| 1 | Excavating in trenches in hard/dense soil, n. exc. 1.5 m wide and n. exc. 1.5 m in depth, for foundation, laying cables etc. or for shafts, wells, cess pits, manholes, pier holes, etc n. exc. 10 sqm on plan and n. exc 1.5 m in depth and getting out complete all as specified and directed. |
| 2 | Excavating in trenches in hard/dense soil, n. exc. 1.5 m wide and exc. 1.5 m but n. exc.3 m in depth, for foundation, etc. or for shafts, wells, cess pits, manholes, pier holes, etc n. exc. 10 sqm on plan and exc 1.5 m but n. exc. 3 m in depth and getting out complete all as specified and directed. |
| 3 | Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25 cm complete all as specified and directed. |
| 4 | Supply and laying of DWC (Double Wall Corrugated) pipe of 75 mm bore as per IS-16205 laid for protection of cables in trenches complete all as specified and diriected. |
| 5 | Supply and laying of DWC (Double Wall Corrugated) pipe of 63 mm bore as per IS-16205 laid for protection of cables in trenches complete all as specified and diriected. |
| 6 | M&L for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate in foundations, filling and mass concrete complete all as specified and directed.Note:- Volume of pole/strut embedded shall be deducted for the purpose of payment. |
| 7 | M&L for PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in pedestal/coping including necessary weathering and form work etc complete all as specified and directed. Note:- Volume of pole/strut embedded shall be deducted for the purpose of payment. |
| 8 | Taking out old unservicable under ground LT XLPE/ PVC cable of any size from trenches/ wall/ roof/ pipe/ DB including taking out of brick layer of cable protection complete all as specified and as directed. Note : Excavation and earth wrok shall be measured and paid for separately. |
| 9 | Supply and laying in trenches or fixed to wall/pole or passing through ducts or pipe, cable LT 1100 volts grade heavy duty, XLPE insulated , armoured heavy duty electric cable, with aluminium conductor of size 10 Sqmm x 4 core or fixed to wall/pole or passing through ducts or pipe of any size, any core, complete all as specified and directed. |
| 10 | Supply and laying in trenches or fixed to wall/pole or passing through ducts or pipe, cable LT 1100 volts grade heavy duty, XLPE insulated , armoured heavy duty electric cable, with aluminium conductor of size 16 Sqmm x 4 core or fixed to wall/pole or passing through ducts or pipe of any size, any core, complete all as specified and directed. |
| 11 | All as per description of srl item No. 10.00 here-in-before but size of cable 25 Sqmm 4 core |
| 12 | All as per description of srl item No. 10.00 here-in-before but size of cable 35 Sqmm 3.5 core. |
| 13 | All as per description of srl item No. 10.00 here-in-before but size of cable 50 Sqmm 3.5 core |
| 14 | All as per description of srl item No. 10.00 here-in-before but size of cable 70 Sqmm 3.5 core |
| 15 | All as per description of srl item No. 10.00 here-in-before but size of cable 95 Sqmm 3.5 core |
| 16 | All as per description of srl item No. 10.00 here-in-before but size of cable 120 Sqmm 3.5 core |
| 17 | Relaying only in trenches or fixed to wall/pole or passing through ducts or pipe, cable LT 1100 volts grade heavy duty, XLPE insulated, armoured heavy duty electric cable, with aluminium conductor of size 10/16 Sqmm x 2/4 core complete all as specified and directed. |
| 18 | All as per description of srl item No. 17.00 here-in-before but size of cable 25 Sqmm 3.5 core |
| 19 | All as per description of srl item No. 17.00 here-in-before but size of cable 35 Sqmm 3.5 core |
| 20 | All as per description of srl item No. 17.00 here-in-before but size of cable 50 Sqmm 3.5 core |
| 21 | All as per description of srl item No. 17.00 here-in-before but size of cable 70 Sqmm 3.5 core |
| 22 | All as per description of srl item No. 17.00 here-in-before but size of cable 95 Sqmm 3.5 core |
| 23 | All as per description of srl item No. 17.00 here-in-before but size of cable 120 Sqmm 3.5 core |
| 24 | All as per description of srl item No. 17.00 here-in-before but size of cable 185 Sqmm 3.5 core |
| 25 | All as per description of srl item No. 17.00 here-in-before but size of cable 240 Sqmm 3.5 core. Note for item No. 10.00 to 24.00:- Excavation & earth work, sand cushioning, brick cover and protection pipe etc. shall be measured and paid for separately. |
| 26 | Supplying, jointing and connecting in repairs cable end termination joint kit, out door, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 25 sqmm to 50 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed. |
| 27 | Supplying, jointing and connecting in repairs cable end termination joint kit, out door, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 70 sqmm to 120 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed. |
| 28 | Supplying, jointing and connecting in repairs cable end termination joint kit, out door, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 150 sqmm to 185 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed. |
