as per pre approved by Engineer in charge. |
| 9 | 13mm thick for indoor Application |
| 10 | 19mm thick for Outdoor Application with 26 SWG Aluminium Cladding |
| 11 | Supply , Installation, Testing and Comissioning of site fabricated ducting made from GI sheet metal conforming to IS:277 with a zinc coating grade not less than 120 GSM (both side inclusive) & fabricated as per IS:655 and as per approved drawings & designs including the cost of hangers, supports, angle, expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. Test Certificate for Galavanizing with lot no. to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 12 | 0.60 mm |
| 13 | 0.80mm |
| 14 | 1.00mm |
| 15 | Providing & Fixing of BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan Conforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 16 | 1200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 ) |
| 17 | Providing & Fixing of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 18 | 1170mm(+/-10%) LED batten with min. lumen output 2200 lm |
| 19 | Supply and fixing following size of Hot dipped Galvanized (275 GSM) floor raceways / Under floor trunking with/ without partion, including common cover, joint sleeve, cross over junction Box etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 20 | 150 mm x 38 mm x 2.0 mm with 2 Compartment |
| 21 | SITC of MS \\"C\\" track grid system (15 mtr.) for Motorised Light Bar with suitable supsenders to install the motorised light bars and other accessories as per site requirement . |
| 22 | SITC of Motorised FOH Light bar 15 Mtr made using 40NBMS Pipe with cable retractor & cable trays undergone through 7tank process and power coated with black matt texture finish with Specially designed compact gear box, required 3 phase AC motor with DC Brake, GI wire rope and cable winding drum complete in all respect. |
| 23 | SITC of Motor Control Panels for run Motorised FOH Light Bar with necessary Indicators and safety controls. Power Junction boxes & installation Hardwares required for successful installation complete in all respect. |
| 24 | SITC of Intermidiate Frill Fabric- 50% Gathering FR Cottonfabrics duly stiched as per site condition on existing frill frame complete in all respect. Dimension : 15 Mtr x 1.3 Mtr |
| 25 | SITC of Stage Side wings Fabric - 0% Gathering FR cottonfabrics duly stiched as per site Condition on existing stage wings frame complete in all respect Dimension : 5.7 Mtr x 1.2 Mtr |
| 26 | SITC of IP20 LED recess mounted deep recessed DALI Dimmable high efficacy downlighter with driver with minimum system lumen output of 3600lm with >130lm/W system efficacy & UGR <19, with beam angle of 80 deg and 60 deg respectively as required . The luminaire shall have life of 50000 burning hrs @L70B50, CRI ≥80, SDCM 5, THD ≤10%, pf ≥0.9, CCT 4000/5700K. The product shall have internal surge protection of 3.5kV, with operating temperature range of 0 to 45 deg C and operating voltage range of 140-270V. The product shall have min. 200mm cut out dia. Make is to be approved by department in-charge and Quality test report from NABL approved labs/ in house NABL approved labs including TPI reports will be submitted by contractor . Both the fixture and Driver should have separate BIS approval. |
| 27 | SITC of DALI Dimmable IP20,front lit 2'x2' LED Surface/ Recessed mounting Mid power (≥ 0.5W) SMD type LED Light fixture ≥35mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for Uniform glare free light distribution. Minimum lumen output 7000lm . High efficiency, EMI complaint CRCA driver with 4 KV internal/external CM- DM & input burst surge protection BIS certified isolated CRCA single piece driver having efficiency > 85% , with Short & Open circuit protection (Input 320VAC-48 hours protection, Input 350VAC-2 hours protection) (Integral with light fixture), operating voltage range 140-270VAC., System Lumen efficacy of ≥ 120 lm / watt, THD<5%, p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends at 45degreeC, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Quality test report from NABL approved labs/ in house NABL approved labs including TPI reports will be submitted by contractor . All as per pre approved by Engineer in charge. |
| 28 | Supply Installation Testing & Commissionig of 12 Channel Signal Dimmer Controller which can support for DALI Broadcas with Instant visual feedback on channel status for all 12 channels. Device should have override option on the control itself. Supply Voltage: 100-240AC, system Output DC current 200mA which can support 10 button panels without any additional power supply. 12-channelcontroller supports switched loads of up to 20 A per channel, up to a maximum device load of 180 A DIN-rail mountable device along with Display Keypad / panel For workstations, break out areas, training rooms etc with Fully programmable options for individual control / group control / Scene control / Tasks etc. Wall mounted on 2M (3 X 3 size) modular box and Network Router with Automatic system With Programming complete in all respect. |
| 29 | Supply and installation of Mixing Chamber of Size 1850 mm x 1450 mm x 550 mm in Existing Air Handling Unit The unit shall be fabricated with frame work hollow extruded aluminium profile with 0.80 mm preplasticised GSS on outside and 0.80mm 275gsm plain GSS on inside complete with 25 mm thick CFC free PUF insulation of minimum 40 kg/cum density sandwiched in between inner and outer skins.Including door handles, hardware etc as required.Make :-Pinaky,Zeco, Edgetech etc make is be approved by engineer in charge . |
| 30 | SITC of 8 Mtr Decorative pole with Single arm with below specifications:- Part-1 GI pipe bottom pole dia 150x150mm Length 2000mm Thickness 3mm. Part-2 GI Ribbed pipe Middle part pole dia 81mm Length 5000mm Thickness 3.2mm. Part-3 GI Pipe Top part pole dia 60mm Length 1000mm Thickness 3mm. Part-4 Arm Band pipe pole dia 42mm Length 1000mm Thickness 2.8mm. Ms base plate 250x250x16mm. Bottom part radium print screen with kda as per drawing. Bottom and Middle part joint Decorative Aluminum Flunch arm top part leser cut design dia 300mm with kda arm band pipe down side welded laser cut design and bottom side liner alumnium chanel led 12w per meter as per Requirement as per Drawing. The pole section Shall be welded by certified welders using high and MIG welding process. The Service door shall be provided at bottom part of the pole to accommodate a built in connection box. The control gear tray is with MCB, terminal connectors for loop in loop out arrangement. The Pole coated with epoxy zinc phosphate primer and finished using envoirnmentally stable polyurethene base paint. Tolerance+-5% Make- Orient, VSTP, Lusture, Pyrotech, Utkarsh, Transrail etc. All as per approved by Engineer in-charge. |
| 31 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 32 | 4 core*10 sqmm |
| 33 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 34 | 63 mm |
| 35 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 36 | 3 core*2.5 SQMM |
| 37 | 12 core*1.5 SQMM |
| 38 | Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver & has a unique BIS R number with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . driver current <750mA. The luminaire shall be BIS certified and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs. Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 39 | LED Street Light fixture with Minimum lumen output 11225 lm |
| 40 | Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 41 | High Power LED Flood Light Minimum lumen output 14800 lm |
| 42 | Supply, installation, testing and commissioning of fully digital dmx driver (CC & CV) ,long working life ,maintining the best Led's , CRI , 0-100% full dimmimg range , pf >0.99 efficiency >85% ,ThD <10% having high voltage range + optional workable with different LED lights at different power . Driver to have inbuilt short circuit / over temperature /overload protection . The drivers to be mounted in IP rated boxes /inside elements to ensure weather proofing against water & dust .Complaint to SELV (Self Extra Low Voltage ) Make :- L-Tech /Osram /Meanwell etc and make is to be approved by department |
| 43 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 44 | 6 core*1.5 sqmm |
| 45 | 3 core*1.5 sqmm |
| 46 | 3 core*2.5 sqmm |
| 47 | Supply, installation, testing and commissioning of lighting control cable (DMX cable ) with exceptional durability and flexible construction .Cable to meet Visit standards for DMX 512. Cable to be all weather proof , extra flexible jacket material that are tough & abrasion resistant .Cable to be properly terminated / connected using standard connectos . Make :- Belden/Max and make is to be approved by department |
| 48 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- |
| 49 | (a)Thickness of CRCA sheet shall be 2.0 mm, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided(b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.[c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra )(d)Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. (e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.(f)Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra )(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 50 | P & F paper phenolic resin bonded laminates confirming to IS : 2036 - 1995 for boxes/ frames including making holes for switches etc, with brass screws, washers/ zinc plated nut and bolts as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 51 | 4.8 mm thick |
