Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | SITC OF DG Set |
| 2 | OD108127/2025-2026:Supply ,Conveyance, Installation ,Testing and Commissioning of 320 KVA DG set with CPCB IV+ norms and as per the technical details given below:-. Engine. a. Make of Engine - As specified in accepted list of material. b. Type of Engine-Diesel Engine. c. No. of cylinder- Suitable to develop the required BHP as per manufacturer's standards. d. Method of cooling - Water cooling(with radiator) e. Aspiration - Turbo charged after cooled. f. Design - Suitable for generator set application. g. Out put - BHP at 1500 RPM under NTP conditions or other BHP ratings Specified by the respective manufactures capable of delivering the required power for alternator. Standard accessories with diesel engine. a. Fly wheel housing and flywheel to suit single bearing alternator (Close coupled arrangement).b. Air cleaner, c. Coolant kit. d, Fuel Pump, e Electronic governor backed with mechanical governor. f. Fuel filter. g .Lubricating oil filter, h. Residential type exhaust silencer. Engine Instrument Panel. a. starting switch with key or button .b. Lubricating oil temperature gauge. c .Lubricating oil pressure gauge, d. Water temperature gauge. e. RPM Indicator with hour meter. f. Battery charging ammeter. Safety Controls for Engine-a. Trip for low lubricating oil pressure. b. Trip for high water temperature. c. Providing necessary warning system and other safeties as contemplated in relevant ISS. d. Fuel shut off facility at over speed. Fuel pipe. Oil resistant flexible hoses & 25mm dia or nearest size MS pipe as per manufactures requirement for fuel line. Alternator-a. make-As specified in accepted make of material .b .Type - Self excited and self regulated. capacity - 320 KVA at 0.8 PF. d. System of voltage - 3 phase, 415V. e. Speed - 1500 RPM. f. Voltage regulation band - 2.50% of rated Voltage .g. Insulation - Class F/H. h. AVR - AVR shall be provided with a motorized or solid state potentiometer. i. IP rating of enclosure - IP 23.j. Wave form distortion - No load<1.5%, non-distorting balanced linear load<5%.k.Telephone interference factor - Better than 50 l. Total harmonic factor - Better than 2%. Standard control panel with suitably rated MCCB with overload and E/F release and standby low set earth fault relay using neutral CT .The alternator should confirm to IS 4722. Routine tests as per relevant ISS shall be conducted and test reports of the same shall be furnished at the time of delivery. Fuel tank-Integral type fuel tank of adequate capacity. Battery-Required number of suitably rated fully charged battery with leads and terminals as required as per manufactures requirements. Battery Charger: supply and providing 24V battery charger suitable for charging battery of DG Set (180 Ah) consisting of the following. a. Transformer / Rectifier with surge protection device. b. Charging facility for 12V & 24 V battery. c. DC Volt Meter. d. DC Ammeter to indicate both charging and discharging current. e. Selector Switch for trickle and boost charging. f. Automatic overcharge cut off facility .Acoustic enclosure: a, The DG set shall be supplied along with specially designed company fabricated (to be fabricated in the same company from where the DG set delivered) acoustic enclosure to meet the stringent MOEF/ CPCB norms of 75 dBA@ 1m at 75% load under free field conditions. b. Sufficient space and clearance shall be maintained inside the enclosure to have optimum serviceability. c. Air inlet louvers shall be designed in such a way as to operate the set at rated load even at 50ºC enclosure temperature. d. The enclosure shall be with UV resistant powder coating capable to withstand extreme environments. e. Hardware used shall be of only stainless steel make, f. Insulation material shall confirm to IS 8183 specification. Documents to be supplied: a. Engine manual, b. Spare parts book, c. Warranty certificate, d. Alternator manual & test certificate, e.1 set control wiring drawing. Installation: It shall be installed in the pre-constructed concrete bed complying to relevant IS standards, IE rules and as per the direction of the official. Testing and commissioning :The DG set shall be tested as per relevant IS standards. Block load testing shall also be conducted and DG should have capacity to withstand block load of 55%.The load required for testing shall be made available at site by the selected agency at their own expense. The DG set should be provided with 3-year comprehensive maintenance inclusive of all Services, periodic maintenance as prescribed by the OEM including all consumable items like Engine Oil, Oil Filter, Air Filter, Coolant etc. except diesel during the DLP period. |
| 3 | OD282901/2025-2026:Supply, installation, programming, testing, and commissioning of a complete PLC-based automation system using SMART PLC for the control and automation of electrical loads and power sources in existing MSB panels. The scope of work includes complete wiring with all control components (wires, relays, connector, numbering ferules etc) and interfacing of the PLC with multifunction energy meters, plug-in relays, SMPS units, and other protective devices. All components shall be properly installed, labeled, and integrated within the panel infrastructure. The system shall communicate using the MODBUS protocol over RS-485, enabling real-time data exchange between the PLC and connected field devices. The PLC shall be programmed to monitor real-time parameters such as grid (KSEB) availability, generator readiness, and load thresholds. Based on these conditions, the system will perform logical decision-making for source switching and load sharing, including the use of interlocks and priority-based control logic. Setpoints and operational parameters shall be configured to ensure automatic failover and safe recovery during power outages or equipment faults. Upon completion of installation, the system will undergo comprehensive testing, including load simulation and sequence verification. The commissioning process will include validation of both automatic and manual operating modes, as well as training for the operator or maintenance team. Make of PLC: Siemens S7-200 SMART or equivalent approved make. Scope Includes: All required control wiring, programming, testing tools, software loading, system documentation, and final commissioning reports in compliance with applicable IS standards and submit all control wiring diagram with PLC programming manual etc as required |
| 4 | 90.14.8.16:800 A, 4 pole, electrical draw out type, microprocessor based ACB with overload , instantaneous SC , delayed SC and ground fault protection 50kA |
| 5 | OD282874/2025-2026:Supply and fixing of Under Voltage Release (UVR) module with adjustable time delay ranging from 0.2 seconds to 3.2 seconds, suitable for Air Circuit Breakers (ACBs) |
| 6 | OD281638/2025-2026:Supply, installation, Testing and commissioning 560 A, 4pole, AC1 contactor with Auxillary contactor(2 NO+ 2 NC) and other necessary connected accessories in the AMF panel board as required (LK make MCX 44 OR EQUIVALENT) |
| 7 | OD282300/2025-2026:Supply, installation, Testing and commissioning 200 A, 4pole, AC1 contactor with Auxillary contactor (2 NO+ 2 NC) and other necessary connected accessories in the AMF panel board as required (LK make MCX 33 or equivalent) |
| 8 | OD281645/2025-2026:Supply, installation, Testing and commissioning 400 A, 4pole, AC1 contactor with Auxillary contactor (2 NO+ 2 NC) and other necessary connected accessories in the AMF panel board as required (LKmake MCX 43 or equivalent) |
| 9 | OD337399/2025-2026:Supply , conveyance , installation , testing and commissioning of Control Relays Auxiliary Contactors, , 2NO + 2NC (Make L&K India MXO AC 22E or equivalent) |
| 10 | OD337412/2025-2026:Supply, conveyance and fixing 4 C/O relay MY4N-GS DC24 with Base PYF14A-N, Coil Supply 24VDC (MAKE :OMRON or equivalent ) |
| 11 | OD337404/2025-2026:Supply , conveyance , installation , testing and commissioning of Add On Auxiliary Contactor Block , Coil voltage 24V DC, MO0 , 2NO + 2NC (Make LK India MO0 or equivalent) |
| 12 | OD337418/2025-2026:Supply, conveyance , fixing and testing of Single phase preventer SPP 3phase. Make :GIC SM301 or equivalent |
| 13 | OD337381/2025-2026:Supplying and drawing 2 Core Shielded Signal Data Transmission Cable in the existing surface / recessed steel/ PVC conduit as required. (0.50 Sqmm X 1 Pair RS-485 Modbus UNARMD Cable) |
| 14 | OD336632/2025-2026:Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:150mm dia |
| 15 | OD160296/2025-2026:Supply and providing cladding for 150mm dia MS exhaust pipe using 50mm thick glass wool /mineral wool /rock wool density not less than 120Kg/m3 and aluminium cladding (0.6mm thick). |
| 16 | OD108180/2025-2026:Supply anfd filling of Diesel for generator |
| 17 | OD336509/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x400 sqmm (clamped with 40x3mm MS flat clamp) |
| 18 | OD336413/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 3.5x300 sqmm |
| 19 | OD336479/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x300 sqmm (clamped with 40x3mm MS flat clamp) |
| 20 | OD336507/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x240 sqmm (clamped with 40x3mm MS flat clamp) |
| 21 | OD336503/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1584/(part I)/1988 for PVC & IS 7098/(part I )/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 3.5x120 sqmm |
| 22 | OD336482/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x120 sqmm (clamped with 25/40x3mm MS flat clamp) |
| 23 | 9.1.31:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm) |
| 24 | 9.1.30:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm) |
| 25 | 9.1.29:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm) |
| 26 | 9.3.22:Supplying and making straight through joint with cast resin compound including ferrules andother jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm |
| 27 | 9.1.25:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm) |
| 28 | 9.1.24:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm) |
| 29 | 9.1.23:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm) |
| 30 | 9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm) |
| 31 | 9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) |
| 32 | 9.1.20:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm) |
| 33 | 9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 34 | 90.12.10.6:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation110/94 mm or nearest size |
| 35 | 90.12.10.4:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation77/63 mm or nearest size |
| 36 | OD108881/2025-2026:Supply, laying and clamping of 1 no. 2.5 sqmm 12 core PVC/ XLPE insulated armoured control cables with copper conductors for working voltages up to and including 1100 V conforming to IS 1554 part I 1988 for PVC and IS 7098 Part I for XLPE with the cables, spacing of clamps with factory made clamp not exceeding 60cms, making good the damages , colour washing etc. as required. |
| 37 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 38 | 5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 39 | 5.11:Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 40 | 90.16.2.4:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.40 mm dia G.I. pipe ( medium class) |
| 41 | OD336634/2025-2026:Providing and fixing 25 X 3 mm copper strip on surface or in recess for connection using copper saddles ,Al alloy/cadmium plated iron screws,40mm long PVC fastener as required. |
| 42 | OD337494/2025-2026:Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required.25 x 3mm brass bolt & nut |
| 43 | OD337497/2025-2026:Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required. 25 x 6mm brass bolt & nut |
| 44 | OD336536/2025-2026:Providing and drawing 4.0 mm (8 SWG) copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 45 | 14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. |
| 46 | 14.8:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required. |
| 47 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels |
| 48 | OD336537/2025-2026:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & shall conform to relevant IS.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc., detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc. shall not be used for the fabrication of panel assembly. The measurements will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc. Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame) |
| 49 | 90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC) |
| 50 | 90.14.2.2:Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 51 | 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 52 | 90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet |
| 53 | 90.14.7:Supply and providing copper earth bus in the panel board |
| 54 | 90.14.10.18:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.630A, 50/55 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC |
| 55 | OD168706/2025-2026:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required. 500A, 50/55 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC |
| 56 | 90.14.10.17:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.320A/400A, 50/55 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC |
| 57 | OD49353/2025-2026:Supply and providing Multi function meter to read: Volts, Amps, PF, F, THD,W, Wh, VA, VAh, Var, Varh, Run hrs, On hrs, Interrupts, Preloaded Demand & Import /Export, Min/Max Monitoring with Date/Time stamping, Calibration LED & heart beat LED for communication status 3 phase accuracy class 1 with RS485 communication Port ( Make: Schneider Electric EM6400NG Class-1 with RS485 Port or equal) |
| 58 | OD336917/2025-2026:Supply and fixing of digital type Multi function meter of 1 accuracy class with backlit LED display, built in selector switch for measuring all electrical parameters like V, A, F, PF 3 phase accuracy class 1 suitable for flush mounting complete as required. |
| 59 | OD113779/2025-2026:Supply and fixing of Red, Green, Black, Yellow, Orange colours LED indicator, AC/DC, 22.5 mm cut out dia and its connected accessories as required |
| 60 | OD113778/2025-2026:Supply and fixing of Blue colour LED indicator, AC/DC, 22.5 mm cut out dia and its connected accessories as required |
| 61 | OD113780/2025-2026:Supply and fixing 800/5A, 15 VA accuracy class 0.5,Resin cast metering CT in the existing panel assembly as required. |
| 62 | OD49319/2025-2026:Supply and fixing 500/5A, 15 VA accuracy class 1,Resin cast metering CT in the existing pannel assembly as required. |
| 63 | OD169773/2025-2026:Supply and fixing 300/5A, 15 VA accuracy class 1,Resin cast metering CT in the existing panel assembly as required. |
| 64 | OD113783/2025-2026:Supply and providing Panel mounting fresh air fan 150 mm with grill etc. as required |
| 65 | OD336539/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required.1.50sq mm wire single run |
| 66 | OD336540/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 2.50sq mm wire single run |
| 67 | OD336740/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 4.00sq mm wire single run |
| 68 | OD336739/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 6.00sq mm wire single run |
| 69 | OD336743/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 10.00sq mm wire single run |
| 70 | OD336742/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 16.00sq mm wire single run |
| 71 | 90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A. |
| 72 | 90.14.11.15:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 315-630 A |
| 73 | OD337509/2025-2026:Supply and installation of DIN Rail Surge Protection Device (4+0) Class B&C/ Type 1&2 with Total Impulse current-50 KA (10/350µ sec) & Total Max Discharge current 200KA (8/20µ sec), Voltage protection level <1.5 kV .The Surge Protection Devices should have TOV safe fail for 120 Min : 442 V. Health Status Indication in all cartridges. Total Response time <25 nano seconds. Protec T1 (4+0) or Equivalent |
| 74 | 90.14.11.4:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 630A to 800A with CBCT. |
| 75 | 90.14.11.6:MCCB AccessoriesSupply and fixing 250 - 400A earth fault module of MCCB with builtin CBCT. |
| 76 | 90.14.24.55:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.5 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel with block reactor. |
| 77 | 90.14.24.58:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.10 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel with block reactor. |
| 78 | 90.14.24.60:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.15 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel with block reactor. |
| 79 | 90.14.24.62:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.25 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel with block reactor. |
| 80 | OD116048/2025-2026:Supply and providing Block Reactor Transformers, 400 V suitable for 5 KVAR 460 V, suitable for filtering harmonics upto 7% THD with H- class insulation, lower operating losses, 180% linearity, Better Harmonic Blocking Capability [Quality Factor > 35] of capacity on existing panel board and giving connection. |
| 81 | OD336688/2025-2026:Supply and providing Block Reactor Transformers, 400 V suitable for 10 KVAR 460 V, suitable for filtering harmonics upto 7% THD with H- class insulation, lower operating losses, 180% linearity, Better Harmonic Blocking Capability [Quality Factor > 35] of capacity on existing panel board and giving connection. |
| 82 | OD116039/2025-2026:Supply and providing Block Reactor Transformers, 400 V suitable for 15 KVAR 460 V, suitable for filtering harmonics upto 7% THD with H- class insulation, lower operating losses, 180% linearity, Better Harmonic Blocking Capability [Quality Factor > 35] of capacity on existing panel board and giving connection. |
| 83 | OD116049/2025-2026:Supply and providing Block Reactor Transformers, 400 V suitable for 25 KVAR 460 V, suitable for filtering harmonics upto 7% THD with H- class insulation, lower operating losses, 180% linearity, Better Harmonic Blocking Capability [Quality Factor > 35] of capacity on existing panel board and giving connection. |
| 84 | OD336692/2025-2026:Supply and fixing 3 Pole Capacitor duty contactors for switching capacitor banks of rating 4 - 7 kVAR with Built-in Auxiliary Contacts in the existing panel assembly and giving connection etc as required. |
| 85 | OD116072/2025-2026:Supply and fixing 3 Pole Capacitor duty contactors for switching capacitor banks of rating 7.5 - 10 kVAR with Built-in Auxiliary Contacts in the existing panel assembly and giving connection etc as required. |
| 86 | OD116070/2025-2026:Supply and fixing 3 Pole Capacitor duty contactors for switching capacitor banks of rating above 11 - 15 kVAR with Built-in Auxiliary Contacts in the existing panel assembly and giving connection etc as required. |
| 87 | OD116071/2025-2026:Supply and fixing 3 Pole Capacitor duty contactors for switching capacitor banks of rating 25.0 kVAR with Built-in Auxiliary Contacts in the existing panel assembly and giving connection etc as required. |
| 88 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 89 | OD169913/2025-2026:Supplying and fixing 40 to 63 amps rating, 415 volts,3 pole \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole |
| 90 | OD336541/2025-2026:Supplying and fixing 2A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 91 | 90.14.11.14:MCCB AccessoriesSupply and fixing rotary handle, Direct type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A |
| 92 | OD116113/2025-2026:Supply and providing 8 stage 440/110V 5/1A Intelligent power factor controller in the existing panel board and giving connection. |
| 93 | OD116118/2025-2026:Supply and providing Illuminated Flush head Actuator - Green with legend 'ON', (Contact - 1 NO) in the existing panel board and giving connection. |
| 94 | OD116119/2025-2026:Supply and providing Illuminated Flush head Actuator - Red with legend 'OFF', (Contact - 1 NC) in the existing panel board and giving connection. |
| 95 | OD117306/2025-2026:Supply and fabrication conveyance and installation of angle iron frame work for supporting exhaust pipe of generator |
| 96 | 4.1.10:Supplying and installing following size of perforated painted with powder coatingM.S. cable trays with perforation not more than 17.5%, in convenient sections,joined with connectors, suspended from the ceiling with M.S. suspendersincluding bolts & nuts, painting suspenders etc as required.450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 97 | OD169905/2025-2026:Supply and providing spreader/terminal adapter kit extended terminal for 4 pole MCCB of rating 630A(8 pcs) |
| 98 | OD169907/2025-2026:Supply and providing spreader/terminal adapter kit extended terminal for 4 pole MCCB of rating 500A(8 pcs) |
| 99 | OD117536/2025-2026:Supply and fixing Spreader/ terminal adapter kit Extended terminal for 4 pole MCCB of rating up to 320 A to 400A (8 Pcs) |
| 100 | OD117538/2025-2026:Supply and providing Danger 415 V, 150 x 100 mm aluminium anodised legend plates in the existing panel board as required. |
| 101 | OD337203/2025-2026:Supply and providing Bus bar chamber, 100 x 40 mm aluminium anodised legend plates in the existing panel board as required. |
| 102 | OD337204/2025-2026:Supply and providing Cable alley, 100 x 40 mm aluminium anodised legend plates in the existing panel board as required. |
| 103 | OD113784/2025-2026:Painting letters or figures of the following sizes with enamel paint as identification mark to the Panels boars etc. as required. 2.5 cm, 4 cm, 5 cm height |
| 104 | OD117503/2025-2026:Supply and providing Class A (2mm thick )Elastomeric insulating mat conforming to IS 15652/2006 with maximum use voltage is 3.3 KV . |
| 105 | OD117502/2025-2026:Supply and Installation of 4.5Kg CO2 fire extinguisher, filled with CO2 gas as per IS 15222, control discharge mechanism fitted with minimum 1.5 meter wire braided hose & flat horn with diffuser nozzle for dispersed discharge of CO2, discharge time 37 sec, average discharge is 95%, applicable on class B, C and electrically started fire, external coating is of enamel spray painting, valve confirm to IS 3224 ISI marked, CO2 cylinder construction: hot spinning by seamless pipes & bearing ISI mark, body confirms to IS 7285 extinguishers to ISI marked. fire rating:89B |
| 106 | OD117504/2025-2026:Supply and Installation of 4Kg ABC Fire Extinguisher cap filled with mono ammonium phosphate powder 50% confirms to IS 1409, stored pressure type, with pressure gauge, the discharge time 24 sec, controllable discharge mechanism, jet range 5 meters, average discharge is 90%, appliccable on A,B & C and electrically started fire, A rating-3A, B rating 21B, construction: deep drawn & co2 mig welded, EPDM rubber hose with both end aluminium clamped, internal coating-epoxy powder coating, external coating-pure polyster powder coating(UV resistant),brass forged valves with safety pin is of ss material, sheet metal thickness ISI approved. |
| 107 | OD283213/2025-2026:Dismantling the existing Change over switch provided for the 200kva DG set without damaging the existing cables and stack them suitable places as directed by departmental Staffs |
| 108 | OD283201/2025-2026: Dismantling the existing APC panel board and its cable connection from the control room and stack them in suitable position as directed by the departmental staff |
| 109 | OD283219/2025-2026:Dismantling the existing cable connections (4x10, 4x16, 3.5x25, 3.5x35) from the panel boards, tracing,taking out from the braided cables by removing the chequered plate and insulation mat and reconnect the cable to the suitable panels /Load bank using supplied end termination |
| 110 | OD117545/2025-2026:Charges for preparation Electrical scheme A3 size- First copy. |
| 111 | OD117544/2025-2026:Copying charges for Electrical scheme A3 size additional coppy |
| 112 | 12.50:Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05%), total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5x55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 113 | 12.4.2:Providing ridges or hips width 60 cm overall width plain G.S. sheet fixed with polymer coated J or L hooks, bolts and nuts 8 mm dia G.I. limpet and bitumen washers complete.0.63 mm thick with zinc coating not less than 275 gm/m2 |
| 114 | 50.10.1:Steel work in built up G I tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete |
| 115 | 50.10.2:Steel work for purlin/single section with G I pipes including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete |
| 116 | 13.50.3:Applying priming coat:With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron /steel works |
| 117 | 13.50.4:Applying priming coat:With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel work (second coat) |
| 118 | 13.61.1:Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work |
| 119 | 16.83:Taking out existing CC interlocking paver blocks from footpath/ central verge, including removal of rubbish etc., disposal of unserviceable material to the dumping ground, for which payment shall be made separately and stacking of serviceable material within 50 metre lead as per direction of Engineer-in-Charge. |
| 120 | 16.84:Laying old cement concrete interlocking paver blocks of any design/ shape laid in required line, level, curvature, colour and pattern over and including 50 mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge. (Old CC paver blocks shall be supplied by the department free of cost.) |
| 121 | 14.72:Providing and fixing double scaffolding system (cup lock type) on the exterior side, upto seven story hight made with 40 mm dia. M.S. tube 1.5 m centre to centre, horizontal & vertical tubes joining with cup & lock system with M.S. tubes, M.S. tube challies, M.S. clamps and M.S. staricase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for the required duration as approved and removing it there after. The scaffolding system shall be stiffened with bracings, runners, connection with the building etc wherever required for inspection of work at required location with essential safety features for the workmen etc. complete as per directions and approval of Engineer- in Charge. The elevational area of the scaffolding shall be measured for payment purpose. The payment will be made once irrespective of duration of scaffolding. Note:- This item to be used for maintenance work judicially, necessary deduction for scaffolding in the existing item to be done . Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail