| 1 | Comprehensive maintenance of LT panel boards, indoor/outdoor typr after isolating the panel board from electric supply, opening all cover/doors, cleaning of all joints/contact points by using CRC, dismantling and taking out old unserviceable spares of Panel board of any type and shape and fixing of new parts complete including tightening of all existing connections/screws/ nuts & bolts etc all as specified and directed.Note : Defective sapre parts required to be replaced will be measured and paid seperately as per relevent items as follows |
| 2 | Comprehensive maintenance of APFC panel boards, indoor/outdoor typr after isolating the panel board from electric supply, opening all cover/doors, cleaning of all joints/contact points by using CRC, dismantling and taking out old unserviceable spares of Panel board of any type and shape and fixing of new parts complete including tightening of all existing connections/screws/ nuts & bolts etc all as specified and directed.Note : Defective sapre parts required to be replaced will be measured and paid seperately as per relevent items as follows |
| 3 | ( a )3Ph LED Ammeter |
| 4 | ( b ) 3Ph LED Voltmeter |
| 5 | (c) CT up to 300/5 of class/burden 1.0/5 VA |
| 6 | (d) LED Indicator Lamp in three colours RYB ( L&T) or equivalent |
| 7 | (e) Replacement of hinges, locking arrangements of each panel board by cutting/ welding etc all as specified and as directed |
| 8 | (f) Fabrication work of LT Panel with 3.00 mm thick MS Sheet (Outer cover), including cutting, welding, moulding all as directed by Engineer-in-charge |
| 9 | (g) Fabrication work of LT Panel with 2.00 mm thick MS Sheet (Inner sheets), including cutting, welding, moulding all as directed by Engineer-in-charge |
| 10 | (h) Aluminium busbar as per existing rating/size and colour coding |
| 11 | Supply only power factor correction capacitor cylindrical type 1 KVAR |
| 12 | Supply only power factor correction capacitor cylindrical type 2 KVAR |
| 13 | Supply onlypower factor correction capacitor cylindrical type 3 KVAR |
| 14 | Supply only power factor correction capacitor cylindrical type 5 KVAR |
| 15 | Supply only power factor correction capacitor cylindrical type 7.5 KVAR |
| 16 | Supply only power factor correction capacitor cylindrical type 10 KVAR |
| 17 | Supply only power factor correction capacitor cylindrical type 15 KVAR |
| 18 | Supply only power factor correction capacitor cylindrical type 20 KVAR |
| 19 | Supply only power factor correction capacitor cylindrical type 25 KVAR |
| 20 | Supply onlypower factor correction capacitor box type type 1 KVAR |
| 21 | Supply onlypower factor correction capacitor box type 2 KVAR |
| 22 | Supply only power factor correction capacitor box type 3 KVAR |
| 23 | Supply only power factor correction capacitor box type 5 KVAR |
| 24 | Supply only power factor correction capacitor box type 7.5 KVAR |
| 25 | Supply only power factor correction capacitor box type 10 KVAR |
| 26 | Supply only power factor correction capacitor box type 15 KVAR |
| 27 | Supply only power factor correction capacitor box type 20 KVAR |
| 28 | Supply only power factor correction capacitor box type 25 KVAR |
| 29 | Material and labour for onload change over switch for 125 Amp, 4 pole with all arrangements for fixing including taking out old UNSV on load change over switch all as directed. |
| 30 | All as per item No 29 above but for 160 Amp 4 pole |
| 31 | All as per item No 29 above but for 250 Amp, 4 pole |
| 32 | All as per item No 29 above but for 400 Amp, 4 pole |
| 33 | All as per item No 29 above but for 630 Amp, 4 pole |
| 34 | Labour for fixing MCCB/MCB 63 Amps with Thermal Magnetic Protection Unit including dismentling of old MCCB complete all as specified and directed. |
| 35 | Labour for fixing MCCB 100 Amps 35 KA, 4 Pole with Thermal Magnetic including dismentling of old MCCB complete all as specified and directed. |
| 36 | Labour for fixing MCCB 125 Amps 16 KA, 4 Pole with Thermal Magnetic setting including dismentling of old one complete all as specified and directed. |
| 37 | Labour for fixing MCCB 160 Amps 35 KA, 4 Pole with Thermal Magnetic setting including dismantling of old one complete all as specified and directed. |
| 38 | Labour for fixing MCCB 250/200 Amps 36 KA, 4 Pole with Thermal Magnetic setting including dismantling of old one complete all as specified and directed. |
| 39 | Labour for fixing MCCB 320/400 Amp 4 Pole 36 KA with Thermal Magnetic setting including dismantling of old one complete all as specified and directed. |
| 40 | Labour for fixing MCB TPN 63 amps with enclosure in existing panel with incoming and outgoing connection complete all as directed. |
| 41 | Labour for fixing MCB TPN 32 amps with enclosure in existing panel with incoming and outgoing connection complete all as directed. |
| 42 | Supply and fix thermoplastic cable junction boxes IP 55/IP 65 with metric knockout for cable entry including connector of size 295x255x120 mm on pole with MS clamps, nut bolts, washers and glands suitable for 10 to 25 sq mm 04 core cable incl dismantling and taking out old unserviceable cable junction boxes all as specified and directed . Make Sintex catpart No GSJB 2520 or equivalent in Hensel/Neptune. |
