| 1 | Material and labour for replacement of fuel filter for 1000/1010 KVA DG Set , Make:-Greaves and change of fuel filter after every 250 Hrs complete all as per site requirement |
| 2 | Material and labour for replacement of fuel filter for 160 KVA DG Set , Make:-Cummins and change of fuel filter after every 250 Hrs complete all as specified and directed by Engr-in Charge. |
| 3 | Material and labour for replacement of fuel filter for , 160, 125, 82.5, 62.5, 32.5 A DG Set , Make:-Kiloskar and change of fuel filter after every 250 Hrs complete all as specified and directed by Engr-in Charge. |
| 4 | Material and labour for replacement of lub oil filter/super by pass filter for 1000/1010 KVA DG Set , Make:- Cummins and change of oil filter after every 250 Hrs complete all as per site requirement including lubricating and greasing to all parts complete all as specified and directed by Engr-in Charge. |
| 5 | Material and labour for replacement of lub oil filter for 200, 160, 125, 82.5, and change of oil filter after every 250 Hrs complete all as per site requirement including lubricating and greasing to all parts complete all as specified and directed by Engr-in Charge. |
| 6 | Material and labour for replacement lub oil filter for 63/35 KVA DG Set , Make:-Kiloskar and change of fuel filter after every 250 Hrs complete all as specified and directed by Engr-in Charge. |
| 7 | Material and labour for replacement of air cleaner filter for 1000/1010 KVA DG Make : Cummins set change of air cleaner filter Make: Kirloskar/Greaves after every 500 Hrs complete all as per site requirement complete all as specified and directed by Engr-in Charge. |
| 8 | Material and labour for replacement of air cleaner filter for 160/125/82.5 KVA DG set change of fuel filter Make:Cummins/Kirloskar after every 500 Hrs complete all as per site requirement complete all as specified and directed by Engr-in Charge. |
| 9 | Material and labour for replacementl of Air cleaner filter for 63/35 KVA DG Set , Make:-Kiloskar and change of fuel filter after every 500 Hrs complete all as per site requirement .complete all as specified and directed by Engr-in Charge. |
| 10 | Calbiration of injector assembly including replacement of injector cups, barrel,nozzles, O-rings screen filter and setting the oil pressure with testing suitable for 160/125/82.5 KVA DG Set, Make:- Kirloskar and Model HA69TC DG set complete all as directed by Engr-in-Charge. |
| 11 | Calbiration of injector assembly including replacement of injector cups, barrel,nozzles, O-rings screen filter and setting the oil pressure with testing suitable for 1010 , Make:-Cummins DG set complete all as specified and directed by Engr-in Charge. |
| 12 | S&F in replacement of fan belt suitable for 160/100/125/82.5 KVA DG set complete all as specified and directed by Engr-in Charge. Make-Fenner/KCL |
| 13 | S&F in replacement of fan belt suitable for 1010 KVA DG set complete all as specified and directed by Engr-in Charge. Make-Fenner/KCL |
| 14 | Supply & fix in replacement of U/S lead acid battery 12 Volt 180AH with initially charged complete all as specified and directed by Engr-in Charge. Make-Exide |
| 15 | Repair/servicing self starter by supply and fixing including taking out the following parts ,(a). Field Coil (b). Armature Winding (c ). Bush (d). Solenoid switch (Gear) for 1010 KVA DG Sets complete all as specified and directed by Engr-in Charge.Make : Cummins |
| 16 | Repair/servicing self starter by supply and fixing including taking out the following parts ,(a). Field Coil (b). Armature Winding (c ). Bush (d). Solenoid switch (Gear) for 63/82.5/125 KVA DG Sets complete all as specified and directed by Engr-in Charge. Make : Kirloskar |
| 17 | M&L for replacement of automatic voltage regulator for DG Set of following capacity :- |
| 18 | Description all as per item No. 17.00 here in before but DG Set 1010 KVA Make : Cummins |
| 19 | Description all as per item No. 17.00 here in before but DG Set 160/125/82.5 KVA Make : Kirloskar/Cummins |
| 20 | Description all as per item No. 17.00 here in before but DG Set of capacity 62.5/32.5 KVA Make : Mahindra |
| 21 | Dismantling the radiator from the engine of 1010 KVA DG set transporting the radiator from site to workshop. Dismantling the radiator in and including descaling ,gas welding the leaking tube whichever required for proper functioning of radiator. After repair retransportation from workshop to site and fixing the same with engine as existing and reseting complete all as specified and directed by Engr-in Charge. |
| 22 | Description all as per item Ser No. 18.00 here-in-before but of capacity 160/125/82.5 KVA |
| 23 | Dismantling disconnecting Turbo charger from 1010 KVA DG Sets supply and fixing the same complete as specified and as directed by Engr-in-charge.Make :Holmet or equivalent |
| 24 | Supply & fixing in replacement Diesel pipe set flexible for 1010/160/125/82.5 KVA DG Set complete all as specified and as directed by Engr-in-Charge. Make :- Cummins/Kirloskar |
| 25 | Supply & fixing hose rubber C/W inlet suitable for 160/125/82.5 KVA DG Set complete all as specified and as directed by Engr-in-Charge. Make :-Kirloskar |
| 26 | Supply & fixing water pump assembly suitable for 1010 KVA DG Set complete all as specified and as directed by Engr-in-Charge. Make :- Cummins or Equivalent |
| 27 | Supply & fixing water pump assembly suitable for 160/125/82.5 KVA DG Set complete all as specified and as directed by Engr-in-Charge. Make :- Kirloskar/Cummins or equivalent |
| 28 | S&F in replacement Alternator (Battery Charger) suitable for DG Set of capacity 1010 KVA of existing make and Modal complete all as specified and directed. |
| 29 | S&F in replacement Alternator (Battery Charger) suitable for DG Set of capacity 160/125/82.5 KVA of existing make and Modal complete all as specified and directed. |
| 30 | M&L for cleaning of fuel tank of DG sets of capacity upto 1010 KVA by draining out the fuel and storing in a container for re-filling complete all as specified and directed by Engr-in-charge. |
| 31 | Supply and fixing for replacement of copper battery lead 3 Mtrs long PVC insulated multi stranded with brass clamp incl necessary bolts & nuts and fixing lugs etc complete all as specified and as directed by Engr-in-Charge. |
| 32 | Draining all the U/S DAFC 50% from the DG Sets Supply and filling the DAFC 50% all as specified and as directed by Engr-in-charge.Make Servo, HP or any approved Make. |
| 33 | Supply and fix electronic nozzle suitable for 82.5 KVA DG set of existing make and model including taking out old UNSV nozzles. Make:-Greaves/Kirloskar/Cummins DG set complete all as directed by Engr-in-Charge. |
| 34 | Description all as per item Ser No. 30.00 here in before but suitable for DG set of capacity 30 to 63 KVA |
| 35 | Supply and fix nozzle suitable for 1010 KVA DG set of existing make and model including taking out old UNSV nozzles Make:-Greaves/Kirloskar/Cummins DG set complete all as directed by Engr-in-Charge. |
| 36 | Description all as per item Ser No. 32.00 here in before but suitable for DG set of capacity 63 to 160 KVA |
| 37 | S&F in replacement oil feed pump with assembly of existing make and model suitable for DG set of capacity 63 KVA to 1010 KVA |
| 38 | S&F in replacement fuel pump with assembly of existing make and model suitable for DG set of capacity 63 KVA to 1010 KVA |
| 39 | S&F in replacement Self Starter 24 volt suitable for DG Set of capacity 160/125 KVA of existing make and model complete all as specified and directed. Make : Lukas or equivalent |
| 40 | S&F in replacement Self Starter 12 volt suitable for DG Set of capacity 63/82.5 KVA of existing make and model complete all as specified and directed. Make : Lukas or equivalent |
| 41 | M&L Calibration of electronic panel of 82.5 KVA Kirloskar DG set with Laptop and fixing all fault including replacement of US relays/wiring as per requirement by cummins Engineer complete all as specified and directed. |
| 42 | M&L Calibration of electronic panel of 30/63 KVA Kirloskar DG set with Laptop and fixing all fault including replacement of US relays/wiring as per requirement by Cummins Engineer complete all as specified and directed. |
| 43 | M&L for repair and cleaning of exhaust silencer of DG Set of capacity 1010 KVA including cutting and welding as per requirement complete all as specified and directed by Engr-in-Charge. |
| 44 | M&L for repair and cleaning of exhaust silencer of DG Set of capacity 160/1225/82.5 KVA including cutting and welding as per requirement complete all as specified and directed by Engr-in-Charge. |
| 45 | Supply & fixing in replacement of Oil sensor suitable for DG set of capacity of DG Sets 63 to 1010 KVA complete all as specified and directed by Engr-in-Charge. |
| 46 | Supply & fixing in replacement of Water/Coolent sensor suitable for DG Sets 63 to 1010 KVA complete all as specified and directed by Engr-in-Charge. |
| 47 | M&L for Calibration of FIP of DG set of capacity 1010 KVA including supply & fixing in replacement plunger, DV, governor wet O-Ring, Pin roll, barrel, Pin ball bearing spring, washer and testing for following capacity of DG Set complete all as specified and directed by Engr in Charge. |
| 48 | Description all as per item Ser No. 44.00 here in before but DG set of capcity 63 to 160 KVA |
| 49 | Supply and Replacement of Thermostate valve suitable for DG Sets of capacity 63 to 1010 KVA complete all as specified and directed by Engr-in-Charge. |
| 50 | M&L for Strip opening of alternator 160/125 KVA DG set , removing rotor from the stator and rewinding to CT coils complete with super enameled copper winding wire of appropriate size including insulating material and replacing the following parts of the alternator.Note: Re-assembling all the component of the alternator and mounting the same on the existing foundation including welding of alternator foundation plate by electric arc welding ,aligning the alternator with engine and testing on full load as specified in particular specification and as directed by Engr-in-Charge. |
| 51 | Description all as per item Ser No. 47.00 here in before but DG set of capacity 82.5/125 KVA |
| 52 | S&F in replacement Control Card (PCB) of existing make and model suitable for DG set of capacity 125/82.5 KVA Make : Kirloskar |
| 53 | S&F in replacement Alternator (Battery Charger) suitable for DG Set of capacity 63/82.5/125 KVA of existing make and Modal complete all as specified and directed. |
| 54 | Draining all the U/S E Oil from the DG Sets Supply and filling the 20 W 40 E oil all as specified and as directed by Engr-in-charge.Make Servo, HP or any approved Make. |
| 55 | S&F in replacement hoses of DG set of capacity 1010 KVA Make : kirloskar/CG of existing size complete all as specified and directed by Engr-in-charge. |
| 56 | S&F in replacement hoses of DG set of capacity 63/82.5/125/160 KVA Make : kirloskar/CG of existing size complete all as specified and directed by Engr-in-charge. |
| 57 | M&L Cleaning of radiator for following capacity DG sets of capacity 63 to 160 KVA by using anti scalent chemical and radiator cleaning solution (Ready to Wash) by pressure pump and brush and re-assembling after painting of the same complete all as directed. |
| 58 | Supply & fixing in replacement of DC wiring of Control panel and DG set of capacity 63 to 125 KVA , complete all as specified and directed by Engr-in-Charge. |
| 59 | S& F In replacement FIP for DG set of Capacity 125/82.5 KVA Make : Kirloskar /cummins of existing make and model as directed by Engr-in-charge |
| 60 | Supply and fix in repair off load change over switch 415 volt 50 Hz conform to IS-13947-3 with enclosure and side handle of cap 63 Amp four pole including taking down old switch Make Havells /C&S/Indoasian |
| 61 | Supply and fix in repair On load change over switch 415 volt 50 Hz confirm to IS-13947-3 with enclosure and side handle of cap 200 Amp four pole including taking down old switch Make Havells /C&S/Indoasian |
| 62 | Supply and fix in repiar On load change over switch 415 volt 50 Hz conform to IS-13947-3 with enclosure and side handle of cap 400 Amp four pole including taking down old switch Make Havells /C&S/Indoasian |
| 63 | Supply and fix in repair On load change over switch 415 volt 50 Hz conform to IS-13947-3 with enclosure and side handle of cap 630 Amp four pole including taking down old switch Make Havells /C&S/Indoasian |
| 64 | Supply and fix in repair On load change over switch 415 volt 50 Hz conform to IS-13947-3 with enclosure and side handle of cap 100 Amp four pole including taking down old switch Make Havells /C&S/Indoasian |
| 65 | Dismantlig/disconnecting the defected Fuel valve of 1010 KVA DG Set supply and fixing the same complete all as specified and directed by Engr-in-charge. Make -Cummins. |
| 66 | Dismantlig/disconnecting/opppening the defected heads of the DG Set 1010 KVA shifting the heads of the DG Sets to Autherised work shop grinding polishing complete with connected items like head valve guide valve, Head Gasket etc reqd while repairing the head of the DG SET refixing the same complete all as directed by Engr-in-charge. |
| 67 | Description all as per item Ser No. 63.00 here in before but DG set of capacity 100/125 KVA DG Set |
| 68 | Calibration of PT pumps, replacement of PT pump kit, gasket set, washers, nuts,plungers,delivery valves, oil pump , O ring and set the oil pressure with testing suitable for 160 KVA DG set complete all as directed by Engr-in-Charge. Make-Cummins . |
| 69 | Calibration of PT pumps, replacement of PT pump kit, gasket set, washers, nuts,plungers,delivery valves, oil pump , O ring and set the oil pressure with testing suitable for 200/250/160 KVA DG set complete all as directed by Engr-in-Charge. Make-Kirloskar.. |
| 70 | Supply & Fixing actuator fuel controller 1010 KVA Make- Cummins |
| 71 | Dismantling/ disconnecting Muffler from 1010 KVA DG set supply and fixing the same as specified and as directed by Engr-in-charge. Make cummins |
| 72 | Dismantling/ disconnecting Muffler from 200 KVA DG at power house set supply and fixing the same as specified and as directed by Engr-in-charge. Make Kirloskar |
| 73 | M&L for dismantling and opening Head of DG Set of capacity 125/160/82.5 KVA and replacement of all unserviceable parts and Head Gasket including necessary lathe work as per requirement complete all as specified and directed. |
| 74 | S&F in Replacement of radiator (Engine Cool) with complete accessories, which is suitable for 125 KVA DG SET as Specified and directed by Engr In charge. |
| 75 | S&F in Replacement of radiator (Engine Cool) with complete accessories, which is suitable for 160 KVA DG SET complete all as specified and directed. |
| 76 | S&F in Replacement of radiator (Engine Cool) with complete accessories, which is suitable for 200 KVA DG SET complete all as specified and directed. |
| 77 | Supply and fix in replacement Speed governor suitable for DG Set of capacity 125/160/200 KVA of existing make and model complete all as specified and directed. |
| 78 | Shifting of DG SET at any Place in KARU, contractor will be fully Responsble arrange vehicle,Hydra/JCB/ Man Power and accessories which is required for shifting complete all as specified and directed by Engr-in-Charge. |
| 79 | Shifting of DG SET at any Place with in 50 KM, contractor will be fully Responsble arrange vehicle,Hydra/JCB/ Man Power and accessories which is required for shifting complete all as specified and directed by Engr-in-Charge. |
| 80 | Shifting of DG SET at any Place with in Above 50 KM to 130 KM, contractor will be fully Responsble arrange vehicle,Hydra/JCB/ Man Power and accessories which is required for shifting complete all as specified and directedby Engr-in-Charge. |
| 81 | M&L for Strip opening of alternator 1010 KVA DG set , removing rotor from the stator and rewinding to CT coils complete with super enameled copper winding wire of appropriate size including insulating material and replacing the following parts of the alternator.Note: Re-assembling all the component of the alternator and mounting the same on the existing foundation including welding of alternator foundation plate by electric arc welding ,aligning the alternator with engine and testing on full load as specified in particular specification and as directed by Engr-in-Charge. Please Enable Macros to View BoQ information |