| 1 | Excavation in trenches, n.exc 1.5m wide & n.exc 1.5m in depth for foundation etc in hard and dence soil & getting out for laying of cable, poles etc, complete all as specified & directed. |
| 2 | Returning filling in including spreading leveling watering & well ramming in layers n exc. 25cm Cum thick. |
| 3 | Removing of surplus excavated soil to a distance n.exe 50 Mtr and depositing where directed at a level n.exe 1.5 mtr above the starting point complete all as specified. |
| 4 | Material and labour for sand in trenches as in cushioning to under ground cable spreading, levelling hand punning complete all as specified and directed. Note- Punned down thickness will be measured for payment purpose complete all as specified and directed. |
| 5 | Supply and laying unreinforced pre cast concrete cable cover class LV type I flat size 250x150x40mm all as specified and directed. |
| 6 | Unbinding from insulators ACSR conductor any size of LT/HT over head line for repairs, restretching of ACSR conductor to achieve proper sag and rewinding to the insulators using aluminium/ GI wire all as required at site or directed. Note:- Distance between two poles irrespective of distance and no of lengths of conductor shall be considered as a single span and Nos of conductor per span is not more than 8 Nos . |
| 7 | Dismantling of insulator complete of any size and type from exisiting site all as directed by Engr -in- Charge. |
| 8 | Repair/Replacement of Shackle Type polymor insulator including galvanised mild steel straps, washers insulator bolts, washers and nuts of height 100 mm, max dia 115 mm,section of straps 31x5 mm,dia of bolts 14 mm all as specified and directed by Engr-in-charge. |
| 9 | Repair/Replacement of Pin insulator polymor white, 100 mm height, 65 mm dia for 1100 volts grade complete all as specified. |
| 10 | Repair/Replacement of loop Polymor insulator white small size with overall dimensions 65 x 90mm, clearance of hole 16mm for stay complete |
| 11 | Dismantling of stay assembly complete of any size and type from exisiting site all as directed by Engr -in- Charge. |
| 12 | M&L for stay assembly complete with stay plate bow, stay rod of dia 16mm and gavanised iron stay wire stranded of size 7/4mm and accessories as shown in electric plate No 1 of SSR part - I (loop type insulator, stay clamps, excavation and concrete shall be measured separately) complete all as spd and directed. |
| 13 | Repairing and servicing (Oiling and greasing) of Gang Operated Switch 11 KV vertical/Horizontal mounted and replacing defective parts including replacement of unserviceable spare parts as required for smooth functioning of AB switch, testing for its proper operation, all as directed at site. |
| 14 | M&L for Painting to exposed surfaces of LT Steel tubular pole with one coat of synthetic enamel paint of complete pole and up to 1 mtr height from ground level with 3 strip of yellow colour synthetic enamel paint and two strip of black synthetic paint including preparation of old painted surface, complete all as specified and directed by engr-in charge. |
| 15 | Repair of pole copping for LT/HT Pole Plain cement concrete M-15 nominal mix, type B-1 using 20mm graded crushed stone aggregate as in coping of pole including necessary form work , complete all as specified. |
| 16 | Dismantling UNSV air break gang operated and Supply, installation connecting electrically & commissioning switch air break, gang operated, tripple pole mounted on Polymer insulators 15 Nos and steel frame with operating mechanism with 20 mm dia GI Pipe (Medium Grade) Rod worked from ground level, drop out fuse, for current rating upto 200 amps and working voltage 11000 volts all as required at site or directed by Engr-in-charge. Make: BHEL/Rashtriya |
| 17 | Repair/Replacement of PVC insulated, heavy duty, LT XLPE galvanised steel strip armoured electric power cable of size 10 Sqmm x 4 core with stranded aluminium conductor 1100 Volts grade, jointed with cable glands, lugs etc., laid in trenches/drawn through pipe, complete all as specified and directed.Note :- excavation and earth work shall be measured and paid separately under respective items. |
| 18 | Repair/Replacement of PVC insulated, heavy duty, LT XLPE galvanised steel strip armoured electric power cable of size 25 Sqmm x 4 core with stranded aluminium conductor 1100 Volts grade, jointed with cable glands, lugs etc., laid in trenches/drawn through pipe, complete all as specified and directed.Note :- excavation and earth work shall be measured and paid separately under respective items. |
| 19 | Repair/Replacement of PVC insulated, heavy duty, LT XLPE galvanised steel strip armoured electric power cable of size 50 Sqmm x 3.5 core with stranded aluminium conductor 1100 Volts grade, jointed with cable glands, lugs etc., laid in trenches/drawn through pipe, complete all as specified and directed.Note :- excavation and earth work shall be measured and paid separately under respective items. |
| 20 | Repair/Replacement of PVC insulated, heavy duty, LT XLPE galvanised steel strip armoured electric power cable of size 95 Sqmm x 3.5 core with stranded aluminium conductor 1100 Volts grade, jointed with cable glands, lugs etc., laid in trenches/drawn through pipe, complete all as specified and directed.Note :- excavation and earth work shall be measured and paid separately under respective items. |