| 29 | Supplying, jointing and connecting in repairs cable end termination joint kit, out door, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 240 sqmm to 300 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed. |
| 30 | Supplying, jointing and connecting in repairs straight through joint, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 25 sqmm to 50 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed. |
| 31 | Supplying, jointing and connecting in repairs straight through joint, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 70 sqmm to 120 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed. |
| 32 | Supplying, jointing and connecting in repairs straight through joint, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 150 sqmm to 185 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed. |
| 33 | Supplying, jointing and connecting in repairs straight through joint, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 240 sqmm to 300 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed. |
| 34 | M&L for replacement of 40 mm bore galvanised steel tubing, light grade, with all fittings, for protection of cable, laid in trenches/road crossing/floor or fixed to pole/wall with and including 02 Nos. MS clamp made of FI 25x4 mm, nuts, bolts and washers complete all as specified and directed. |
| 35 | M&L for replacement 50 mm bore galvanised steel tubing, light grade, with all fittings, for protection of cable, laid in trenches/road crossing/floor or fixed to pole/wall with and including 02 Nos. MS clamp made of FI 25x4 mm, nuts, bolts and washers complete all as specified and directed. |
| 36 | M&L for replacement 80 mm bore galvanised steel tubing, light grade, with all fittings, for protection of cable, laid in trenches/road crossing/floor or fixed to pole/wall with and including 02 Nos. MS clamp made of FI 25x4 mm, nuts, bolts and washers complete all as specified and directed. |
| 37 | S&F in repairs MCCB 4 Pole, 415 V, fixed type, 160 Amps rating, microprecesser based energy with rupturing capacity 36 KA, as approved complete all as specified and directed. |
| 38 | S&F in repairs MCCB 4 Pole, 415 V, fixed type, 200 Amps rating, microprecesser based energy with rupturing capacity 36 KA, as approved complete all as specified and directed. |
| 39 | S&F in repairs MCCB 4 Pole, 415 V, fixed type, 250 Amps rating, microprecesser based energy with rupturing capacity 36 KA, as approved complete all as specified and directed. |
| 40 | S&F in repairs MCCB 4 Pole, 415 V, fixed type, 315 Amps rating, microprecesser based energy with rupturing capacity 36 KA, as approved complete all as specified and directed. |
| 41 | S&F in repairs MCCB 4 Pole, 415 V,fixed type, 400 Amps rating, microprecesser based energy with rupturing capacity 36 KA, as approved complete all as specified and directed. |
| 42 | S&F in repairs MCCB 4 Pole, 415 V, fixed type, 630 Amps rating, microprecesser based energy with rupturing capacity 36 KA, as approved complete all as specified and directed. |
| 43 | Supply, installation, commissioning and testing of totally enclosed outdoor type LT Panel in replacement dust and vermin proof floor mounted type (IP-65 degree of protection) made out of 3 mm thick CRCA sheet of recommended size, All sheet metal parts separately chemically treated with 7 tank treatment process, The panel having both side opening door with locking arrangement, all doors fixed with aluminium hinges with suitable size nuts, bolts and shall have flexible fixing of each switchgear and controlgear compartment with cable alley tray of size not less than 30 cm, duly painted with two coats of synthetic enamel paint powder coated, having bus bar 1000 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50 HZ AC supply, thimbling, cable entry boxes, cable gland and LT panel shall be mounted on iron angle frame made out of 50mm x 50mm x 6 mm frame with 4 No. legs of size not less than 45 cms each fixed with nut bolts of suitable size at bottom portion of the panel, grouted in PCC foundation 1:2:4 type B-1 with 20 mm graded stone aggregates totally tested on completion, including taking down existing LT panel complete and suitable for and including the following :- |
| 44 | (i) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 630 amp rating, microprecesser based energy with rupturing capacity 50 KA - 01 No. as income. (ii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 315 amp rating, with rupturing capacity 36 KA - 02 No. for outgoing(iii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 250 amp rating, with rupturing capacity 36 KA - 02 No. for outgoing (iv) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 200 amp rating, with rupturing capacity 36 KA - 01 No. for outgoing (v) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 100 amp rating, with rupturing capacity 36 KA - 01 No. for outgoing (vi) Indicator set RYB -01 Set of 3 (vii) Multifunction digital panel meter suitable to display amps, volts, frequency etc - 01 No including CTs of appropriate ratio. (viii) All accessories prewired with suitable size copper conductor cable or strip including foundation as per manufacturer instruction all as required and directed. |
