| 1 | Supplying, laying, jointing & testing, in replacement of 1100 volts grade, heavy duty, LT XLPE cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed,3.5 Core, 185 Sqmm nominal cross section in service connections laid in loops /ducts, along wall /pole or under floor /road or laid in trenches including taking out old unserviceable cable complete all as specified and directed. |
| 2 | All as per ser item No. 1 here-in-before but 120 Sqmm 3.5 Core. |
| 3 | All as per ser item No. 1 here-in-before but 95 Sqmm 3.5 Core. |
| 4 | Supplying, laying, jointing & testing in replacement of 11000 volts grade, heavy duty, HT XLPE cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed, 3 Core, 95 Sqmm nominal cross-section in service laid in loops /ducts, along wall /pole or under floor /road or laid in trenches connections including taking out old unserviceable cable complete all as specified and as directed. |
| 5 | Supply and spread dry sand for cable cushioning in trenches all as specified in clause 19.75 of SSR Part-I complete all as specified and as directed by Engineer-in-Charge. |
| 6 | M&L for brick, subclass 'B' well burnt, laid dry flat in trenches for protection of cable with a maximum gap of 10 mm between two consecutive brick over LT cable including taking out old unserviceable bricks, complete all as specified and as directed by Engr-in-charge. |
| 7 | Excavation in trenches not exceeding 1.5 m in deep & not exceeding 1.5 m wide and getting out in soft / loose soil including leveling and ramming complete all as specified and as directed. |
| 8 | Returning, refilling in trenches exvcavated soils, including spreading leveling & well ramming in layers not exceeding 25 cm thick complete all as specified and directed. |
| 9 | Removal of excavated surplus soil to a distance n.exceeding 50 m and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed. |
| 10 | M&L for 40 mm bore GI pipe (light grade) in replacement with all fittings laid in trenches or walls complete for UG cable protection when crossing the road of size 40 mm bore complete all as specified and directed. |
| 11 | M&L for 50 mm bore GI pipe (light grade) in replacement with all fittings laid in trenches or wall complete for UG cable protection when crossing the road of size complete all as specified and directed. |
| 12 | M&L for 80 mm bore GI pipe (light grade) in eplacement with all fittings laid in trenches/wall complete for UG cable protection when crossing the road of size complete all as specified and directed. |
| 13 | M&L for Servicing /Caliberation / Repairs to Air Circuit Breaker upto 630 Amps by OEM of ACB only for EDO ( Electrically Draw Out) type/ MDO type(Mannually Draw out type)/ Fixed type. Taking out any type of ACB for servicing / repair and checking / caliberation of microprocessor release,Earth fault protection of 4 pole, 50 KA breaking capacity 415 volts with all draw out type mechanism, advanced self powered electronic protection units, neutral overload protection, automatic earth fault relay / over current relay , automatic safety shutter, inbuilt temperature protection, icu=ics=icw(1s)=50 KA fixed in panel complete including relay wiring checking ,LT UG cable connection with main incoming ACB complete connection for its healthy functioning all as directed. Note- Certificate of Servicing /Caliberation will be provided by the contractor free of cost. |
| 14 | S&F of LED flood light with pressure die cast aluminium housing 150 Watt completed with connection including taking down old unserviceable light complete all as specified and directed. |
| 15 | S&F of LED flood light with pressure die cast aluminium housing 200 Watt completed with connection including taking down old unserviceable light complete all as specified and directed. |
| 16 | Supply and fixing in LED street light fitting 45 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection including taking down old HPSV light fitting 70/150/250 watt complete all as specified and directed by Engr-in-Charge. |
| 17 | M&L for boring of holes by manually / machine under road, pavement, hard standing by \\"trenchless technology for laying of 40/50/80 mm GI pipe for cable laying, complete all as specified and directed by Engr in charge. Note: GI pipe will be measured and paid seperately under respective item. |
| 18 | S&F in repairs cable jointing kit for 11 KV (earthed) grade cable, for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 Core XLPE armoured aluminium conductor cable of 95 Sqmm complete all as specified and directed. |
| 19 | S&F in repair Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified and directed. |
| 20 | S&F in repair Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified and directed. |
| 21 | S&F in replacement busbar chambers three phase forur wire system rated current 400 Amps with suitable busbar thickness IP41, 415 volts, complete all as specified and directed. |
| 22 | S&F in replacement busbar chambers three phase forur wire system rated current 630 Amps with suitable busbar thickness IP41, 415 volts, complete all as specified and directed. |
| 23 | S&F in repair on load change over switch including enclosure, 1000 Amp, 4 pole with advance neutral including making cable connection to the change over switch, fixing on wall/ floor with mild steel fastener, nut/bolts complete all as specified and directed. |
| 24 | S&F in repair on load change over switch including enclosure, 630 Amp, 4 pole with advance neutral including making cable connection to the change over switch, fixing on wall/ floor with mild steel fastener, nut/bolts complete all as specified and directed. |
| 25 | S&F in repair on load change over switch including enclosure, 400 Amp, 4 pole with advance neutral including making cable connection to the change over switch, fixing on wall/ floor with mild steel fastener, nut/bolts complete all as specified and directed. |
| 26 | Supply & fix cable jointing kit for 1.1 KV (earthed) grade cable for straight through Heat shrink type joint complete with jointing material and accessories suitable for 3.5 Core XLPE armoured aluminium conductor cable of 120 Sqmm complete all as specified and directed. |
| 27 | Supply & fix cable jointing kit for 1.1 KV (earthed) grade cable for straight through Heat shrink type joint complete with jointing material and accessories suitable for 3.5 Core XLPE armoured aluminium conductor cable of 95 Sqmm complete all as specified and directed. |
| 28 | Supply & fix cable jointing kit for 1.1 KV (earthed) grade cable for straight through Heat shrink type joint complete with jointing material and accessories suitable for 3.5 Core XLPE armoured aluminium conductor cable of 70 Sqmm complete all as specified and directed. |
| 29 | S&F in repair Copper lugs, E-blot size 10.5 mm, suitable for 25 sqmm 3.5 core to 120 sqmm 3 core cable including crimping/ connecting with UG cable and panel board complete all as specified and directed. |
| 30 | M&L for earthing complete with galvanized steel earth plate 600x600x6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanised iron strip 32x6 mm dia as earthing lead by means of bolts, nuts, check-nuts, and washers of galvanised iron or steel besides welding at all joints as shown in drawings and including excavation and earth work, GI pipe light grade 40 mm bore for protection of GI strip from earth electrode to and including the earth test point of galvanised Iron/steel . supplying and laying charcoal stone aggregate) chamber and RCC cover of size 54x54x50 mm (1:2:4) type B1 using 20 mm graded crushed stone aggregate reinforced with 8 mm dia TMT bars @ 75mm C/C both ways with mild steel handle 12 mm dia, PGI funnel with wire mesh, 20 mm dia GI pipe medium grade for watering all as shown in drawing Note - Cost of GI stripand GI protection pipe up to a distance 7.5 M shall be included in quated rate of above Items complete all as specified and directed. |
| 31 | M&L for earthing complete with galvanized steel earth plate 600x600x6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanised earth lead wire of 4 mm dia as earthing lead by means of bolts, nuts, check-nuts, and washers of galvanised iron or steel besides welding at all joints as shown in drawings and including excavation and earth work, GI pipe medium grade 15 mm bore for protection of GI wire from earth electrode to test point /machinery / equipment. supplying and laying charcoal dust comman salt PCC (1:2:4) type B1 using 20 mm graded stone agregrate chamber and RCC cover 54 cm X 54cm x50 mm thick (1:2:4) type B-1 using 20 mm stone agrigrtae ) reinforced with 8 mm dia TMT bars @ 75mm C/C both ways with mild steel handle 12 mm dia, using round bar ,PGI funnel with wire mesh, 20 mm dia GI pipe light grade for watering all as shown in electrical plate No-3 of SSR part-1 including testing and taking out the old one complete all as specified and directed Note - Cost of GI wire and GI protection pipe up to a distance 7.5 M shall be included in quated rate of above Items. |
| 32 | S&F MCCB TPN 63 Amp 415 Volts, 50 Hz suitable for existing and connection with copper lugs including taking down old one complete all as specified and directed. |
| 33 | S&F MCB TPN 63 Amp,C curve, 415 Volts, 50 Hz suitable for existing and connection with copper lugs including taking down old one complete all as specified and directed. |
| 34 | S&F MCB TPN 32 Amp,C curve, 415 Volts, 50 Hz suitable for existing and connection with copper lugs including taking down old one complete all as specified and directed. |
| 35 | S&F MCB SPN 32 Amp,C curve, 415 Volts, 50 Hz suitable for existing and connection with copper lugs including taking down old one complete all as specified and directed. |
| 36 | Supply ,installation, testing and commissioning of canopy headed HT 11K volt grade, 3 phase, , AC, 50 cycle, feeder piller box size 1200x1000x1000 mm, factory made outdoor pedestal type double door, fabricated out of 3.15 mm thick CRCA sheet with powder coated painting in side and outside of approved shade ,locking arrangement with duplicate keys two earthy terminal suitable cable gland for all incoming and outgoing cable grouting of feeder pillar box 15 cm above ground level by providing 90 cm long angle iron of size 50x50x6 mm welded on all the four comers embedded in PCC (1:2:4) using 20 mm graded stone agg upto 30 CM deep and 45 CM above from normal ground level complete all as specified and directed incl the following components:- (a) The panel will be having copper bus bar of size 400×40×6 mm 03 strips with porcelain HT long post insulator Note - HT Feeder Piller will be from CPRI Approved firm. |
| 37 | M & L for filtration/dehydration transformer oil of transformer capacity 50 KVA to 800 KVA indoor/outdoor type, pole mounted / plinth mounted in situ till achieve dielectric strength min 40 KV at 4mm gap complete all as specified and as directed. |
| 38 | M & L for topping up/replacement of transformer oil with new transformer oil suitable for working voltage 11000 volts grade including necessary dehydration to achieve dielectric strength min 40 KV at 4mm gap complete all as specified and as directed. Note :- (a) New transformer oil to be bought in company sealed ISI marked container with or original test certificate (b) Filtration /dehydration of transformer oil shall be carried out at the location where transformer is installed and necessary filter/dehydration plant having pressure gauge, hour meter, temperature gauge to be brought at site by contractor (c) During process of filtration of oil, transformer shall be on load. |
| 39 | M&L for silica gel grain in the breather assembly of transformer complete all as specified and directed |
| 40 | M&L for LT bush insulator complete with outer bushing studs made out of brass including oil seal ,gaskets as per existing sample for three indoor/outdoor type transformer of cap for upto 800 KVA (set of four) including taking out the old complete all as specified and directed. |
| 41 | M&L for HT bush insulator complete with outer bushing stud, made out of brass including oil seal ,gaskets as per existing size for indoor/outdoor transformer of cap for upto 800 KVA for 11K / 440 Volts including taking out the old all as specified and directed (Set of three) Please Enable Macros to View BoQ information |
| 42 | M&L for HT bush insulator complete with outer bushing stud, made out of brass including oil seal ,gaskets as per existing size for indoor/outdoor transformer of cap for upto 800 KVA for 11K / 440 Volts including taking out the old all as specified and directed (Set of three) Please Enable Macros to View BoQ information |