| 21 | Repair/Replacement of PVC insulated, heavy duty, LT XLPE galvanised steel strip armoured electric power cable of size 185 Sqmm x 3.5 core with stranded aluminium conductor 1100 Volts grade, jointed with cable glands, lugs etc., laid in trenches/drawn through pipe, complete all as specified and directed.Note :- excavation and earth work shall be measured and paid separately under respective items. |
| 22 | Repair/Replacement of PVC insulated, heavy duty, LT XLPE galvanised steel strip armoured electric power cable of size 300 Sqmm x 3.5 core with stranded aluminium conductor 1100 Volts grade, jointed with cable glands, lugs etc., laid in trenches/drawn through pipe, complete all as specified and directed.Note :- excavation and earth work shall be measured and paid separately under respective items. |
| 23 | Taking down old unserviceable GI pipe light grade any size coplete all as specified and directed |
| 24 | S&F GI tubing 50mm dia \\"light grade\\" with all fittings, laid in trenches, fixed on pole/under road crossing or passing through gutters etc, complete all as directed. |
| 25 | S&F GI tubing 80mm dia \\"light grade\\" with all fittings, laid in trenches, fixed on pole/under road crossing or passing through gutters etc, complete all as directed. |
| 26 | Repair and Replacement of LT panel board, outdoor cubical type, floor on MS angle iron frame of size 50 x 50 x 6 mm thick, made out of 3.15 mm thick CRCA sheet powder coated for load bearing members for double doors both side openable and covers, Suitable for 3 phase 4 wire 50 cycle 500 Volts system weather and vermin proof, including internal wiring with suitable size copper cable, heat shrinkable sleeves, chromium plated brass cable glands, lugs, 400Amps Aluminium Busbar and necessary excavation earth work, PCC grouting etc. to comprising of the following, complete all as directed by Engineer -in- Charge . (a) MCCB 400 Amps 4 Pole 36KA (Main Incoming) -01 No b) MCCB 160 Amps 3Pole 36KA 415V, 50 Hz (Outgoing) 01 Noc) MCCB 63Amps 3Pole 36KA 415V, 50Hz (Outgoing) 02 Nos d) Digital type panel mounted 3 phase Voltmeter with LED display - 01 Nos e) Digital type panel mounted 3 phase Ammeter incl suitable CT with LED display - 01 Nosf) Indicator lamp RYB LED type(3 Nos) - 01 Set |
| 27 | S & F in replacement ACB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 1250 Amps 50 KA complete incl taking donw old one, all as specified and directed by Engr-In-Charge. |
| 28 | S & F in replacement MCCBs 415 Volt 3 pole Adjustable thermal & adjustable Magnetic Setting with breaking capacity 25 KA 63 Amps complete all as specified and directed by Engr-In-Charge. |
| 29 | S & F in replacement MCCBs 415 Volt 3 pole Adjustable thermal & adjustable Magnetic Setting with breaking capacity 36KA 125 Amps complete all as specified and directed by Engr-In-Charge. |
| 30 | S & F in replacement MCCBs 415 Volt 4 pole Adjustable thermal & adjustable Magnetic Setting with breaking capacity 36KA 160 Amps complete all as specified and directed by Engr-In-Charge. |
| 31 | S & F in replacement MCCBs 415 Volt 4 pole Adjustable thermal & adjustable Magnetic Setting with breaking capacity 36KA 200 Amps complete all as specified and directed by Engr-In-Charge. |
| 32 | S & F in replacement MCCBs 415 Volt 4 pole Adjustable thermal & adjustable Magnetic Setting with breaking capacity 36KA 250 Amps complete all as specified and directed by Engr-In-Charge. |
| 33 | S & F in replacement MCCBs 415 Volt 4 pole Adjustable thermal & adjustable Magnetic Setting with breaking capacity 36KA 400 Amps complete all as specified and directed by Engr-In-Charge. |
| 34 | S & F in replacement MCCBs 415 Volt 4 pole Adjustable thermal & adjustable Magnetic Setting with breaking capacity 50KA 630 Amps complete all as specified and directed by Engr-In-Charge. |
| 35 | Supply and fix in Replcement of digital type voltmeter of size 96x96 sqmm, flush mounted type, model three phase, class 0.5 including taking down old unsv complete all as specified and as directed |
| 36 | Supply and fix in Replcement of digital type ampere meter, three phase, class 0.5 flush mounted case including taking down old unsv complete all as specified and as directed. . |
| 37 | Supply and fix in Replcement of lamp indicator, three phase, class 0.5 flush mounted case including taking down old unsv complete all as specified and as directed. |
| 38 | Supply and fix in Replcement of selector Switch, three phase, class 0.5 flush mounted case including taking down old unsv complete all as specified and as directed. |
| 39 | Repair/replacement of bus chamber factory made Outdoor type, CPRI approved, size 0.45mx0.75mx0.4m deep, fabricated out of 3.15 mm thick mild steel sheet and vermin proof with neoprene gasket having front opening and locking arrangement mounted on angle iron legs made out of angle iron size 40 mm x 40 mm x 6 mm, 8.0 mtr long, 0.40 mtr above ground level and 0.40 mtr embedded in PCC 1:2:4 type 'B'-1 using 20mm graded crushed stone agreegate blocks of size 0.30 mtr x 0.30 mtr x 0.50 mtr - 04 Nos, duly painted with two coats of synthetic enemel paint over a coat of red oxide Primer, complete with 200 Amp rated aluminium bus bar (Size LED phase indicators, suitable for 3 phase 4 wire supply system with MCCB 125 Amp 4 pole breaking capacity 25 KA -01 No, duly drilled holes for cable connection mounted on epoxy based post insulators all as required at site, complete all as specified and directed . |
| 40 | Repair/replacement of Wall Mound 6 way LT Bus bar Chamber of 200 Amps fabricated by using sheet steel (CRCA) of 1.6 mm thickness, epoxy powder coated and comprising of 04 Nos of aluminium bus bar. |
| 41 | M&L in replacement for earthing complete with Copper earth plate electrode 60 cm x 60 cm x 3.15 mm thick buried directly in ground to a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at a depth not less than 1.50 mtr below ground level, earth plate surrounded by 15 cm thick packed layer of charcoal and common salt alternatively upto 90 cm and connected with and including Copper strip 20 x 3 mm by means of bolts, nuts, check nuts and washers of GI. 15 mm bore GI pipe light grade for protection of GI wire from earth plate to testing point for protection, 20mm bore GI pipe medium grade for water with wire mesh and funnel for watering including necessary excavation and earth work, PCC chamber (1:3:6) type C-2 with RCC cover complete all as shown in electrical plate No 3 of MES schedule Part I of SSR Part I (2009) complete all as specified |
| 42 | M&L in replacement for Earthing complete with galvanised steel earth plate electrode 60 cm X 60 cm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to and inclduing GI Strip 32X6 mm as earthing lead, by means of bolts, nuts, check nuts and washers of galvanised iron all as shown in electrical plate No 5 of MES SSR Part I and testing on completion inclduing excavation and earth work in any type of soil, PCC (1:3:6) type C1 chamber, MS frame and cover 6 mm thick in cement concrete (1:2:4) type B1 reinforced with welded steel wire fabric or XPM (weight not less than 4 Kg per Sqm) with cast iron frame, funnel with wire mesh, GI watering pipe 20mm dia medium grade and lugs complete all as specified and directed |
| 43 | Supply, erecting and fixing in true vertical position Steel tubular swaged poles (9.0 metres long) complete with cast iron base plate, finial taper plug,bolts,nuts & screws including Dismandling of damaged poleect al as specified type 410 SP-31, complete all as specified. Note : - Earth work & PCC work will be measured & paid seprately under relavent item. |
| 44 | Material & labour for Providing PCC 1:3:6, type C2 (using 40 mm graded stone aggregate) as in mass filling all as specified and directed. |
| 45 | Supply and fixing in replacement On load changeover switch 1000 Amps, 4 pole in sheet metal enclosure, side /front handle operated, complete all as secified and directed |
| 46 | Supply and fixing in replacement On load changeover switch 630 Amps, 4 pole in sheet metal enclosure, side /front handle operated, complete all as secified and directed |
| 47 | Supply and fixing in replacement On load changeover switch 400 Amps, 4 pole in sheet metal enclosure, side /front handle operated, complete all as secified and directed |
| 48 | Supply and fixing in replacement Off load changeover switch 1250 Amps, 4 pole in sheet metal enclosure, side /front handle operated, complete all as secified and directed |
| 49 | Supply and fixing in replacement Off load changeover switch 1000 Amps, 4 pole in sheet metal enclosure, side /front handle operated, complete all as secified and directed |
| 50 | Supply and fixing in replacement Off load changeover switch 630 Amps, 4 pole in sheet metal enclosure, side /front handle operated, complete all as secified and directed |
| 51 | Supply and fixing in replacement Off load changeover switch 200 Amps, 4 pole in sheet metal enclosure, side /front handle operated, complete all as secified and directed |
| 52 | Supply & laying or fixing 1100 volts grade Heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape overall PVC sheathed Solid conductor in service connections 6 Sqmm twin core flat/circular cable complete all as specified and directed. |
| 53 | Supply & laying or fixing 1100 volts grade Heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape overall PVC sheathed Solid conductor in service connections 16 Sqmm twin core flat/circular cable complete all as specified and directed. |
| 54 | Cutting the existing PCC/ Road for passing of UG Cable in road crossing and making good the disturbed surface of road to its original specification complete all as directed. |
| 55 | Repair/replacement aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground |
| 56 | Repair/replacement air termination, single pointed aluminium rod 12mm dia and 300mm long |
| 57 | Repair/replacement test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw |
| 58 | Deduct Schedule of Credit of Rs (-) 56314.00 (Minus) as listed in Schedule 'A' (Contd). Contract Sum shall be arrived after deducting the credit amount.Note :- Tenderers will not quote against this item being a firm amount. Please Enable Macros to View BoQ information |