| 1 | M&L for Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for laying UG cable in trenches on plan and n exc 1.5 m in depth in any type of soil and getting out all as specified and directed by Engr-in-Charge. |
| 2 | M&L for Excavation in trenches, n exc 1.5 m wide and exc 1.5 m in depth but n exc. 3.0 m for foundation, of plole or laying of UG cable in trenches on plan in any type of soil and getting out of all as specified and directed by Engr-in-Charge. |
| 3 | M&L for Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25m, complete all as specified by Engr-in-Charge. |
| 4 | M&L for Removing excavated material to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the strating point, complete all as specified by Engr-in-Charge |
| 5 | M&L for Sand cushioning to underground cables 8 cm below the cable before laying & 15 cm above the cable after laying, complete all as specified in clause 19.75 of SSR Par-I, complete all as specified. Note : Punned thickness of 18 CM will be measured and paid. |
| 6 | Supply and laying in replacement factory made, machine pressed, unreinforced, pre-cast concrete cable cover class LV type-1 flat size 250 mm x 150 mm x 40mm , complete all as specified and directed |
| 7 | M&L for fault finding, of PVC / XLPE Cable of any size by opening the aluminium lugs from Junction box / DB / MCCB and meggering the cable and removing the unservicable part of cable and lugs and restoring the supply as directed by Engr -in-charge. Note:- 1) The excavation, sand filling , cable protection cover, removing of surplus soil etc will be measure and paid respective items. 2) ALuminium lugs and straigt through joint will be measured and paid separetly. The rate are included for using Tools required at site. |
| 8 | Supply and laying in replacement of XLPE insulated, armoured, heavy duty electric cables with stranded aluminium conductor rating 1100 volts grade of size 630 Sqmm 3.5 core laid in trences or passing through pipes.ducts or fixed to walls/poles complete all as specified. Note::- (Earth work, cable protection and sand cushioning shall be measured and paid for seperately) |
| 9 | All as per srl item No. 08 above but of size 500 sqmm, 3.5 core complete all as specified and directed by Engr-in-Charge |
| 10 | All as per srl item No. 08 above but of size 240 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge . |
| 11 | All as per srl item No. 08 above but of size 185 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 12 | All as per srl item No. 08 above but of size 150 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 13 | All as per srl item No. 08 above but of size 120 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge . |
| 14 | All as per srl item No. 08 above but of size 95 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge . |
| 15 | All as per srl item No. 08 above but of size 70 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 16 | All as per srl item No. 08 above but of size 50 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge . |
| 17 | All as per srl item No. 08 above but of size 35 sqmm, 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 18 | All as per srl item No. 08 above but of size 25 sqmm, 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 19 | All as per srl item No. 08 above but of size 16 Sqmm, 2 core complete all as specified and directed by Engr-in-Charge. |
| 20 | All as per srl item No. 08 above but of size 10 Sqmm, 2 core complete all as specified and directed by Engr-in-Charge |
| 21 | Supply & fixing in replacement of tubes light grade of size 80 mm bore galvanised with all fittings and fixed complete to walls and ceiling or laid in floors complete all as specified and directed by Engr-in-Charge . |
| 22 | Supply & fixing in replacement of tubes light grade of size 50 mm bore galvanised with all fittings and fixed complete to walls and ceiling or laid in floors complete all as specified and directed by Engr-in-Charge.. |
| 23 | M&L for fixing in replacement of ACSR conductor any size drawn straight horizontal on over head lines on existing poles including binding with insulators. Weight of conductor shall be measured straight horizontal distance between centre of two adjacent poles and calculating weight of conductor of size and length by adding 3% extra for sag ,jointing jumpers,etccomplete all as specified and directed by Engr-in-Charge. |
| 24 | Supply & Installation, testing and Commissioning in replacement of LT Panel cubical type out door floor mounted weather proof totally enclosed, (CPRI approved) factory made and made out of 3 mm thick CRCA powder coated sheet and angle iron complete with bus bar of Aluminium of suitable size for capacity 400 Amps 3 Phase and Neutral 415 Volts 50 Hz mounted on epoxy type insulators with PCC flooring and angle iron base frame complete all as directed by the Engr-in-charge including fallowing accessories:- a) ACB 4P 800 Amps Cap 4 Pole -1 No for( I/C) b) Change over switch open execution type 800 Amp 4 pole - 01 No c) Digital Volt meter with sellector switch(0-500V) - 02 Set d) Digital Amp meter with sellector switch with necessary CT (0-500A) - 02 Set e) LED indicating lamp - 02 Set Note : (i) The Make of Change over and MCCB considered are Havells/Standard/Indo Asian/HPL (ii) The rates deemed to be inclusive of suitable size copper wirinng/copper strips from Main I/C MCCBs to Channge over switch, Change over switch to Main Bus bar and Bus Bar to Outgoing MCCBs complete all as specified and directed. (iii) The design of Panel, Make of complete accessories and drawing of the LT Panel should be submitted by the contractor for pre-approval from the Engineer-in-cfharge before order and execution at site. |
| 25 | M&L for fixing in replacement of stay assembly complete with stay plate bow, stay rod of dia 16mm and gavanised iron stay wire stranded of size 7/4mm and accessories as shown in electric plate No 1 of SSR part-I (loop type insulator, stay clamps, excavation and concrete shall be measured separately) complete all as spd and directed by Engr-in-Charge. |
| 26 | M&L for fixing in replacement of shackle insulator porcelain white, brown or green 100 mm height, 65 mm dia for 1100 volts grade complete all as specified and directed by Engr -in-charge. |
| 27 | M&L for fixing in replacement of pin insulator porcelain white, brown or green 100 mm height, 65 mm dia for 1100 volts grade complete all as specified and directed by Engr -in-charge. |
| 28 | M&L for fixing in replacement of galvanized steel wire 4mm dia for continuous earth wirecomplete all as specified and directed by Engr-in-Charge. |
| 29 | Supply and fixing in replacement of bus bar chamber size 600x 450x 300 mm outdoor type made out of MS sheet 2.0 mm thick mounted on angle iron frame dully painted with two coat of synthetic enemelled paint over a coat of primer and comprising of three phase aluminum bus bar 200 amps mounted on insulators including provisioning of foundation complete all as specified and directed by Engr -in-charge. |
| 30 | All as per item No 29 above but of capacity 100 Amp complete all as specified and directed by Engr-in-Charge |
| 31 | M&L in replacement for Incoming Off load Changeover Switch Enclosure with 200 A 4 Pole Incoming change Over switch- to accommodate all connected accessories complete all as specified and directed by Engr-in-Charge |
| 32 | M&L in replacement for Incoming Off load Changeover Switch Enclosure with 320 A 4 Pole Incoming change Over switch- to accommodate all connected accessories complete all as specified and directed by Engr-in-Charge |
| 33 | M&L in replacement for Incoming Off load Changeover Switch Enclosure with 400 A 4 Pole Incoming change Over switch- to accommodate all connected accessories complete all as specified and directed by Engr-in-Charge |
| 34 | M&L in replacement for Incoming Off load Changeover Switch Enclosure with 630 A 4 Pole Incoming change Over switch- to accommodate all connected accessories complete all as specified and directed by Engr-in-Charge |
| 35 | M&L for fixing in replacement of cross arms bracing supports clamps, back plates fabricated from steel section made out of Fe-0-310/ Fe-0-410 incuding nuts,bolts and washers welding,drilling hole complete with two coats of aluminium paint over one coat of primer complete all as specified and directed by Engr -in-charge. |
| 36 | Supply and fixing in relacement Aluminium Thimble of size 10/16/35/50/70/95 Sq mm complete all as specified and directed by Engr -in-charge. |
| 37 | Supply and fixing in relacement Aluminium Thimble of size 120/150/185/240/300/400 Sq mm complete all as spd and directed by Engr-in-Charge. |
| 38 | M&L for painting 9 mtr steel tubular pole after scrapping and peeling of the old existing paint, corrosive patches and painting primary coat with synthetic enamelled silver paint and another final second coat to match the entire surface area of the pole and highliting the pole with 20 CM wide ulternate white and red radium strips upto height of 1Mtr from Ground level complete all as specified and directed by Engr-in-Charge |
| 39 | M&L for painting 11 mtr steel tubular pole after scrapping and peeling of the old existing paint, corrosive patches and painting primary coat with synthetic enamelled silver paint and another final second coat to match the entire surface area of the pole and highliting the pole with 20 CM wide ulternate white and red radium strips upto height of 1Mtr from Ground level complete all as specified and directed by Engr-in-Chage. |
