| 1 | Electrical Work (LT Panel Board ) |
| 2 | OD183724/2025-2026:Supply Design installation testing and commissioning of LT panel (MSB panel with all smart features including power management software) in place of old Panel. The Panel board will be fabricated using CRCA 14 SWG/ 2 mm MS Sheet steel. The sheet steel fabrication will be treated through 7 tank cold pre-treatment process before powder coating. Panel will be powder coated with approved colour and interconnected with Aluminum Bus bars 2500A current carrying density tested and certified by the company. Panel board shall be of cubicle type indoor, floor mounted, dust and vermin proof main free standing 415V LT distribution panel / sub distribution panels as per current IS/IEC standards complete with all accessories such as protection relays, control wiring, auxiliary contacts, indicating lamps, measuring CTs and multi function meters, spreader terminals, EXTENDED ROTORY HANDLE, Com-Module, indication lamps, power supply modules, control MCBs etc. for all incoming and outgoing switches. All the 415V AC, devices/equipment like bus support insulators, circuit breakers, VTs, etc., mounted inside the switchgear shall be suitable for continuous operation and satisfactory performance under the following supply conditions: (a) Variation in supply voltage: 5%, (b) Variation in supply frequency: 3%.The switchboards shall be based on IEC 61439 OEM certified design, supplied by OEM authorized franchises. OEM Partnership certificate shall be furnished by the company. The company shall certify the design and company name imposed/punched on the panel.The Panels shall be tested for internal arc compliance of minimum 85kA for 0.3 sec as per IEC 61641. The LV panel shall have provision for top / bottom in coming and out going respectively to suit site conditions of cable entries. The LV Panel shall comply with the Technical Data Sheet, SLD, and Feeder List as specified by the customer. Degrees of protection provided by enclosures for electrical equipment against mechanical impacts shall be IK10 as per IEC62262. All CTs & PTs shall be resin cast unless specified otherwise or as approved by the customer. All relays, meters & switches shall be flush mounted. All metering equipment shall be digital unless specified otherwise or as approved by the customer. All holes in metalwork shall be protected by substantial grommets or bushes to protect wiring passing through them. The arrangement of controlling switches in the LV panels and their marking shall be such that these are prominent, easily identifiable and accessible. Single line power / control diagrams shall be placed at the back of door or other accessible locations in the panels or near to panel with complete details as required. Equivalent Panel Model - LK Enersys / Siemens Zepan 8PU / Schneider Blok set Equivalent ACB Models & Releases - Main Incomer (EB/DG) - LK Omega - MTX 3.5EC / Siemens 3WA - ETU600 / Schneider MTZ micrologic 6X MCCB 200A & above - LK D-Sine MTX2.0 + Display / Siemens 3VA- / Schneider Compact NSX - 6 E (with display) |
| 3 | OD183721/2025-2026:Dismantling the All connections from the existing panel board gently and removing the panel board without any further damages shifting the same using crane, skilled labours and supporting tools etc and removing storing all other accessories to from existing site and conveyance to convenient place |
| 4 | OD183722/2025-2026:Charges towards the preparation of necessary plan, scheme and other related papers for submission to KSELB - First A3 Sheet |
| 5 | OD183723/2025-2026:Charges towards the preparation of necessary plan, scheme and other related papers for submission to KSELB - Additional A3 Sheet |
| 6 | Substation Panel |
| 7 | OD338899/2025-2026:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & shall conform to relevant IS .Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurements will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc. Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) |
| 8 | 90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 9 | 90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet |
| 10 | 90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC) |
| 11 | 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board |
| 12 | 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 13 | 90.14.7:Supply and providing copper earth bus in the panel board |
| 14 | OD332134/2025-2026:Supply and fixing panel mounting Castell key interlock and its accessories for 630A MCCB |
| 15 | OD332163/2025-2026:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 320/400A Amp, 50 KA, 4 pole |
| 16 | 90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 17 | OD332133/2025-2026:Supply, conveyance and fixing the following types & current rated control gears & switchgears Conforms to IS/IEC 60947-2 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.160A, 25 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL (L&K make DN1-250C or equivalent) |
| 18 | OD332136/2025-2026:Supply, conveyance and fixing the following types & current rated control gears & switchgears Conforms to IS/IEC 60947-2 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.200A, 25 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL(L&K make DN1-250C or equivalent) |
| 19 | OD332137/2025-2026:Supply, conveyance and fixing the following types & current rated control gears & switchgears Conforms to IS/IEC 60947-2 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 25 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL (L&K make DN1-250C or equivalent) |
| 20 | 90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A |
| 21 | 90.14.11.15:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 315-630 A |
| 22 | OD332157/2025-2026:Supply and fixing of spreader/ terminal adaptor kit with shroud in the existing microprocessor based 4pole MCCB of rating 160A (8Pieces) |
| 23 | OD332158/2025-2026:Supply and fixing of spreader/ terminal adaptor kit with shroud in the existing microprocessor based 4pole MCCB of rating 400 (8Pieces) |
| 24 | OD332159/2025-2026:Supply and fixing of spreader/ terminal adaptor kit with shroud in the existing microprocessor based 4pole MCCB of rating upto 125A (8Pieces) |
| 25 | OD332161/2025-2026:Supply and fixing 240 V AC/DC Panel Mounted LED Indicator,22.5 mm cut out dia (Red,Yellow,Green colour) in the existing panel assembly and giving connection etc as required. |
| 26 | 9.1.20:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm) |
| 27 | 9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) |
| 28 | 9.1.23:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm) |
| 29 | 9.1.25:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm) |
| 30 | 9.1.29:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm) |
| 31 | 9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 32 | 9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 33 | OD332162/2025-2026:Supply and providing 6mm thick MS chequered plate cut to shape and place in position excluding frame work if required |
| 34 | OD332168/2025-2026:Supply and providing Class A (2mm thick )Elastomeric insulating mat conforming to IS 15652/2006 with maximum use voltage is 3.3 KV . |
| 35 | OD332169/2025-2026:Dismantling the substation room panel board and its accessories from panel board , conveyance the same to section store without any further damages. |
| 36 | temporary supply |
| 37 | OD332170/2025-2026:Hire and labour charges for providing 250KVA Generator with operator as directed in position and giving connections etc. as required for 1st day |
| 38 | OD332171/2025-2026:Hire and labour charges for providing 250KVA Generator with operator as directed in position and giving connections etc. as required for 2nd day |
| 39 | OD332172/2025-2026:Hire and labour charges for providing 250KVA Generator with operator as directed in position and giving connections etc. as required for 3rd day to final day |
| 40 | OD332173/2025-2026:Running charges for 250 KVA Generator set including supply of fuel |
| 41 | OD332359/2025-2026:Hire and labour charges for providing 100KVA Generator with operator as directed in position and giving connections etc. as required for 1st day |
| 42 | OD332360/2025-2026:Hire and labour charges for providing 100KVA Generator with operator as directed in position and giving connections etc. as required for 2nd day |
| 43 | OD332361/2025-2026:Hire and labour charges for providing 100KVA Generator with operator as directed in position and giving connections etc. as required for 3rd day onwards |
| 44 | OD332362/2025-2026:Running charges for 100 KVA Generator set including supply of fuel |
| 45 | OD332363/2025-2026:Hire and labour charges for providing 3.5x120 sqmm PVC insulated and PVC sheathed armored Al cable of 1.1 KV grade for 1st day |
| 46 | OD332364/2025-2026:Hire and labour charges for providing 3.5x120 sqmm PVC insulated and PVC sheathed armored Al cable of 1.1 KV grade for 2nd day |
| 47 | OD332365/2025-2026:Hire and labour charges for providing 3.5x120 sqmm PVC insulated and PVC sheathed armored Al cable of 1.1 KV grade for 3rd day onwards |
| 48 | OD332366/2025-2026:Hire and labour charges for providing 400A, 4 pole On-Load Change Over Switches In SS Enclosure and giving connection for 1st day |
| 49 | OD332367/2025-2026:Hire and labour charges for providing 400A, 4 pole On-Load Change Over Switches In SS Enclosure and giving connection for 2nd day |
| 50 | OD332368/2025-2026:Hire and labour charges for providing 400A, 4 pole On-Load Change Over Switches In SS Enclosure and giving connection for 3rd day onwards |
| 51 | OD332185/2025-2026:Hire and labour charges for providing 3.5x185 sqmm PVC insulated and PVC sheathed armored Al cable of 1.1 KV grade for 1st day |
| 52 | OD332186/2025-2026: Hire and labour charges for providing 3.5x185 sqmm PVC insulated and PVC sheathed armored Al cable of 1.1 KV grade for 2nd day |
| 53 | OD332187/2025-2026:Hire and labour charges for providing 3.5x185 sqmm PVC insulated and PVC sheathed armored Al cable of 1.1 KV grade for 3rd day onwards |
| 54 | OD332188/2025-2026:Hire and labour charges for providing main board consisting of 400A TPN SDF with 400A TPN bus bar chamber as incomer and 1No 200A TPN SDF and 4Nos 100A TPN SDF as out going and giving connections for 1st day |
| 55 | OD332189/2025-2026:Hire and labour charges for providing main board consisting of 400A TPN SDF with 400A TPN bus bar chamber as incomer and 1No 200A TPN SDF and 4Nos 100A TPN SDF as out going and giving connections for 2nd day |
| 56 | OD332190/2025-2026:Hire and labour charges for providing main board consisting of 400A TPN SDF with 400A TPN bus bar chamber as incomer and 1No 200A TPN SDF and 4Nos 100A TPN SDF as out going and giving connections for 3rd day onwards |
| 57 | OD333744/2025-2026:Hire and labour charges for providing ordinary pipe earthing using 40mm dia GI pipe of 4.5 m long including accessories etc. as required for 1st day |
| 58 | OD333745/2025-2026:Hire and labour charges for providing ordinary pipe earthing using 40mm dia GI pipe of 4.5 m long including accessories etc. as required for 2nd day |
| 59 | OD333746/2025-2026:Hire and labour charges for providing ordinary pipe earthing using 40mm dia GI pipe of 4.5 m long including accessories etc. as required for 3rd day onwards |
| 60 | OD333747/2025-2026:Hire and labour charges for providing No 4 SWG bare copper conductor and giving connection for 1st day |
| 61 | OD333748/2025-2026:Hire and labour charges for providing No 4 SWG bare copper conductor and giving connection for 2nd day |
| 62 | OD333749/2025-2026:Hire and labour charges for providing No 4 SWG bare copper conductor and giving connection for 3rd day onwards Please Enable Macros to View BoQ information |