| 45 | Supply, installation, commissioning and testing of totally enclosed outdoor type LT Panel in replacement dust and vermin proof floor mounted type (IP-65 degree of protection) made out of 3 mm thick CRCA sheet of recommended size, All sheet metal parts separately chemically treated with 7 tank treatment process, The panel having both side opening door with locking arrangement, all doors fixed with aluminium hinges with suitable size nuts, bolts and shall have flexible fixing of each switchgear and controlgear compartment with cable alley tray of size not less than 30 cm, duly painted with two coats of synthetic enamel paint powder coated, having bus bar 600 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50 HZ AC supply, thimbling, cable entry boxes, cable gland and LT panel shall be mounted on iron angle frame made out of 50mm x 50mm x 6 mm frame with 4 No. legs of size not less than 45 cms each fixed with nut bolts of suitable size at bottom portion of the panel, grouted in PCC foundation 1:2:4 type B-1 with 20 mm graded stone aggregates totally tested on completion, including taking down existing LT panel complete and suitable for and including the following :- |
| 46 | (i) MCCB 4 pole, 415 volts, , 400 amp rating, microprecesser based energy with rupturing capacity 50 KA - 01 No. as income.(ii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 250 amp rating, with rupturing capacity 36 KA - 02 No. for outgoing (iii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 200 amp rating, with rupturing capacity 36 KA - 01 No. for outgoing (iv) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 100 amp rating, with rupturing capacity 36 KA - 02 No. for outgoing (v) Indicator set RYB -01 Set of 3 (vi) Multifunction digital panel meter suitable to display amps, volts, frequency etc - 01 No including CTs of appropriate ratio. (vii) All accessories prewired with suitable size copper conductor cable or strip including foundation as per manufacturer instruction all as required and directed. |
| 47 | Supply, installation, commissioning and testing of totally enclosed outdoor type LT Panel in replacement dust and vermin proof floor mounted type (IP-65 degree of protection) made out of 3 mm thick CRCA sheet of recommended size, All sheet metal parts separately chemically treated with 7 tank treatment process, The panel having both side opening door with locking arrangement, all doors fixed with aluminium hinges with suitable size nuts, bolts and shall have flexible fixing of each switchgear and controlgear compartment with cable alley tray of size not less than 30 cm, duly painted with two coats of synthetic enamel paint powder coated, having bus bar 600 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50 HZ AC supply, thimbling, cable entry boxes, cable gland and LT panel shall be mounted on iron angle frame made out of 50mm x 50mm x 6 mm frame with 4 No. legs of size not less than 45 cms each fixed with nut bolts of suitable size at bottom portion of the panel, grouted in PCC foundation 1:2:4 type B-1 with 20 mm graded stone aggregates totally tested on completion including taking down existing LT panel complete and suitable for and including the following :- |
| 48 | (i) MCCB 4 pole, 415 volts, 400 amp rating, microprecesser based energy with rupturing capacity 50 KA - 01 No. as income. (ii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 315 amp rating, with rupturing capacity 36 KA - 01 No. for outgoing(iii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 200 amp rating, with rupturing capacity 36 KA - 02 No. for outgoing (iv) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 100 amp rating, with rupturing capacity 36 KA - 01 No. for outgoing (v) Indicator set RYB -01 Set of 3 (vi) Multifunction digital panel meter suitable to display amps, volts, frequency etc - 01 No including CTs of appropriate ratio.(vii) All accessories prewired with suitable size copper conductor cable or strip including foundation as per manufacturer instruction all as required and directed. |
| 49 | Supply, installation, commissioning and testing of totally enclosed outdoor type LT Panel in replacement dust and vermin proof floor mounted type (IP-65 degree of protection) made out of 3 mm thick CRCA sheet of recommended size, All sheet metal parts separately chemically treated with 7 tank treatment process, The panel having both side opening door with locking arrangement, all doors fixed with aluminium hinges with suitable size nuts, bolts and shall have flexible fixing of each switchgear and controlgear compartment with cable alley tray of size not less than 30 cm, duly painted with two coats of synthetic enamel paint powder coated, having bus bar 600 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50 HZ AC supply, thimbling, cable entry boxes, cable gland and LT panel shall be mounted on iron angle frame made out of 50mm x 50mm x 6 mm frame with 4 No. legs of size not less than 45 cms each fixed with nut bolts of suitable size at bottom portion of the panel, grouted in PCC foundation 1:2:4 type B-1 with 20 mm graded stone aggregates totally tested on completion, including taking down existing LT panel complete and suitable for and including the following :- |
| 50 | (i) MCCB 4 pole, 415 volts, 400 amp rating, microprecesser based energy with rupturing capacity 50 KA - 01 No. as income.(ii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 250 amp rating, with rupturing capacity 36 KA - 02 No. for outgoing (iii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 100 amp rating, with rupturing capacity 36 KA - 01 No. for outgoing(iv) Indicator set RYB -01 Set of 3 (v) Multifunction digital panel meter suitable to display amps, volts, frequency etc - 01 No including CTs of appropriate ratio. (vi) All accessories prewired with suitable size copper conductor cable or strip including foundation as per manufacturer instruction all as required and directed. |
| 51 | Supply, installation, commissioning and testing of totally enclosed outdoor type LT Panel in replacement dust and vermin proof floor mounted type (IP-65 degree of protection) made out of 3 mm thick CRCA sheet of recommended size, All sheet metal parts separately chemically treated with 7 tank treatment process, The panel having both side opening door with locking arrangement, all doors fixed with aluminium hinges with suitable size nuts, bolts and shall have flexible fixing of each switchgear and controlgear compartment with cable alley tray of size not less than 30 cm, duly painted with two coats of synthetic enamel paint powder coated, having bus bar 600 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50 HZ AC supply, thimbling, cable entry boxes, cable gland and LT panel shall be mounted on iron angle frame made out of 50mm x 50mm x 6 mm frame with 4 No. legs of size not less than 45 cms each fixed with nut bolts of suitable size at bottom portion of the panel, grouted in PCC foundation 1:2:4 type B-1 with 20 mm graded stone aggregates totally tested on completion including taking down existing LT panel complete and suitable for and including the following :- |
| 52 | (i) MCCB 4 pole, 415 volts, 250 amp rating, microprecesser based energy with rupturing capacity 36 KA - 01 No. as incoming (ii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 100 amp rating, with rupturing capacity 36 KA - 03 No. for outgoing (iii) Indicator set RYB -01 Set of 3 (iv) Multifunction digital panel meter suitable to display amps, volts, frequency etc - 01 No including CTs of appropriate ratio. (v) All accessories prewired with suitable size copper conductor cable or strip including foundation as per manufacturer instruction all as required and directed. |
| 53 | S&F in repairs junction box, factory fabricated, pole mounted, for street light, size 260mm x 160mm x 250 mm of approved make, made out of 2 mm thick CRCA powder coated sheet as per IP 65, including 63A,Three Phase four wire having four no. aluminium Bus Bar including 6A SP MCB. The box should have auto Door Lock facility with magnetic Lock (both side of plate) using necerssary fixing arrangement such as clamps ,nut, bolts and washer complete all as specified and directed. |
| 54 | Trimming up Bushes/ Tree branches upto 5 mtr all around security light poles & LT line, removing cut branches/ leaves from site complete all as specified and directed, Note :- (i) The overhead lines will be kept clear from all trees by trimming of tree branches with 5 mtr all around the line. (ii) Necessary permission shall be obtained by contractor from department one day prior to trimming and shut down in particular area will be arranged by department. (iii) Only effected Span where tree branches are touching nearly LT lines shall be measured. |
| 55 | M&L for detection of any type of fault in LT underground cable, laid in soil at plane area or forest area, with the help of Cable fault locator machine. Cable fault locator with carriyng vehicle and cable fault detection technician shall be provided by the contractor. Span of faulty cable shall be traced out by the technician by meggering LT cable. Note : (i) Detection of fault in one span of length will be measured as Each Job.(ii) Technicians will be employed by the working agencies. (iii) Excavation & Earth work shaill be measured and paid seperately.(iv) Replacement of cable & joints shall be measured and paid saperately.(v) Measurement & Payment shall be made only if the fault has been located & rectified. |
| 56 | M&L in repairs for mild steel cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat & two coats of aluminium paint including dismantling from pole complete all as specified and directed. Please Enable Macros to View BoQ information |
| 57 | M&L in repairs for mild steel cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat & two coats of aluminium paint including dismantling from pole complete all as specified and directed. Please Enable Macros to View BoQ information |