Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | GRAND TOTAL |
| 2 | Supply |
| 3 | Erection |
| 4 | 2.0 33 kV Overhead Line |
| 5 | Supports for 33 kV overhead line as per technical specification, approved drawings and scope of work |
| 6 | 13 M long WPB 160x160x30.44 kG/Meter with Grade E300 |
| 7 | PCC Pole: 9M long |
| 8 | 12.8 mtr long 52 kg Rail pole |
| 9 | Pre-fabricated galvanised steel items like Top Channel ,Cross Bracing, Horizontal Bracing , Guarding Channel, extension channel, Clamps by M.S. Channel, M.S. Angle, M.S. Flat etc. of proper size. |
| 10 | Pre-fabricated galvanised 33 kV \\"V\\" Brackets for 13 M long WPB |
| 11 | Pre-fabricated galvanised 33 kV Top Adaptor for 13 M long WPB |
| 12 | Pre-fabricated galvanised 33 kV \\"V\\" Brackets for 9M long PCC Pole |
| 13 | Pre-fabricated galvanised 33 kV Top Adaptor for 9M long PCC Pole |
| 14 | Stay arrangement as per technical specification, approved drawings and scope of work |
| 15 | GI Stay Set HT (1830x20mm)WRKG LD-7900KG |
| 16 | HT Porcelain Guy Insulator |
| 17 | GI Stay Wire 7/4 mm (8SWG) |
| 18 | Insulators & hardwares as per technical specification, approved drawings and scope of work |
| 19 | 33 kV Polymer composite 70 kN Disc insulator |
| 20 | Single Tension Hardware Fittings for ACSR Wolf (150 sq. mm) Conductor. |
| 21 | Composite Hardware Fittings for ACSR Dog (100 sq. mm) Conductor. |
| 22 | 33 kV Polymer composite with fittings Pin Insulators (10KN -900 mm creepage distance) |
| 23 | Earthing arrangement as per technical specification, approved drawings and scope of work |
| 24 | GI Earth Spike (1853x20) mm |
| 25 | GI Wire 5 mm (6 SWG) |
| 26 | Conductors of following sizes with jointing sleevs, binding materials, PG clamps, bi-metalic clamps, Packing Piece, Turn Buckle, hardwares etc. for overhead lines & jumpers as required as per technical specification, approved drawings and scope of work |
| 27 | ACSR Wolf (150 sq. mm) Conductor |
| 28 | ACSR Dog (100 sq. mm) Conductor |
| 29 | ACSR Squirrel (20 sq. mm.) Conductor New 33 kV Underground Line |
| 30 | Supports for 33 kV Under Ground System as per Technical specifications, approved drawings and scope of the work. |
| 31 | 33 kV Grade XLPE Cable 3C X 400 Sq. mm |
| 32 | 33 kV Outdoor Type Heat Shrinkable Termination Joint for 3C X 400 Sq. mm XLPE Cable |
| 33 | 33 kV Stright Through Heat Shrinkable joint for 3C X 400 Sq. mm XLPE Cable |
| 34 | Lightening Arrestor 42 kV, 1 Ph. 10 kA Porcelain Housed Gapless Type for 33 kV system, with mounting platform, jumpering from Bus Bar, hardware etc. as per technical specification, approved drawing and scope of work. (3 nos. LA per set) New 11 kV Overhead Line |
| 35 | Supports for 11 kV overhead line as per technical specification, approved drawings and scope of work. |
| 36 | 13 M long WPB 160x160x30.44 kG/Meter with Grade E300 |
| 37 | PCC Pole: 9M long |
| 38 | Pre-fabricated galvanised steel items like Top Channel ,Cross Bracing, Horizontal Bracing , Guarding Channel, extension channel, Clamps by M.S. Channel, M.S. Angle, M.S. Flat etc. of proper size. |
| 39 | Pre-fabricated galvanised 11 kV \\"V\\" Brackets for 13 M long WPB |
| 40 | Pre-fabricated galvanised 11 kV Top Adaptor for 13 M long WPB |
| 41 | Pre-fabricated galvanised 11 kV \\"V\\" Brackets for 9M long PCC Pole |
| 42 | Pre-fabricated galvanised 11 kV Top Adaptor for 9M long PCC Pole |
| 43 | Insulators & hardwares as per technical specification, approved drawings and scope of work |
| 44 | 11 kV Polymer composite with fittings Pin Insulators (5KN -320 mm creepage distance) |
| 45 | 11 kV Polymer composite 45 kN Disc insulator |
| 46 | Composite Hardware Fittings for ACSR Rabbit (50 sq. mm) Conductor. |
| 47 | Stay arrangement as per technical specification, approved drawings and scope of work |
| 48 | GI Stay Set HT (1830x20mm)WRKG LD-7900KG |
| 49 | HT Porcelain Guy Insulator |
| 50 | GI Stay Wire 7/3.15 mm (10 SWG) |
| 51 | Earthing arrangement as per technical specification, approved drawings and scope of work |
| 52 | GI Earth Spike (1853x20) mm |
| 53 | GI Wire 5 mm (6 SWG) |
| 54 | Conductors of following sizes with jointing sleevs, binding materials, PG clamps, bi-metalic clamps, Packing Piece, Turn Buckle, hardwares etc. for overhead lines & jumpers as required as per technical specification, approved drawings and scope of work |
| 55 | ACSR Rabbit (50 sq. mm.) Conductor |
| 56 | ACSR Squirrel (20 sq. mm.) Conductor |
| 57 | 12kV, 400A, Vertical Mounting type tripple pole, Gang Operated Isolator (TPGO) along with support insulators, Base Channel, down pipe, Arching Horns etc. and all accessories as per technical specifications, approved drawings and scope of works. |
| 58 | 12kV, 400A, Vertical Mounting type tripple pole, Gang Operated Isolator (TPGO) along with all accessories. New 11 kV Underground Line |
| 59 | Supports for 11 kV Underground System as per Technical specifications, approved drawings and scope of the work. |
| 60 | Cable (XLPE 11 kV) 3C x 300 sq. mm., armoured, aluminium conductor |
| 61 | 11 kV Heat Shrinakable Outdoor Termination Joint. for 3 x 300 sq. mm. XLPE Cable |
| 62 | 11 kV Heat Shrinakable Straight Through Joint for 3 x 300 sq. mm. XLPE Cable |
| 63 | 12kV, 10 KA, 1-ph Station Class Lightening Arrester with mounting platform, hardware etc as per technical specification, approved drawing and scope of work. (3 nos. LA per set) Construction of 33/11 kV Substation |
| 64 | 33/11 kV Sub Station as per Technical specifications, approved drawings and scope of the work. |
| 65 | 10 MVA 33/11 kV Power Transformer |
| 66 | RTCC panel for 10 MVA Power Transformer |
| 67 | 100 kVA 33/0.415 kV 3 Phase ONAN Outdoor type Station Service Transformer. |
| 68 | Cable supporting G.I Structure with necessary arrangment of Fabricated G.I for fixing of U.G Cable of Station Service Transformer. |
| 69 | Cable supporting G.I Structure with necessary arrangment of Fabricated G.I for fixing of U.G Cable & LA for PTR LV side / Bus. |
| 70 | 33kV, 1250A, 3-ph, SCADA compatible Outdoor type Vacuum Circuit breaker, 33KV, 1-Phase Outdoor type current trasformers with junction box, supporting angle ( The CT secondary terminals shall be broughtout in a weatherproof secondary terminal box, 1 no. junction box for 3 nos CT) jumpers, earthing, supporting structures, bi-metallic clamps permanent maintenance platform, marshalling box etc required as per technical specifications,approved drawings and scope of works. |
| 71 | 33 kV VCB: 1250 Amps: Outdoor type |
| 72 | 33 kV CT having Ratio 400 - 200/1 - 1A. (For 33 kV I/C or O/G) along with supporting structures and Junction Box for CT with required accossories etc. (3 nos. CT per set) |
| 73 | 33 kV CT having Ratio 200 - 100/1 - 1 - 1A. (For PTR) along with supporting structures and Junction Box for CT with required accossories etc. (3 nos. CT per set) |
| 74 | 33 kV, 3 pole, 1 Phase 33kV/110 volt, single core outdoor type Potential Trasformer along with Junction box and supporting angle, bi-metallic clamps and supporting structure with required accossories etc. complete as per technical specifications,approved drawings and scope of works. |
| 75 | 33 kV PT having Ratio 33 kV/ 110 volt along with supporting structures and Junction Box for PT with required accossories etc. (3 nos. PT per set) |
| 76 | 33 kV SCADA Compatible metal enclosed, indoor, Control Relay panel (30 Volt DC auxiliary supply) consist of Voltmeter, Ammeter, Micoprocessor based relays, provision of TVM energy meter indicating lamps, annunciation windows with annunciation relay, mimic diagram and other components for control, complete, including base mounting channel for CR Panel as per technical specification, approve drawing and scope of work |
| 77 | 33 kV C&R Panel with differential relay SCADA compatible for individual transformer. |
| 78 | 33 kV C&R Panel with directional relay SCADA compatible for feeder control. |
| 79 | 36kV, 400A, 3-ph double break center rotating type (DBCR) isolators along with Support Insulators, Operating Mechanism, Base Channel , down Pipe and all required accessories complete as per technical specifications, approved drawings & scope of works. |
| 80 | 33 kV 400A CR Type Isolator with Earth Switch (High Level) |
| 81 | 33 kV 400A CR Type Isolator without Earth Switch (High Level) |
| 82 | 33 kV 400A CR Type Isolator without Earth Switch (Low Level) |
| 83 | Lightening Arrestor ,Porcelain Housed Gapless Type with mounting platform, jumpering from Bus Bar, hardware etc as per technical specification, approve drawing and scope of work. |
| 84 | Lightening Arrestor 42 kV, 1 Ph. 10 kA Porcelain Housed Gapless Type for 33 kV system, with mounting platform, jumpering from Bus Bar, hardware etc. as per technical specification, approved drawing and scope of work. (3 nos. LA per set) |
| 85 | 12kV, 10 KA, 1-ph Station Class Lightening Arrester with mounting platform, hardware etc as per technical specification, approved drawing and scope of work. (3 nos. LA per set) |
| 86 | Battery, Battery charger, Battery stand, Battery insulators, inter battery wiring, Terminal connectors with all accessories as per technical specification, approve drawing and scope of work |
| 87 | 30V, 100 AH Pb Acid Battery, battery stand, battery insulators, inter battery wiring using 30 sq. mm. 1.1 kV Copper single core multi strand cable, terminal connectors with all Accessories |
| 88 | 30V, 35 Amp. Float-cum-Boost Battery Charger with full wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply (auto manual, float cum boost ,thyristor controlled battery charger) |
| 89 | Cold Rolled Steel sheet enclosed floor mounted Distribution Board with all accessories as per technical specification, approve drawing and scope of work. |
| 90 | Cold Rolled Steel sheet enclosed floor mounted 415 V, AC Distribution Board with all accessories |
| 91 | Cold Rolled Steel sheet enclosed floor mounted 30 V Distribution Board with all accessories. |
| 92 | Conductors for Bus Bar, jumpers, droper, terminations including hardware fittings, Connector, Clamp, Compression Joints etc. as per technical specification, approved drawings and scope of work |
| 93 | ACSR Panther (200 sq. mm) Conductor |
| 94 | ACSR Wolf (150 sq. mm) Conductor |
| 95 | ACSR Dog (100 sq. mm) Conductor |
| 96 | Aluminium Bus Pipe 1.5\\" |
| 97 | Insulators & hardwares as per technical specification, approved drawings and scope of work |
| 98 | 33 kV Polymer composite with fittings Pin Insulators (10KN -900 mm creepage distance) |
| 99 | 11 kV Polymer composite with fittings Pin Insulators (5KN -320 mm creepage distance) |
| 100 | 33 kV Polymer composite 70 kN Disc insulator |
| 101 | Post Insulator 33 kV |
| 102 | Single Tension Hardware Fittings for ACSR Wolf (150 sq. mm) Conductor. |
| 103 | Single Tension Hardware Fittings for ACSR Panther (200 sq. mm) Conductor. |
| 104 | LT power cables for yard lighting and LT power connection to various equipments as per technical specification, approved drawings and scope of work |
| 105 | Cable (PVC 1.1 kV Grade) 4C x 185 sq. mm., armoured, aluminium conductor |
| 106 | Cable (PVC 1.1 kV Grade) 4C x 50 sq. mm., armoured, aluminium conductor |
| 107 | Cable (PVC 1.1 kV Grade) 4C x 25 sq. mm., armoured, aluminium conductor |
| 108 | Cable (PVC 1.1 kV Grade) 4C x 10 sq. mm., armoured, aluminium conductor |
| 109 | Cable (PVC 1.1 kV Grade) 2C x 10 sq. mm., armoured, aluminium conductor |
| 110 | Cable (XLPE 1.1 kV Grade) 4C x 120 sq. mm., armoured, aluminium conductor |
| 111 | LT Control Cable as per technical specification, approved drawings and scope of work |
| 112 | 1.1 KV grade PVC insulated armoured stranded Copper Control Cable: 4C x 2.5 sq. mm. |
| 113 | 1.1 KV grade PVC insulated armoured stranded Copper Control Cable: 8C x 2.5 sq. mm. |
| 114 | 1.1 KV grade PVC insulated armoured stranded Copper Control Cable: 12C x 2.5 sq. mm. |
| 115 | 12 kV, 800A, SCADA compatible, 3 Phase, Shunt Trip, Indoor type, motor operated spring closing vacuum circuit breaker, along with 12 kV single phase 600-400/1-1-1 A(Incomming ) and 200-100/1-1A(Outgoing ) current transformer indoor type with indoor mounting type control and relay panel consisting of Ammeter, Voltmeter, Relay and accessories, control cabling between VCB and indoor control panel and required accessories complete for protection and supply of indoor type potential transformer (11kV/110 V) Three Phase 5 limb type or combination of 3 nos single phase PT housed in a withdrawable carriage shall be dry/rasin cast, drawout type as per technical specification, approved drawing and scope of work. |
| 116 | 12 kV, 800 A, SCADA compatible, 3 Phase, 9 Panel (2 I/C+ 1 B/C + 6 O/G) Shunt Trip VCB |
| 117 | 12 kV, 800 A, SCADA compatible, 3 Phase, 11 Panel (3 I/C+ 2 B/C + 6 O/G) Shunt Trip VCB |
| 118 | 11 kV 3 Phase Aluminium armoured XLPE insulated power cable and termination kit as per technical specification, approved drawings and scope of work |
| 119 | Cable (XLPE 11 kV) 3C x 300 sq. mm., armoured, aluminium conductor |
| 120 | 11 kV Heat Shrinakable Outdoor Termination Joint. for 3 x 300 sq. mm. XLPE Cable |
| 121 | 11 kV Heat Shrinakable Indoor Termination Joint for 3 x 300 sq. mm. XLPE Cable |