| 43 | Material and labour for roughing old painting from the LT panels by paint removers, cleaning with scrapes and preparing the surface and applying two coats Painting complete with synthetic enameled paint of existing colour and writing incoming and outgoing feeder/area with stencil complete all as directed. |
| 44 | Material & Labour for Cement concrete in foundation, filling and mass concrete type B2 1:2:4 (40mm graded aggregate). Not exceeding 15 CM in deapth for plinth protaction for path including dismentling of old surface. |
| 45 | Material and labour for PCC 1:2:4 for coping of existing LT pole of size 45X45X30cm with 20mm graded aggregate type B-1 including dismantling of old broken coping complete and also including finishing work with plaster 15 mm thick CM (1:4) and necessary cleaning of surronding Pole of 1 Mtr distance all as directed by Engineer-in-Charge |
| 46 | Cutting / trimming of tree branches which are touching of street light/ peremeter pole and disposal of timber complete all as directed. |
| 47 | Taking out existing LT cable of sizes up to 95 Sqmm 2 to 4 core from duct/wall/floor/trenches and re-laying the same serviceable cable after fault rectification in existing position with supply and fixing connecting materials such as thimbles, lugs, nuts, bolts and washers as required at site all as specified and directed. |
| 48 | Taking out existing LT cable of sizes from 120Sqmm to 300 Sqmm 2 to 4 core from duct/wall/floor/trenches and re-laying the same serviceable cable after fault rectification in existing position with supply and fixing connecting materials such as thimbles, lugs, nuts, bolts and washers as required at site all as specified and directed. |
| 49 | Labour only Laying the cable of sizes up to 95 Sqmm 2 to 4 core from duct/wall/floor/trenches with supply and fixing connecting materials such as thimbles, lugs, nuts, bolts and washers as required at site all as specified and directed. |
| 50 | Labour only Laying the cable of sizes from 120 Sqmm to 300 Sqmm 2 to 4 core from duct/wall/floor/trenches with supply and fixing connecting materials such as thimbles, lugs, nuts, bolts and washers as required at site all as specified and directed. |
| 51 | Material and labour for LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 10 sq mm 2 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete after detection of fault all as specified and directed. |
| 52 | All as per item No 51 above but cross sectional area 16 sq mm 4 core |
| 53 | All as per item No 51 above but cross sectional area 25 sq mm 3.5 core |
| 54 | All as per item No 51 above but cross sectional area 35 sq mm 3.5 core |
| 55 | All as per item No 51 above but cross sectional area 50 sq mm 3.5 core |
| 56 | All as per item No 51 above but cross sectional area 120 sq mm 3.5 |
| 57 | All as per item No 51 above but cross sectional area 240 sq mm 3.5 core |
| 58 | Material and labour Aluminium lugs for upto 25 Sqmm E-bolt hole 8.4 to 13 upto 4 core |
| 59 | Material and labour Aluminium lugs for 35 Sqmm E-bolt hole 8.4 to 10.5 upto 4 core |
| 60 | Material and labour Aluminium lugs for 50 Sqmm E-bolt hole 8.4 to 13 upto 4 core |
| 61 | Material and labour Aluminium lugs for 70 Sqmm E-bolt hole 8.4 to 13 upto 4 core |
| 62 | Material and labour Aluminium lugs for 95 Sqmm E-bolt hole 10.5 to 17 upto 4 core |
| 63 | Material and labour Aluminium lugs for 120 Sqmm E-bolt hole 10.5 to 17 upto 4 core |
| 64 | Material and labour Aluminium lugs for 150 Sqmm E-bolt hole 10.5 to 17 upto 4 core |
| 65 | Material and labour Aluminium lugs for 185 Sqmm E-bolt hole 10.5 to 17 upto 4 core |
| 66 | Material and labour Aluminium lugs for 240 Sqmm E-bolt hole 13 to 17 upto 4 core |
| 67 | Material and labour Aluminium lugs for 300 Sqmm E-bolt hole 17 to 20.3 upto 4 core |
| 68 | Material and labour Copper lugs for upto 25 Sqmm E-bolt hole 8.4 to 13 upto 4 core |
| 69 | Material and labour copper sector connector upto 25 Sqmm upto 4 core |
| 70 | Material and labour Aluminium sector connector barrel type upto 25 Sqmm upto 4 core |
| 71 | Material and labour Aluminium sector connector barrel type upto 35 Sqmm upto 4 core |
| 72 | Material and labour Aluminium sector connector barrel type upto 50 Sqmm upto 4 core |
| 73 | Material and labour Aluminium sector connector barrel type upto 70 Sqmm upto 4 core |
| 74 | Material and labour Aluminium sector connector barrel type upto 95 Sqmm upto 4 core |
| 75 | Material and labour Aluminium sector connector barrel type upto 120 Sqmm upto 4 core |
| 76 | Material and labour Aluminium sector connector barrel type upto 150 Sqmm upto 4 core |
| 77 | Material and labour Aluminium sector connector barrel type upto 240 Sqmm upto 4 core |
| 78 | Material and labour Aluminium sector connector barrel type upto 300 Sqmm upto 4 core |
| 79 | Material and labour for Straight through joint kit Heat shrinkable type suitable for 1.1 KV XLPE under ground cable of size 6 sqmm to 16 Sqmm 3.5 core all as directed. |
| 80 | All as per item No 79 above but of size 25 Sqmm to 50 sqmm 3.5 core. |
| 81 | All as per item No 79 above but of size 70-120 sqmm 3.5 core. |
| 82 | All as per item No 79 above but of size 150-185 sqmm 3.5 core . |
| 83 | All as per item No 79 above but of size 240 to 300 sqmm 3.5 core. |
| 84 | Surface excavation n.exc 30 cm deep and averaging 15 cm deep and getting out hard/dense soil including cleaning away all grass vegetation saplings, brush wood under grouting, roots & tree and not exceeding 30 cm girth and removing rubbish to a distance of 50 mtr outside the periphery of area as directed |
| 85 | Excavation in trenches in hard/dense soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of cables and getting out of excavated material complete all as specified and directed. |
| 86 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed. |
| 87 | Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed. |
| 88 | Material and labour for cutting of PCC/Hard standing/WBM road not exceeding 20 cm in width not exceeding 30 cm in depth for passing of LT cable and making good of disturbed surface to match with the existing surfaces by using old and new material i.e bitumen/PCC (1:3:6) type C-1 complete all as specified and directed . |
| 89 | Material and labour for DWC pipe of 50 mm dia for cable protection complete all as specified and as directed. |
| 90 | All as per item No 89 above but 75 mm dia. |
| 91 | Supply and laying in trenches/Floor or fixed to Pole/Wall GI pipe light grade with fitting of size 100 mm bore for protection of cable complete all as specified and directed by the Engineer-in-Charge. |
| 92 | All as per item No 92 above but 40 mm bore |
| 93 | All as per item No 92 above but 20 mm bore |
| 94 | Material and labour for PCC cable route indicator in mix of 1:2:4 type B1of size 450x200x100 mm with ovel shapeand writing the letter LT cable with synthtic ennamel paint over a coat of yellow paint and embedded with PCC foundation type D2 1:4:8 of size minimum 250mm deapth including necessary earth work complete all as specified and directed. |
| 95 | Dismantling/Taking down and Re-fixing/erecting of Old steel tubular swaged poles any type with accessories/fittings at other location as directed including necessary excavation, removal of soil, refilling of soil, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate for foundation of pole and coping with PCC (1:2:4) type B-1 using 20 mm graded stone aggregate all as per SSR part I complete all as specified and directed. |
| 96 | Dismantling/Taking down and erecting of new steel tubular swaged 9 m poles with accessories/fittings at other location as directed including necessary excavation, removal of soil, refilling of soil, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate for foundation of pole and coping with PCC (1:2:4) type B-1 using 20 mm graded stone aggregate all as per SSR part I complete all as specified and directed. |
| 97 | Material and labour for preparing surfaces of LT/HT electric poles of any type size including street light brackets, bracket clamps, cable protection pipe, terminal box, stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of aluminium paint completely including painting strips on poles with one coats of sky blue and white synthetic enamel paint complete all as specified and as directed by Engineer-in-Charge. |
| 98 | Taking out old UNSV earthing and Material and labour for new earthing complete with galvanised steel plate earth electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25 meter below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to GI strip 25X4mm at two points by means of bolts and nut, check nut and washers including charcoal dust, common salt, necessary excavation in hard/dense soil, returning filling in and removal of surplus soil to a distance up to 50metres, PCC pit in 1:3:6 type CI (using 20mm grade stone aggregate) RCC 1:2:4 type B-1 (using 20mm grade stone aggregate ) 50mm thick pit cover, reinforced with 8mm dia TMT bars 75mm c/c, both ways MS handle 12mm dia, GI funnel, wire mesh and GI watering pipe of 20mm bore GI (light grade) and earth lead protection pipe 40mm bore (light grade) all as specified, directed and shown in electrical plate No 3 of SSR Part-I including testing complete. Note : GI strip and protection pipes 40 mm GI light grade upto 7.5 metre shall deemed to be included in unit rate and beyond that the same will be measured separately. |
| 99 | Material and labour for Earth continuty conductor or main earthing lead as 25x4 mm GI strip fixed to wall on batten or recess or chasses or burried in ground or drawn in conduit /pipe or fixed to pole or any other situation for loop earthing etc all as specified and directed. Please Enable Macros to View BoQ information |
| 100 | Material and labour for Earth continuty conductor or main earthing lead as 25x4 mm GI strip fixed to wall on batten or recess or chasses or burried in ground or drawn in conduit /pipe or fixed to pole or any other situation for loop earthing etc all as specified and directed. Please Enable Macros to View BoQ information |