| 40 | Supply and fixing in replacement L Frame: Adjustable Thermal* & Fixed Magnetic setting MCCB 630 Amps, 50 KA, 415 Volts four pole complete all as specified and directed by Engr -in-charge. |
| 41 | Supply and fixing in replacement L Frame: Adjustable Thermal* & Fixed Magnetic setting MCCB 400 Amps, 36 KA, 415 Volts four pole complete all as specified and directed by Engr -in-charge. |
| 42 | Supply and fixing in replacement L Frame: Adjustable Thermal* & Fixed Magnetic setting MCCB 250 Amps, 36 KA, 415 Volts four pole complete all as specified and directed by Engr-in-Charge |
| 43 | Supply and fixing in replacement L Frame: Adjustable Thermal* & Fixed Magnetic setting MCCB 200 Amps, 36 KA, 415 Volts three pole complete all as specified and directed by Engr-in-Charge |
| 44 | Supply and fixing in replacement of L Frame: Adjustable Thermal* & Fixed Magnetic setting MCCB 160 Amps, 25 KA, 415 Volts three pole complete all as specified and directed by Engr-in-Charge |
| 45 | Supply and fixing in replacement of L Frame: Adjustable Thermal* & Fixed Magnetic setting MCCB 125 Amps, 25 KA, 415 Volts three pole complete all as specified and directed by Engr-in-Charge. |
| 46 | Supply and errect steel tublar swaged poles in true verticle position complete with MS sheet welded on base, finial taper plug, bolts, nuts and screws as specified type 410 SP -31 (9 meters long). including painting with two coats of synthetic enamell paint complete all as specified and directed by Engr-in-Charge |
| 47 | M&L for Cement concrete in filling and mass concrete/ foundation of poles/Stay and PCC for road crossings etc all as directed , type C-2 1:3:6 (40 mm graded aggregate) complete all as specified and directed by Engr-in-Charge |
| 48 | M&L for Cement concrete in filling and mass concrete/Coping of Poles and PCC for road crossings etc all as directed , type C-1 1:3:6 (20 mm graded aggregate) complete all as specified and directed byEngr-in-Charge |
| 49 | Replacement of Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directly in groud to a depth not lss than 2.25 mtrs deep below normal ground level with top edge of earth plate not less than 1,5 ntrs below normal ground level connected to galvanised iron strip 32 x 6mm as earthing leads by means of galvanised bolts, nuts, check nuts and washer of galvanised iron or steel complete with 20 mm dia GI Pipe light grade for watering and 40mm dia GI light grade pipe for protection of strip upto test point including test point of strip 50x50x3mm GI, charcoal dust, common salt 15cm all around the earth plate all as shown inelectric plate No.5 of MES SSR Part-I all as specifed or indicated and testing on competion including necessary excavation, earth work PCC pit and with RCC cover of suitable size water funnel with wire mesh all as directed byEngr-in-Charge. |
| 50 | All as per item No 49 above but using GI wire 4.0 mm dia as earthing leads by means of galvanised bolts, nuts, check nuts and washer of galvanised iron or steel complete with 20 mm dia GI Pipe light grade for watering and 40mm dia GI light grade pipe for protection of 4.0mm dia GI wire charcoal dust, common salt 15cm all around the earth plate all as shown inelectric plate No.5 of MES SSR Part-I all as specifed or indicated and testing on competion including necessary excavation, earth work PCC pit and with RCC cover of suitable size water funnel with wire mesh all as directed by Engr-in-Charge |
| 51 | M&L for Restringing/Restretching aluminium conductor/ GI wire of LT over head line three phase and Neutral by opening the binding wire from insulator and tightening the all conductor and rebinding the same by binding wire with insulator as existing as directed by |
| 52 | M&L for Restringing/Restretching aluminium conductor/ GI wire of LT over head line for Single phase and neutral with street light by opening the binding wire from insulator and tightening the all conductor and rebinding the same by binding wire with insulator as existing as directed by Engr -in-charge. |
| 53 | S&F PVC Spacer 2/4 way for LT over head line 1100 V complete all as specified and directed by Engr-in-Chage. |
| 54 | M&L for servicing of ACB of any capacity by opening the inner compartment and cleaning / greasing the male / female part , spring charge mechanism etc including calibration complete all as specified and directed by Engr-in-charge. |
| 55 | M&L for Incoming Off load Changeover Switch Enclosure with 800 A Incoming change Over switch- to accommodate all connected accessories complete all as specified and directed by Engr-in-Charge. |
| 56 | Deduct Schedule of Credit of Rs (-) 92965.00 (Minus) as listed in Schedule 'A' (Contd). Contract Sum shall be arrived after deducting the credit amount.Note :- Tenderers will not quote against this item being a firm amount. Please Enable Macros to View BoQ information |