| 52 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 53 | Single pole MCB (With B/C curve tripping Characteristics) |
| 54 | 6 A to 32 A rating |
| 55 | Triple pole MCB (With B/C curve trippingCharacteristics) |
| 56 | 40 A rating |
| 57 | Providing & Fixing of thermal over load relay with built in single phase protection and having at least 1NO & 1NC contacts, manual /auto reset facility including making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 58 | Up to 14 Amp |
| 59 | Providing & Fixing of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 60 | One day & week reserve (Analog type ) |
| 61 | Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor as per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 62 | 3 pole Power contactors with following AC 3 Rating |
| 63 | 32 Amp. |
| 64 | 50 Amp |
| 65 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 66 | 1 x 6.0 sq.mm |
| 67 | Providing & Fixing of IP - 65 protected impact resistant polycarbonate / Polysterene enclosures with knock out for cable entry/out including fixing with nut, bolt, fatner etc as required complete in all respect of following sizes.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 68 | 320 x 440 x 179 mm |
| 69 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 70 | S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 71 | 25 mm |
| 72 | SITC of BIS approved under IS 10322 part 5/ sec 5 (Shape) RGBW (W=3000K/ 4000K) IP66 rated (Square / Rectangle/ Circular) shape Projector Light 36W. Product should have highly thermal efficient aluminium Pressure Die Cast(ADC 12) along with clear Toughened glass with impact tresisitance IK07. Product should have Lumen 1440 with efficacy > 40 Lumen /Watt when all LED are in ON condition. Product should have different beam angle (Narrow Beam/ Medium Beam/ Wide beam/ elliptical beam) Lens, made of VDE/ UL approved UV resistant, non yellowing PC material. Product Should be equipped with 8bit/16 bit DMX 512 based decoder or data processing device with in the product maintaing same IP rating.Product should be equipped with BIS approved IP65/67 rated Constant Voltage Power Supply. Product should be operational on 240V AC without any extrenal/ remote led driver.Product should have CLASS I electrical safety. Product should have IP67 rated industrial grade locked moulded cable connector for DMX signal. Product should be equipped with LED of reputed LED manufacturer CREE/ OSRAM. LED's LM80 should declare >50,000 @ 85ºC. Product ambient temperature should be (-10ºC to 50ºC).Make is to be approved by department in-charge and Quality test report from NABL approved labs/ in house NABL approved labs including TPI reports will be submitted by contractor |
| 73 | SITC of BIS approved with RGBW (W=3000K/ 4000K) IP66 rated Linear Wall Washer Light 12W 1000mm. Product should have highly thermal efficient Extruded aluminium with Die casted end caps. Product should have clear Toughened glass with impact resisitance IK07. Product should have Lumen output 480 lumen with efficacy > 40 Lumen /Watt when all LED are in ON condition. Product should have different beam angle ( Narrow Beam/ Medium Beam/ Wide beam/ elliptical beam) Lens, made of VDE/ UL approved UV resistant, non yellowing silicon material. Product Should be equipped with 8bit/ 16 bit DMX 512 based decoder or data processing device with in the product maintaing same IP rating.Product should be equipped with BIS approved IP65/67 rated Constant Voltage Power Supply. Product should be rated DC 24V and operational on 240V AC with any extrenal/ remote led driver. Product should have CLASS III electrical safety.Product should have IP67 rated industrial grade locked moulded cable connector for DC voltage supply. Product should be equipped with LED of reputed LED manufacturer CREE/ OSRAM. LED's LM80 should declare >50,000 @ 85ºC. Product ambient temperature should be (-10ºC to 50ºC).Make is to be approved by department in-charge and Quality test report from NABL approved labs/ in house NABL approved labs including TPI reports will be submitted by contractor |
| 74 | Supply ,Installation testing and commissioning of DMX controllers,mounted in outdoor IP rated enclosure . Controller should be able to control the drivers as per color design theme. The enclosure should have power supply , dmx controller, ethernet control connectivity , (Ethernet/ KNX) digital output with complete programming and software for control as required complete in all respect.. Make :- Madrix/Ltech/ABB and make is to be approved by department |
| 75 | SITC of Signal Booster/Splitter with 8Way output for spreading and amplyfing the DMX Data signals in multiple directions, Input-220- 240V AC. The splitter should be of same make as the fixtures and the controller should be BIS approved Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail