| 1 | providing power connection |
| 2 | 90.12.5.34:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 185 sq mm |
| 3 | 90.12.7.34:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 185 sq mm |
| 4 | 90.12.7.27:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 25 sq mm with factory made clamp |
| 5 | 90.12.7.29:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp |
| 6 | 9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm) |
| 7 | 9.1.20:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm) |
| 8 | 9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm) |
| 9 | 9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 10 | 90.12.10.9:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation145/123 mm or nearest size |
| 11 | 90.11.1.18:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 12 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 13 | OD262269/2025-2026:Supplying and fixing 40 A to 63 A, TP MCB (C curve), 10 kA breaking capacity, suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole |
| 14 | 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 15 | 2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 16 | 2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.63 amps |
| 17 | OD154703/2025-2026:Supply and fixing of SMC type Sintex box with necessary connected items as required. ( Make Sintex code. GSJB. 1510 or its equivalent) |
| 18 | 1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm |
| 19 | OD262785/2025-2026:supply and fixing of 20 mm Corrugated PVC flexible conduit as required |
| 20 | OD84025/2025-2026:Supply, Installation, Testing and commissioning of 150/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT as required |
| 21 | OD262787/2025-2026:Supply and fixing Three phase voltmeter suitable for 250A 4way Double door Load bank |
| 22 | OD262788/2025-2026:Supply and fixing single phase ammeter suitable for 250A 4way Double door Load bank |
| 23 | OD262807/2025-2026:Supply and fixing Voltmeter selector switch 6 A 3 Pole suitable for 250A 8 way Double door Load bank |
| 24 | OD262814/2025-2026:Supply and Fixing of Blue colour LED indicator, AC/DC, 22.5 mm cut out dia |
| 25 | OD262815/2025-2026:Supply and Fixing of Red, Green, Black, Yellow, Orange colours LED indicator, AC/DC, 22.5mm cut out dia |
| 26 | OD84028/2025-2026:Supplying and fixing 2 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for meter protection of following poles in the existing Load Bank complete with connections, testing and commissioning etc. as required. Single Pole |
| 27 | OD84030/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables 1.5 sq mm single run with required sockets.conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. |
| 28 | OD84032/2025-2026:Supply and fixing Spreader/ terminal adapter kit Extended terminal for 4 pole MCCB of rating up to 100 A (8 Pcs) |
| 29 | OD84033/2025-2026:Supply and fixing Spreader/ terminal adapter kit Extended terminal for 4 pole MCCB of rating up to 200 A (8 Pcs) |
| 30 | OD262401/2025-2026:Supply and fixing Spreader/ terminal adapter kit Extended terminal for 4 pole MCCB of rating from 250 A to 400A (8 Pcs) |
| 31 | 90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG) |
| 32 | 90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip |
| 33 | OD262466/2025-2026:Supply and laying following copper strips on the existing cable trench 25X3 mm copper strips |
| 34 | 90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG) |
| 35 | OD83579/2025-2026: Supply and installation, testing and commissioning of CO2 type fire extinguisher with 4.5 kg. Capacity complete with installation brackets confirming to IS15683 with ISI mark as required. |
| 36 | OD84176/2025-2026:Dismantling the existing exhaust fan without any damage and stack them in store as per the directions of departmental staff. |
| 37 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 38 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 39 | 1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 40 | 1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 41 | 1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 42 | OD262870/2025-2026:Providing and laying of C class GI pipe conforming to IS 1239 in the existing trench/across the open masonary channel-100 mm |
| 43 | OD262872/2025-2026:Supply and providing 2mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 3.3 KV dielectric strength. |
| 44 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 45 | 90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) |
| 46 | 90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 47 | 90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet |
| 48 | 90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC) |
| 49 | 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 50 | 90.14.7:Supply and providing copper earth bus in the panel board |
| 51 | 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board |
| 52 | 90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 53 | OD306810/2025-2026:Supply, conveyance and fixing the following types & current rated control gears & switchgears Conforms to IS/IEC 60947-2 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.160A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL (L&K make DZ1-160D or equivalent) |
| 54 | civil Items |
| 55 | 16.83:Taking out existing CC interlocking paver blocks from footpath/ central verge, including removal of rubbish etc., disposal of unserviceable material to the dumping ground, for which payment shall be made separately and stacking of serviceable material within 50 metre lead as per direction of Engineer-in-Charge. |
| 56 | 16.84:Laying old cement concrete interlocking paver blocks of any design/ shape laid in required line, level, curvature, colour and pattern over and including 50 mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge. (Old CC paver blocks shall be supplied by the department free of cost.) Please Enable Macros to View BoQ information |