| 122 | Sub Station support structures as per technical specification, approved drawings and scope of work. |
| 123 | PCC Pole: 9M long |
| 124 | Pre-fabricated galvanised steel items like Top Channel ,Cross Bracing, Horizontal Bracing , Guarding Channel, extension channel, Clamps by M.S. Channel, M.S. Angle, M.S. Flat etc. of proper size. |
| 125 | Pre-fabricated galvanised steel structure for High level isolator |
| 126 | Pre-fabricated galvanised steel structure for Low level isolator |
| 127 | Pre-fabricated galvanised steel structure forLow level bus support |
| 128 | Shielding arrangement with 13 mtr. Long WPB Pole fitted with earth spike (on the top of the pole), turn buckles etc. as required as per technical specification, approved drawing and scope of work. |
| 129 | 13 M long WPB 160x160x30.44 kG/Meter with Grade E300 |
| 130 | ACSR Rabbit (50 sq. mm.) Conductor |
| 131 | Composite Hardware Fittings for ACSR Rabbit (50 sq. mm) Conductor. |
| 132 | GI Earth Spike (1853x20) mm |
| 133 | 12kV, 400A, Vertical Mounting type tripple pole, Gang Operated Isolator (TPGO) along with support insulators, Base Channel, down pipe, Arching Horns etc. and all accessories as per technical specifications, approved drawings and scope of works. |
| 134 | 12kV, 400A, Vertical Mounting type tripple pole, Gang Operated Isolator (TPGO) along with all accessories. |
| 135 | Stay arrangement as per technical specification, approved drawings and scope of work |
| 136 | GI Stay Set HT (1830x20mm)WRKG LD-7900KG |
| 137 | HT Porcelain Guy Insulator |
| 138 | GI Stay Wire 7/3.15 mm (10 SWG) |
| 139 | Supply of flat of different sizes ( GI flat 75 mm x 8 mm and GI flat 65 mm x 6 mm), GI pipe earth electrode of 40 mm inner dia. 3 mtr. long, bentonite powder and other accessories for earthing arrangement at Switchyard and Control room at new / existing substation as per technical specifications, approved drawings and scope of the work. |
| 140 | Switchyard earthing at new susbstation |
| 141 | Control room earthing at new susbstation |
| 142 | Earthing arrangement for construction of new 33 kV feeder bay at existing Substation |
| 143 | Earthing of 6 nos 11 kV terminal Isolator DP with GI Pipe and GI flat 65 mm X 6 mm |
| 144 | Electrification of switch yard by LED flood light fitted on pole structure and control room roof complete as per technical specifications, approved drawings and Scope of works. |
| 145 | LED flood light complete set 250 watt with all accessorie and fittings of reputed manufacturer. |
| 146 | Furniture as per technical specifications, approved drawings and Scope of works |
| 147 | Steel Almirah (Size: 6'6\\"-3'4\\"-21\\") of any |
| 148 | Wooden table for Office Work with drawers (size 6 ftX3ft) |
| 149 | Arm chair (Revolving) |
| 150 | Normal four leg chair with arm |
| 151 | Wall Clock |
| 152 | Fire Fightning Equipments as per technical specifications, approved drawings and Scope of works |
| 153 | Portable type Dry Chemical Powder (BC)/ABC type (5 kg),IS : 15683:2006 |
| 154 | Portable type Mechanical Foam type (AB) IS:10204 (9 LITER) |
| 155 | Portable wall mounted CO2 Type of 5 kg capacity (squeze grip type) IS : 15683:2006 |
| 156 | Portable type Water (CO) Type (A) IS : 940 Capacity - 9 liter |
| 157 | CO2 Type Trolley Mounted of 22.5 Kg Capacity for Switch Yard. |
| 158 | Sand Buckets with Stand(9 Ltr.) I.S : 2546 ( 1 set = 4 nos. sand filled bucket with steel stand) |
| 159 | Tools & tackles, Safety equipments as per technical specifications, approved drawings and Scope of works |
| 160 | Fibre Glass or Bamboo Ladder (20ft.) |
| 161 | Crimping Tools wretched type suitable for size 6 to 400 aq.mm. |
| 162 | Digital Clip On Ammeter (Tong Tester) 0-600 Amps |
| 163 | Insulation Tester (Megger):1 no. 5000 V & 1 no. 1000 Volt (Electrically as well as manually operated) of Megger /Fluke/Motwane or equivalent make |
| 164 | Insulated Cutting plier 8\\" |
| 165 | Insulated Nose plier 8\\" |
| 166 | Insulated Cutter 6\\"/8\\" |
| 167 | Srew Driver set |
| 168 | Ring Wrench |
| 169 | Pipe Wrench |
| 170 | Torque Wrench |
| 171 | D Spanner |
| 172 | Tester Pen |
| 173 | Wire Cutter Knife |
| 174 | Hacksaw |
| 175 | Steel Measuring Tape (5 M) |
| 176 | Insulation tape ( R , Y , B ) |
| 177 | Allen Key Set |
| 178 | Line Tester |
| 179 | Sleeve Jointing Machine |
| 180 | Test Lamp |
| 181 | Earth resistance meter: Megger/Fluke/Motwane or equivalent make |
| 182 | Electrician tool box – Taparia standard kit |
| 183 | Multi-meter Motwane make Digital type, |
| 184 | Electrical Resistance Hand Gloves conforming IS: 4770 - 33 KV GRADE (TESTED) |
| 185 | 33 KV Grade Electrical Insulating Power Mat 3 mm thick ( IS:15652/2006 ) |
| 186 | Safety Belt with thigh straps confirming IS:2925 with ISI mark (Tested) |
| 187 | Rubber Gum Boot confirming to relevant IS codes of different sizes |
| 188 | 250x200 mm and 2 mm thick M.S. plate with vitreous enamelled white with red letter as per drawing no. RE/LF/36 (Danger Board) |
| 189 | Shock Therapy Chart |
| 190 | ISI marked, Discharge Cum Earthing rod 66 KV rating with discharging multi stranded copper cables & terminals |
| 191 | Safety Helmet made FRP material confirming to IS: 2925 & ISI marked in matt finish with adjustable type superior rexine headband and cotton tape chinstrap. |
| 192 | Manila Rope |
| 193 | Equipped First Aid Box |
| 194 | Chain With Lock |
| 195 | Infrared thermometer |
| 196 | Blue Coloured Safety Vest |
| 197 | Soft Barricading Tapes |
| 198 | 2.0 Erection Testing and Commissioning of 33 kV Overhead Line |
| 199 | Excavation of pole pit and erection of poles by providing and installing Caution Board, Anti-climbing devices (barbed wire) as per approved drawings and specifications and scope of work: |
| 200 | Survey, route alignment & pole spotting of HT Overhead line and preparation & submission of soft and hard copy of GPS survey report. |
| 201 | 13 M long WPB 160x160x30.44 kG/Meter with Grade E300 with cement concrete foundation (1:3:6) , muffing (1:2:4) etc. |
| 202 | PCC Pole: 9M long with refilling by 200 mm average size boulders or/and Brick Ballast mixed with excavated earth(BB:Earth::60:40) etc. |
| 203 | 12.8 M long Rail pole without foundation (for river crossing) |
| 204 | Erection, testing & commissioning of pre-fabricated galvanized steel items like DP top mounting channel, cross bracings , belting Angle , guarding bracket , extension channel, clamps etc. for over head structures with supply of GI nuts, bolts & washers as per technical specification, approved drawings and scope of work. |
| 205 | Erection of Pre-fabricated galvanised 33 kV \\"V\\" Brackets for 13 M long WPB |
| 206 | Erection of Pre-fabricated galvanised 33 kV Top Adaptor for 13 M long WPB |
| 207 | Erection of Pre-fabricated galvanised 33 kV \\"V\\" Brackets for 9M long PCC Pole |
| 208 | Erection of Pre-fabricated galvanised 33 kV Top Adaptor for 9M long PCC Pole |
| 209 | Excavation of stay pit and erection of complete Stay Set with solid GI stay rod, anchor plate providing cement concrete foundation, GI stay wire, Guy Insulator, stay clamp, GI nut & bolts, turn-buckle, etc. as per technical specifications, approved drawings and scope of works. |
| 210 | HT Stay Set complete |
| 211 | Erection, testing and commissioning of 33 kV insulator including their hardware fittings as per technical specification, approved drawings and scope of work. |
| 212 | 33 kV Polymer Composite with fittings Pin Insulator |
| 213 | 33 kV Polymer Composite with fittings Disc Insulator with strain hardware |
| 214 | Earthing arrangement as per Technical specifications, approved drawings and scope of work |
| 215 | Excavation, erection, testing & commissioning of G.I Earthing Spike |
| 216 | Erection of 6 SWG GI wire for earthing and guarding (lacing) by providing GI nut, bolts & washers, turn buckle etc |
| 217 | Erection, laying, hoisting, stringing, sagging, jumpering, binding,testing and commissioning of ACSR Conductor with supply and erection of jointing sleeves, P.G Clamps, helical formed fittings, GI turn buckle, CI packing piece, comression joint etc. as required as per technical specifications, approved drawings and scope of work |
| 218 | ACSR 150 sqmm. Wolf conductor (3 wire) |
| 219 | ACSR 100 sqmm. Dog conductor (3 wire) |
| 220 | ACSR 20 sqmm. Squirrel conductor (2 wire) Erection Testing and Commissioning of 33 kV, 3CX400 sq. mm. Underground Line |
| 221 | Excavation of soil for formation of cable trenches & re-instatement of cable trenches / Micro tunnelling work, Laying of Cable with Bricks, Sands etc. as per approved drawings and specifications and scope of work |
| 222 | Survey, route alignment and preparation & submission of soft and hard copy of GPS survey report. |
| 223 | Excavation of soil for making of trial hole (minimum size 1.1X0.5X1.2 mtr. Depth) including back filling the excavated soil |
| 224 | Excavation of soil for formation of cable trenches & re-instatement of the same |
| 225 | Excavation of soil by Cutting of metalled road / Cement Concrete / Brick Soling etc.for formation of cable trenches& re-instatement of the same |
| 226 | Micro-tunnelling work with Supply & laying of HDPE pipe grade-PE-80, PN-6, 200 mm dia ( as per IS 4984-2016 with latest amendment) |
| 227 | Supply and laying of kiln-burnt 1st class bricks having proper size & shape suitable for cable protective cover |
| 228 | Laying & dressing of 33 kV 3CX400 sq. mm. XLPE Cable with supply and fixing of cable tag and cable marker |
| 229 | Making & Fixing of End Termination joint, Outdoor Type for 33 kV 3CX400 sq. mm. XLPE Cable |
| 230 | Making of Straight Through Type Joint including making of jointing pit of the 33 kV 3CX400 sq. mm. XLPE Cable |
| 231 | Making of Protective Duct for cable Joint complete. |
| 232 | Supply & laying of HDPE pipe grade-PE-80, PN-6, 200 mm dia ( as per IS 4984-2016 with latest amendment) for riser of 33 kV 3CX400 sq. mm. Cable |
| 233 | Erection, testing and Commissioning of 42kV, 1-ph Station Class Lightening Arresters, jumpering from bus bar, earthing connection (3 nos. LA per Set) |
| 234 | Earthing of LA conisting of 1 no 3 mtrs long 50 mm dia medium guage TATA make GI Pipe (Medium) using GI Flat 50 mm x 6 mm (including supply of all materials) by welding Erection Testing and Commissioning of 11 kV Overhead Line |
| 235 | Excavation of pole pit and erection of poles by providing and installing Caution Board, Anti-climbing devices (barbed wire) and pole numbering as per approved drawings and specifications and scope of work: |
| 236 | Survey, route alignment & pole spotting of HT Overhead line and preparation & submission of soft and hard copy of GPS survey report. |
| 237 | 13 M long WPB 160x160x30.44 kG/Meter with Grade E300 with cement concrete foundation (1:3:6) , muffing (1:2:4) etc. |
| 238 | PCC Pole: 9M long with refilling by 200 mm average size boulders or/and Brick Ballast mixed with excavated earth(BB:Earth::60:40) etc. |
| 239 | Erection, testing & commissioning of pre-fabricated galvanized steel items like DP top mounting channel, cross bracings , belting Angle , guarding bracket , extension channel, clamps etc. for over head structures with supply of GI nuts, bolts & washers as per technical specification, approved drawings and scope of work. |
| 240 | Erection of Pre-fabricated galvanised 11 kV \\"V\\" Brackets for 13 M long WPB |
| 241 | Erection of Pre-fabricated galvanised 11 kV Top Adaptor for 13 M long WPB |
| 242 | Erection of Pre-fabricated galvanised 11 kV \\"V\\" Brackets for 9M long PCC Pole |
| 243 | Erection of Pre-fabricated galvanised 11 kV Top Adaptor for 9M long PCC Pole |
| 244 | Erection, testing and commissioning of 11 kV insulator including their hardware fittings as per technical specification, approved drawings and scope of work. |
| 245 | 11 kV Polymer Composite with fittings Pin Insulator |
| 246 | 11 kV Polymer Composite with fittings Disc Insulator with strain hardware |
| 247 | Excavation of stay pit and erection of complete Stay Set with solid GI stay rod, anchor plate providing cement concrete foundation, GI stay wire, Guy Insulator, stay clamp, GI nut & bolts, turn-buckle, etc. as per technical specifications, approved drawings and scope of works. |
| 248 | HT Stay Set complete |
| 249 | Earthing arrangement as per Technical specifications, approved drawings and scope of work |
| 250 | Excavation, erection, testing & commissioning of G.I Earthing Spike |
| 251 | Erection of 6 SWG GI wire for earthing and guarding (lacing) by providing GI nut, bolts & washers, turn buckle etc |
| 252 | Erection, laying, hoisting, stringing, sagging, jumpering, binding,testing and commissioning of ACSR Conductor with supply and erection of jointing sleeves, P.G Clamps, helical formed fittings etc. as required as per technical specifications, approved drawings and scope of work |
| 253 | ACSR 50 sqmm. Rabbit conductor (3 wire) |
| 254 | ACSR 20 sqmm. Squirrel conductor (2 wire) |
| 255 | Erection, Testing and Commissioning of Isolators along with support insulators, Base Channel, down pipe, Arching Horns etc. and all complete accessories as per technical specification, approved drawings and scope of work |
| 256 | 12kV, 400A Vertical Mounting type tripple pole, Gang Operated Isolator (TPGO) Erection Testing and Commissioning of 11 kV, 3CX300 sq. mm. Underground Line |
| 257 | Excavation of soil for formation of cable trenches & re-instatement of cable trenches / Micro tunnelling work, Laying of Cable with Bricks, Sands etc. as per approved drawings and specifications and scope of work |
| 258 | Survey, route alignment and preparation & submission of soft and hard copy of GPS survey report. |
| 259 | Excavation of soil for making of trial hole (minimum size 1.1X0.5X1.2 mtr. Depth) including back filling the excavated soil |
| 260 | Excavation of soil for formation of cable trenches & re-instatement of the same |
| 261 | Excavation of soil by Cutting of metalled road / Cement Concrete / Brick Soling etc.for formation of cable trenches& re-instatement of the same |
| 262 | Micro-tunnelling work with Supply & laying of HDPE pipe grade-PE-80, PN-6, 160 mm dia ( as per IS 4984-2016 with latest amendment) |
| 263 | Supply and laying of kiln-burnt 1st class bricks having proper size & shape suitable for cable protective cover |
| 264 | Laying & dressing of 11 kV 3CX300 sq. mm. XLPE Cable with supply and fixing of cable tag and cable marker |
| 265 | Making & Fixing of End Termination joint, Outdoor Type for 11 kV 3CX300 sq. mm. XLPE Cable |
| 266 | Making of Straight Through Type Joint including making of jointing pit of the 11 kV 3CX300 sq. mm. XLPE Cable |
| 267 | Making of Protective Duct for cable Joint complete. |
| 268 | Supply & laying of HDPE pipe grade-PE-80, PN-6, 160 mm dia ( as per IS 4984-2016 with latest amendment) for riser of 11 kV 3CX300 sq. mm. Cable |
| 269 | Erection, testing and Commissioning of 12kV, 1-ph Station Class Lightening Arresters, jumpering from bus bar, earthing connection (3 nos. LA per Set) |
| 270 | Earthing of LA conisting of 1 no 3 mtrs long 50 mm dia medium guage TATA make GI Pipe (Medium) using GI Flat 50 mm x 6 mm (including supply of all materials) by welding Construction of 33/11 kV Substation |
| 271 | Erection, testing and commissioning of 33/11 kV, 3 ph., 50 Hz, ONAN, Cu. Wound, Outdoor Conventional type Power Transformer fitted with on load Tap Changer, transformer oil, Buchholz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, RTCC Panel, valves on bushing end supported with insulators, Vent explosion plug, control wiring / cabling, cable supporting tray on the body, transformer wheels, bushing etc. as per Technical Specification, approved Drawing and Scope of works. |
| 272 | 10 MVA, 33/11 kV Power transformer |
| 273 | RTCC Panel for 10 MVA, 33/11 kV Power transformer |
| 274 | Erection, Testing & commissioning of 100 KVA 33/0.415 KV, 3 ph., 50 Hz, ONAN, Cu. wound CRGO core outdoor type Station service Transformers as per Technical Specification, approved drawing and Scope of work. |
| 275 | Erection, testing & commissioning of Pre-fabricated galvanized Cable supporting G.I Structure with necessary arrangment of Febricated G.I for fixing of U.G Cable for Station Service Transformer as per Technical Specification, approved drawing and Scope of work. |
| 276 | Erection, testing & commissioning of Pre-fabricated galvanized Cable supporting G.I Structure with necessary arrangment of Febricated G.I for fixing of U.G Cable & LA for PTR LV sideas per Technical Specification, approved drawing and Scope of work. |
| 277 | Erection, testing and commissioning of 33KV, 1250A, 3-ph, SCADA compatible Outdoor type Vacuum Circuit breaker, 33KV, 1-Phase, outdoor type Current Transformers with junction box, supporting angle ( The CT secondary terminals shall be brought out in a weather proof secondary terminal box, 1 no. Junction Box for 3 nos. CT), Jumpers, earthing, supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box etc. required as per technical specifications, approved drawings and scope of work. |
| 278 | 33KV, 1250A Outdoor type Vacuum Circuit breaker |
| 279 | CT having Ratio (400-200/1-1A) (For 33KV I/C or O/G) along with Supporting Structures & Junction Box etc.(3Nos. CT per Set) |
| 280 | CT having Ratio (200-100/1-1-1A) (For 6.3/10 MVA PTR) along with Supporting Structures & Junction Box etc.(3 nos. CT per set) |
| 281 | Erection, testing and Commissioning of 33 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core 3 nos. outdoor type Potential Transformer along with junction box (1 no junction box for 3 no of 1-phase PTs), Supporting Structures , bi-metallic clamp along with required accessories complete as per technical specifications, approved drawings and scope of works. |
| 282 | 33 kV, 3-pole, 1-Phase, 33kV/110 volt, outdoor type Potential Transformer along with Supporting Structures & Junction Box etc.(3 nos. PT per set) |
| 283 | Erection, testing and commissioning of 33KV SCADA compatible metal enclosed Indoor, Control & Relay panel on base mounting 100X50 MS channel with grouting as per technical specification, approved drawings and scope of work. |
| 284 | 33 kV C&R Panel, SCADA Compatible for individual control of power transformers with differential relay |
| 285 | 33 kV C&R Panel, SCADA Compatible for feeder control with directional relay |
| 286 | Erection, testing and commissioning of 36kV, 400A, 3-ph double break centre rotating type (DBCR), Gang Operated, isolator along with support Insulators, Operating Mechanism, Base Channel down Pipe and all required accessories complete as per as per technical specification, approved drawings and scope of work. |
| 287 | 33 kV 400A CR Type Isolator with Earth Switch (High Level) |
| 288 | 33 kV 400A CR Type Isolator without Earth Switch (High Level) |
| 289 | 33 kV 400A CR Type Isolator without Earth Switch (Low Level) |
| 290 | Erection, testing and Commissioning of Lightening Arresters, jumpering from bus bar, earthing connection as required, as per approved drawings, technical specifications and scope of the work. |
| 291 | Erection, testing and Commissioning of 42kV, 1-ph Station Class Lightening Arresters, jumpering from bus bar, earthing connection (3 nos. LA per Set) |
| 292 | Erection, testing and Commissioning of 12kV, 1-ph Station Class Lightening Arresters, jumpering from bus bar, earthing connection (3 nos. LA per Set) |
| 293 | Erection, cabling, interconnection cabling, testing, initial charging, and commissioning of Battery on battery stand, Battery Charger, battery insulators, inter-battery wiring using 30 sqmm. copper single core multi strand cable, terminal connectors & all other accessories and connectors as per as per approved drawings , technical specifications and scope of the work |
| 294 | 30V, 100 AH Pb Acid Battery, battery stand, battery insulators, inter battery wiring using 30 sq. mm. 1.1 kV Copper single core multi strand cable, terminal connectors with all Accessories |
| 295 | 30V, 35 Amp. Float-cum-Boost Battery Charger with full wave rectification for 230 V, 1 phase, 50 Hz AC Input Supply (auto manual, float cum boost ,thyristor controlled battery charger) |
| 296 | Erection, testing & commissioning of Distribution Board by providing MS angle 50x50x6 mm structure, cement concrete foundation, LT Cu. Cable etc. as per technical specifications, approved drawings and scope of work. |
| 297 | Cold Rolled Steel sheet enclosed floor mounted 415 V, AC Distribution Board with all accessories |
| 298 | Cold Rolled Steel sheet enclosed floor mounted 30 V Distribution Board with all accessories. |
| 299 | Erection, laying, hoisting, stringing, sagging, jumpering, binding to various equipment with supply of bimetallic connectors, clamps, Compression Joints, Connectors, hardware etc. as required as per technical specifications, approved drawings and scope of works. |
| 300 | ACSR 200 sqmm. Panther conductor (3 wire)-Substation part |
| 301 | ACSR 150 sqmm. Wolf conductor (3 wire)-Substation part |
| 302 | ACSR 100 sqmm. Dog conductor (3 wire)-Substation part |
| 303 | Aluminium Bus Pipe 1.5\\" |
| 304 | Erection, testing and commissioning of insulator including their hardware fittings as per technical specification, approved drawings and scope of work. |
| 305 | 33 kV Polymer Composite with fittings Pin Insulator |
| 306 | 11 kV Polymer Composite with fittings Pin Insulator |
| 307 | 33 kV Polymer Composite with fittings Disc Insulator with strain hardware |
| 308 | Post Insulator 33 kV |
| 309 | Laying, testing and commissioning of LT Power Cable in cable trench/ pipes/ underground/ overhead with termination at indoor/outdoor terminals including supply of glands, lugs, cable ties, tagging etc. as required as per Technical Specification, approved Drawing and Scope of works. |
| 310 | Cable (PVC 1.1 kV Grade) 4C x 185 sq. mm., armoured, aluminium conductor |
| 311 | Cable (PVC 1.1 kV Grade) 4C x 50 sq. mm., armoured, aluminium conductor |
| 312 | Cable (PVC 1.1 kV Grade) 4C x 25 sq. mm., armoured, aluminium conductor |
| 313 | Cable (PVC 1.1 kV Grade) 4C x 10 sq. mm., armoured, aluminium conductor |
| 314 | Cable (PVC 1.1 kV Grade) 2C x 10 sq. mm., armoured, aluminium conductor |
| 315 | Cable (XLPE 1.1 kV Grade) 4C x 120 sq. mm., armoured, aluminium conductor |
| 316 | Laying, testing and commissioning of Control Cables in cable trench/ pipes / underground including termination at indoor/outdoor with supply of glands, lugs, cable ties, tagging etc. as required as per Technical Specification, approved Drawing and Scope of works. |
| 317 | 1.1 KV grade PVC insulated armoured stranded Copper Control Cable: 4C x 2.5 sq. mm. |
| 318 | 1.1 KV grade PVC insulated armoured stranded Copper Control Cable: 8C x 2.5 sq. mm. |
| 319 | 1.1 KV grade PVC insulated armoured stranded Copper Control Cable: 12C x 2.5 sq. mm. |
| 320 | Erection, testing & commissioning of 12 kV, 800 A, 3-ph, Multi panel Shunt trip, Indoor Type, motor operated, spring closing Vacuum Circuit Breaker and indoor control panel by providing ISMC 100 channel, levelling, alignment and welding on existing cable trench in control room including indoor type Current Transformers, indoor type Potential Transformers, indoor mounting type control panels, by providing control cabling between VCB and indoor control panel and required accessories, bi-metallic clamps, A-meter, volt-meter, Relay & accessories complete for protection as per technical specifications, approved Drawing and scope of the work. |
| 321 | 12 kV, 800 A, SCADA compatible, 3 Phase, 9 Panel (2 I/C+ 1 B/C + 6 O/G) Shunt Trip VCB |
| 322 | 12 kV, 800 A, SCADA compatible, 3 Phase, 11 Panel (3 I/C+ 2 B/C + 6 O/G) Shunt Trip VCB |
| 323 | Laying, erection and Testing of 11KV XLPE, 3 phase Power cables in substation cable trench, fixing/laying of HDPE Pipe for rising as required as per technical specifications, approved Drawing and scope of works |
| 324 | Cable (XLPE 11 kV) 3C x 300 sq. mm., armored, aluminium conductor |
| 325 | 11 kV Heat Shrinakable Outdoor Termination Joint for 3 x 300 sq. mm. XLPE Cable |
| 326 | 11 kV Heat Shrinakable Indoor Termination Joint for 3 x 300 sq. mm. XLPE Cable |
| 327 | Supply & laying of HDPE pipe grade-PE-80, PN-6, 160 mm dia ( as per IS 4984-2016 with latest amendment) for riser of 11 kV 3CX300 sq. mm. Cable |
| 328 | Erection of outdoor gantry structure ( 9 M PCC Pole) with foundation but without fittings including providing and installing danger plate top muffing and pole painting by excavation of pit and by providing shuttering, cement concreting etc. as per Technical Specification, approved Drawing & Scope of works |
| 329 | 4-Pole Structure by 9M long PCC pole with cement concrete foundation (1:3:6) for LA cum Isolator Support |
| 330 | 4-Pole Structure by 9M long PCC pole with cement concrete foundation (1:3:6) for High Level Isolator Support / Bus support |
| 331 | 4-Pole Structure by 9M long PCC pole with cement concrete foundation (1:3:6) for Low Level Isolator Support / Bus support |
| 332 | DP Structure by 9M long PCC pole with refilling by 200 mm average size boulders or/and Brick Ballast mixed with excavated earth(BB:Earth::60:40) etc. for outgoing 11 kV Feeder |
| 333 | Erection, testing & commissioning of pre-fabricated galvanized steel items like DP top mounting channel, cross bracings , belting Angle , guarding bracket , extension channel, clamps etc. for over head structures with supply of GI nuts, bolts & washers as per technical specification, approved drawings and scope of work. |
| 334 | Pre-fabricated galvanised steel structure for High level isolator |
| 335 | Pre-fabricated galvanised steel structure for Low level isolator |
| 336 | Pre-fabricated galvanised steel structure forLow level bus support |
| 337 | Erection of Shielding arrangement with WPB Pole fitted with earth spike (on the top of the pole), turn buckles etc. as required as per technical specification, approved drawing and scope of work. |
| 338 | 13 M long WPB 160x160x30.44 kG/Meter with Grade E300 with cement concrete foundation (1:3:6) , muffing (1:2:4) etc. |
| 339 | Stringing, sagging of ACSR Rabbit (50 sq. mm) Conductor with Hardware Fittings complete |
| 340 | Welding and fixing of GI Earth Spike (1853x20) mm |
| 341 | Erection, Testing and Commissioning of Isolators along with support insulators, Base Channel, down pipe, Arching Horns etc. and all complete accessories as per technical specification, approved drawings and scope of work |
| 342 | 12kV, 400A Vertical Mounting type tripple pole, Gang Operated Isolator (TPGO) |
| 343 | Excavation of stay pit and erection of complete Stay Set with solid GI stay rod, anchor plate providing cement concrete foundation, GI stay wire, Guy Insulator, stay clamp, GI nut & bolts, turn-buckle, etc. as per technical specifications, approved drawings and scope of works. |
| 344 | HT Stay Set complete |
| 345 | Excavation, laying, welding of earthing & grounding conductor with GI flat of 75 mm X 8 mm, GI pipe earth electrode, bentonite powder etc. and backfilling and erection of riser upto various equipments / gantry structure with GI flat of 65 mm X 6 mm of substation. Separate earthing arrangement for PTR neutral, Station Service Transformer neutral, control room equipments. The work shall be as per technical specifications, approved drawings and scope of the work. |
| 346 | Switchyard earthing at new susbstation |
| 347 | Control room earthing at new susbstation |
| 348 | Earthing arrangement for construction of new 33 kV feeder bay at existing Substation |
| 349 | Earthing of 6 nos 11 kV terminal Isolator DP with GI Pipe and GI flat 65 mm X 6 mm |
| 350 | Erection , testing and commissioning of Switch yard electrification by LED flood light fitted on pole structure and control room roof complete with supply and fixing of junction box as per technical specifications, approved drawings and Scope of works. |
| 351 | Erection of LED flood light complete set 250 watt with all accessorie and fittings. |
| 352 | Erection, testing and commissioning of internal electrification of control room building through conceal wiring of control room by supplying of main DB sub DB, copper flexible multi conductor (FRLSH) 2.5 sq. mm. wiring (for light and fan,), 4 sq. mm. (for power point), power and light points, conduits, fan, LED lamp, Tube fittings, exhaust fans, switches, sockets, 2 mm thick PVC 25 sq. mm. dia conduit pipe, plugs MCB, separate independent earthing (2 nos. 40 mm. GI pipe 3 mtr. long) etc. as required including DC emergency lighting from DCDB as per technical specification, approved drawing and scope of work. |
| 353 | Electrification of control room building CIVIL |
| 354 | Soil investigation of Sub-Station area by drilling 04 nos. of bore holes of 150mm dia. Upto depth of 10 mtr, collection of soil sample, conducting laboratory/ field test, submission of test results and reports in three complete sets including the report about the soil resistivity, mobilization of all tools, plants etc all complete as per relevent IS codes & as per Technical Specification vide Office Order no. CED/121 dated: 28.03.2016 |
| 355 | Detail field survey (Pre level & Post level) work with levelling & @5.0 mtr grid in both sides for land development work including prepare of 03 sets of necessary drawing & data as per direction of EIC including charges of all tools & tackels etc. |
| 356 | Earth work in filling of compound, tank, low land, ditches etc with good earth in layers not exceeding 150mm including breaking clods and consolidating the same by ramming and dressing complete. (Payment to be made on the profile measurement before and after the work). Earth should be arranged by the Contractor. |
| 357 | With carried earth arranged by the contractor within a radius of 5 km. but not exceeding 10 km including cost of carried earth. |
| 358 | With carried earth arranged by the contractor within a radius of 3 km. but not exceeding 5 km including cost of carried earth. |
| 359 | With carried earth arranged by the contractor within a radius of 3 km. including cost of carried earth. |
| 360 | Design, engineering, supply of materials, labours, tools and plants for construction of boundary wall including retention wall (whichever necessary) height from FGL to 1.80 mtr made of reinforced cement concrete foundation (beam, column, footing), angle supports, brick works(1:4), plastering(1:4) including supply and fixing of 600 mm (+/- 30 mm) diametre R.B.T (Reinforced Barbed Tape) Concertina fencing with 50x50x6 M.S. angle including applying zink primer & enamel paint for M.S. angle and for boundary wall- one coat cement based paint, one coat exterior grade Acrylic primer and two coat Protective & decorative Acrylic exterior paint of approved quality all complete as per technical specification, approved drawing & scope of works and specification as per Annexure-A. |
| 361 | Boundarywall with 1.50 mtr(approx.) retention wall for Borai S/Stn |
| 362 | Design, engineering, supply of materials, labours, tools and plants for construction of 02 nos. gate column including S/Stn's Main Gate made by M.S. materials including with brick works(1:4), plastering(1:4) including applying zink primer & enamel paint for M.S. main gate and for 02 nos. gate column- one coat cement based paint, one coat exterior grade Acrylic primer and two coat Protective & decorative Acrylic exterior paint of approved quality all complete as per technical specification, approved drawing & scope of works and specification as per Annexure-A. |
| 363 | Design, engineering, supply of materials, labours, tools and plants for construction of single storied control room building complete with foundation, tiles flooring, cable trench with 6mm thick MS chequrred plate cover, plastering(1:4), 250mm th. brick work(1:6), 125mm th brick wall(1:4), rcc frame structure(M-20 concrete) , roof treatment by screed concrete, painting with inside putty, 01 coat solvent based primer & 02 coats acrylic emulsion paint and for outside wall one coat cement based paint, one coat exterior grade Acrylic primer and two coat Protective & decorative Acrylic exterior paint of approved quality all complete, aluminium doors & windows(min. 1.50mm thick of aluminium member) with M.S. grill(01 coat zink primer & 02 coats enamel synthetic paint), floor & wall tiles as per requirement, recessed water supply cpvc & upvc pipe, sanitary fittings, toilet, water supply arrangements including 1000 litre PVC water storage tank of approved make, septic tank (10 users), soak well with 2-5 nos. inspection pit, plinth protection & surface drain, Glow-sign board, 01 water purifier with R.O., internal cable trench/cable carrying structure etc., spiral stair case and internal electrification all complete as per technical specification, approved drawing & scope of works and specification as per Annexure-A. [Measurement to be made on Volume of building Structure], V= AXH in cum. where A=Plinth area in sq. m., H= [1/2xDepth of foundation (FGL to bottom of BFS/PCC for foundation)+ FGL to PL + no. of floor x floor to floor ht.+ roof treatment (0.10m)] in mtr. [vide memo no. 1029/CE(HQ)/PWD dt: 09.07.2014] |
| 364 | CRB with 1.50 mtr(approx.) land filling for Borai S/Stn |
| 365 | Drilling of tube well bore (100 mm x 50 mm size) using PVC pipes & fittings Schedule 80 (heavy duty) conforming to ASTMD - 1785 for supplying drinking water including installation of 3\\" dia. 1HP, 8-11 stage, single phase, 220-240 V submersible pump with motor, 3 core x 1.5 mm2 Submersible flat cable and control panel of suitable capacity with 01 no. horizontal check valve G.M. tested to 21 kg per sq. cm. as per Technical Specification, approved Drawing & Scope of works and specification as per Annexure-A. |
| 366 | Design, engineering and construction of foundation including supply of materials, labours, tools and plantsand considering original equipment manufacturer recommendations including excavation of pit, shuttering, reinforcement, cement concreting, providing and erecting guiding rail, wheel stopper etc. all complete as per technical specification, approved drawing & scope of works and specification as per Annexure-A. |
| 367 | 10/6.3 MVA Power Transformer |
| 368 | 33/0.415 KV Station Service Transformer |
| 369 | 11kV cable support structure |
| 370 | 33 kV VCB |
| 371 | 33 kV CT |
| 372 | 33 kV PT |
| 373 | Cable loop for power cable trench (inner dia. 2.50 m min.) |
| 374 | Cable loop for Station service cable trench (inner dia. 1.20 m min.) |
| 375 | Extra for road crossing structure for crossing power cable & control cable under concrete approach road. |
| 376 | Muffing (M-15 concrete, 0.450x0.550x0.400 ht. with plaster & neat cement) |
| 377 | Design, engineering, supply of materials, labours, tools and plants for construction of cable trench of required dimension with grill grating cover, water slope ,brick work wherever required, including fixing of edge protection M.S. angle for cover slab, lugs, flats, hangers, trays and conduit pipes (from trench to equipment), excavation, backfilling etc. all complete as per technical specification, approved drawing & scope of works and specification as per Annexure-A.---Cable Trench (900X900) |
| 378 | Design, engineering, supply of materials, labours, tools and plants for construction of cable trench of required dimension with grill grating cover, water slope ,brick work wherever required, including fixing of edge protection M.S. angle for cover slab, lugs, flats, hangers, trays and conduit pipes (from trench to equipment), excavation, backfilling etc. all complete as per technical specification, approved drawing & scope of works and specification as per Annexure-A.---Cable Trench (600X600) |
| 379 | Design, engineering, supply of materials, labours, tools and plants for construction of cable trench of required dimension with grill grating cover, water slope ,brick work wherever required, including fixing of edge protection M.S. angle for cover slab, lugs, flats, hangers, trays and conduit pipes (from trench to equipment), excavation, backfilling etc. all complete as per technical specification, approved drawing & scope of works and specification as per Annexure-A.---Cable Trench (300X300) |
| 380 | Design, engineering, supply of materials, labours, tools and plants for construction of external drainage system in the substation premises along with formwork, excavation, plastering, neat cementing, finishing etc. wherever required all complete as per technical specification, approved drawing, scope of works and specification as per Annexure-A.-(600X450 avg. depth) |
| 381 | Design, engineering, supply of materials, labours, tools and plants for construction of RCC aproach road (RCC 150mm thick) including reinforcement steel, form work, and excavation, compaction etc. all complete as per technical specification, approved drawing & scope of works and specification as per Annexure-A. [Consider - S/Stn's approach road top = FGL of S/Stn] |
| 382 | Design, engineering, supply of materials, labours, tools and plants for construction of Pathway (Cast in situ Chequered tiles 250x250 mm or 200x200 mm over 65mm 1:2:4 CC) with 35mm thick I.P.S. at edge of both side of pathway including form work, and excavation, compaction etc. with 02 coats floor paint over pathway all complete as per technical specification, approved drawing & scope of works and specification as per Annexure-A. |
| 383 | Design, engineering, supply of materials, labours, tools and plants for construction of fencing including M.S. gate & grill around switchyard including reinforcement steel, form work, excavation and applying one coat zink primer and 02 coats enamel paint for M.S. work, with one coat cement based paint, one coat exterior grade Acrylic primer & two coat Protective & decorative Acrylic exterior paint for cemented surface of approved quality etc. all complete as per technical specification and approved drawing & scope of works and specification as per Annexure-A. |
| 384 | Supplying & spreading of 100mm thick Grade-II (53-22.4mm) hand broken Black Stone aggregates spreading over 75mm thick M-15 concrete. Before concreting, the switchyard area should be cleaned by cutting bush, jungles and dressing, levelling & compacting with hand compactor machine. After compaction, laying 75mm BFS over 150mm thick silver sand/fine sand. The Polythene Sheet (150gm / sq.m.) should be laying in-between BFS & M-15 CC. One layer 125mm thick brick work(1:4) with plaster & neat cement should be provide at the edge of sheilding area over CC for gaurding black stone. 300-400 mm ht., 250mm thick brick wall(1:6) with plaster & neat cement should be provide at the edge of sheilding area under M-15 concrete as per site condition & instrcution of EIC with all labour, materials etc. all complete including as per technical specification, approved drawing & scope of works and specification as per Annexure-A.[ Consider- Switchyard black stone top = 300mm down of top of PTR foundation] |
| 385 | Design, engineering and construction of RC Box culvert including wing walls, if required made of RC (M20) CONCRETE Slab over drain/nallah with its foundation considering 5 m width and class of loading \\"A\\" including all bye-works etc. complete as per approved drawing and specification & scope of works and specification as per Annexure-A. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
| 7 | Click here to download tender document | Tender Documents |
| 8 | Click here to download tender document | Tender Documents |
| 9 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail