| 1 | (E/M PORTION)Taking down carefully the existing aluminium/copper point wiring of any size and capacity and type by disconnecting from the either terminals complete including fittings and fixtures such as switches, sockets,ceiling rose,fan regulators, lamp holders, call bell, bell pushes any type etc by unscrewing and taken away from site complete and make good the disturbed surface as existing complete all as specified and directed. |
| 2 | Taking down Sub main wiring of any make and size complete all as specified and directed. |
| 3 | M & L for point wiring with 1.5 sqmm (Nominal Area) FRLS PVC insulated un sheathed multi stranded copper conductor, 1100 Volts grade, in and including PVC casing capping/conduit (ISI marked) with accessories such as bends, cross, elbow, tees etc. of suitable size including MS pressed steel cadmium plated terminal box not less than 1.6 mm thick for mounting switches, sockets, fan regulators etc and 3 mm thick laminated sheet top cover(ISI marked) including continuous earth wire FRLS PVC insulated unsheathed 1.5 Sq mm(nominal area) copper multistarnded conductor, 1100 Volts grade, connecting to common earth and earth dolly complete all as specified for one light point/Exhaust fan/ceiling fan/ call bell point point controlled by one switch Note : Wiring Color code i.e. Red/Yellow/Blue for Phase, Black for neutral and Green for earth shall be maintained.( for concealed wiring chase cutting will be measured and paid seperately.) |
| 4 | All as per item No 3 above but for one three pin socket outlet on same board. |
| 5 | All as per item No 3 above but for one three pin socket out let 5 amps on independent board. |
| 6 | S&F Modular switch 1 way 6A, 1 module complete all as specified and directed. |
| 7 | S&F Ceiling rose surface type 3 terminals 65x20mm compelete all as specified |
| 8 | S&F Socket, 6A - 2/3 pin combined 2 module complete all as specified and directed. |
| 9 | S&F Switch socket outlet 3 pin 6 amp' flush type complete all as specified and directed. |
| 10 | S&F Fan step regulator, 120W - 2 module complete all as specified and directed. |
| 11 | S&F White cover plate with frame, 1 module complete all as specified and directed. |
| 12 | S&F White cover plate with frame, 2 module complete all as specified and directed. |
| 13 | S&F White cover plate with frame, 3 module complete all as specified and directed. |
| 14 | S&F White cover plate with frame, 4 module complete all as specified and directed. |
| 15 | S&F White cover plate with frame, 6 module complete all as specified and directed. |
| 16 | S&F White cover plate with frame, 8 module complete all as specified and directed. |
| 17 | S&F White cover plate with frame, 12 module complete all as specified and directed. |
| 18 | S&F Metal flush box 1/2 module complete all as specified and directed. |
| 19 | S&F Metal flush box 3 module complete all as specified and directed. |
| 20 | S&F Metal flush box 4 module complete all as specified and directed. |
| 21 | S&F Metal flush box 6 module complete all as specified and directed. |
| 22 | S&F metal flush box, 8 module complete all as specified and directed. |
| 23 | S&F metal flush box, 12 module complete all as specified and directed. |
| 24 | M & L for point wiring with 4.00 sqmm (Nominal Area) FRLS PVC insulated un sheathed multi stranded copper conductor, 1100 Volts grade for 3 Pin socket outlet 15 Amps on independent board with PVC conduit (ISI Marked) medium duty not less than 20mm dia with accessories such as elbow, tees,internal & external bend etc. of suitable size including continuous earth wire FRLS PVC insulated 4.00 Sq mm copper multi stranded conductor, 1100 Volts grade, connecting to common earth and earth dolly complete all as specified. Note : 1) Wiring Color code i.e. Red for Phase, Black for neutral and Green for earth shall be maintained. 2) Necessary chase cutting for conduits if requires, shall be measured & paid separately under respective items in this schedule. |
| 25 | S&F modular Switch Socket combination outlet 6 pin 16 Amps flush type complete all as specified and directed. |
| 26 | S&F AC Starter of 32 Amps Alongwith Plug top complete all as specified and directed. |
| 27 | M & L for sub main wiring with single core PVC insulated unsheathed , 1100 Volts grade, (FRLS) copper cable 4 sqmm stranded conductor and drawing through and including rigid PVC non metalic surface conduit medium duty (ISI Marked) with conduit accessories such as junction boxes, bends, tees etc. including continuous earth wire PVC insulated unsheathed 1100 volts grade, cable 4 sqmm copper conductor and connected to common earth dolly complete as directed including taking down old submain wiring.Note :-(i) One run of PVC conduit, two runs of cable (Phase + Neutral) and one run of earth wire shall be measured and paid as one unit. (ii) chase cutting if required shall be measured and paid separately under relevant items in this schedule. |
| 28 | M & L for sub main wiring with single core PVC insulated unsheathed , 1100 Volts grade, (FRLS) copper cable 6 sqmm stranded conductor and drawing through and including rigid PVC non metalic surface conduit medium duty (ISI Marked) with conduit accessories such as junction boxes, bends, tees etc. including continuous earth wire PVC insulated unsheathed 1100 volts grade, cable 6 sqmm copper conductor and connected to common earth dolly complete as directed including taking down old submain wiring.Note :-(i) One run of PVC conduit, two runs of cable (Phase + Neutral) and one run of earth wire shall be measured and paid as one unit. (ii) chase cutting if required shall be measured and paid separately under relevant items in this schedule. |
| 29 | M & L for sub main wiring with single core PVC insulated unsheathed , 1100 Volts grade, (FRLS) copper cable 10.00 sqmm stranded conductor and drawing through and including rigid PVC non metalic surface conduit medium duty (ISI Marked) with conduit accessories such as junction boxes, bends, tees etc. including continuous earth wire PVC insulated unsheathed 1100 volts grade, cable 10.00 sqmm copper conductor and connected to common earth dolly complete as directed.( Three Phase supply )Note :-(i) One run of PVC conduit, three runs of cable (3 Phase + Neutral) and one run of earth wire shall be measured and paid as one unit. (ii) chase cutting if required shall be measured and paid separately under relevant items in this schedule. |
| 30 | Cutting chases for concealed conduit wiring and making complete good with putty and paint and matching the surface with original surface cutting not exc 10 cm girth complete all as specified and directed. |
| 31 | Supply and fix MCB SP 240V, 6-32 Amps capacity complete all as specified and directed. |
| 32 | Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity 40 to 63 AMP in the MCB DB complete with connection testing and commissioning complete all as specified and directed. |
| 33 | S&F sheet metal enclosure of Bus bar of SPN 8 way including flushing in wall complete all as specified and directed. |
| 34 | S&F sheet metal enclosure of 12 way TPN DB including flushing in wall complete all as specified and directed. |
| 35 | Supply and fixing TPN /FP 40 to 100 AMP 415V 10KA 'B' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning complete all as specified and directed. |
| 36 | Supply and fix 4 Pole MCCB 160 Amp, 50 Hz, 415 V with rupturing capacity 25 KA complete all as specified and directed. |
| 37 | Supply and fix 4 Pole MCCB 200 Amp, 50 Hz, 415 V with rupturing capacity 25 KA complete all as specified and directed. |
| 38 | S & F in replacement of VTPN MCCB 200 A DB Double Door, 08 way, IP 53 protection with Door earthing and mechanical impact strength IK 08 complete all as specified and directed.Make Legrand Cat Part No: 5077 50 or equivalent make specified in tender. |
| 39 | S & F in replacement of VTPN MCCB 160 A DB Double Door, 08 way, IP 53 protection with Door earthing and mechanical impact strength IK 08 complete all as specified and directed.. Make Legrand Cat Part No: 5077 52 or equivalent make specified in tender. |
| 40 | S & Fix Energy efficient light fitting (LED ) Sleek type of capacity 36 W fitting 4FT with extruded Aluminium Hosuing Lamps,driver,connector etc incl hanging/Fixing arrangement with PVC insulated three core flexible copper conductor of suitable size from ceiling rose to fitting through suitable size flexible PVC pipe making good to wall for old fitting including taking down old fitting of complete all as specified and directed. Make Philips Model No 581951 36 W ( Philips Ultron edge 4 ft LED wall Light or equivalent make specified in tender. |
| 41 | Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed. |
| 42 | S & Fix Energy efficient light fitting (LED ) Batten fitting 4FT (Cute linea,surface &wall mounting LED 4ft batten with extruded synthetic housing,3\\" X3\\" PVC block 2 Nos,Lamps,driver,connector etc incl hanging arrangement with PVC insulated three core flexible copper conductor of suitable size from ceiling rose to fitting through suitable size flexible PVC pipe making good to wall for old fitting including taking down old fitting of complete all as specified and directed |
| 43 | Supply and fixing LED luminaire track light of 10 W in WW colour ,black in finish 220 V AC complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor of suitable size complete all as specified and directed. |
| 44 | Supply and fixing LED luminaire wall light with E-27 base threaded bulb with die cast aluminium housing with glass diffuser and black in colour with IP 43 protection including connecting up with driver three core flexible copper conductor of suitable size complete all as specified and directed. |
| 45 | Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete withIP 65/66 protection complete all as specified and directed. |
| 46 | Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and directed. Please Enable Macros to View BoQ information |
| 47 | Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and directed. Please Enable Macros to View BoQ information |