| 1 | Lump sum price worked out by the contractor for \\"BUILDING WORKS\\" as listed in Schedule ‘A’ Part-I representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 2 | Lump sum price worked out by the contractor for \\"INTERNAL ELECTRIFICATION\\" as listed in Schedule ‘A’ Part-II representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 3 | Lump sum price worked out by the contractor for \\"INTERNAL WATER SUPPLY\\" as listed in Schedule ‘A’ Part-III\\" representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 4 | Lump sum price worked out by the contractor for \\"ROAD, PATH AND CULVERT\\" as listed in Schedule ‘A’ Part-IV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 5 | Lump sum price worked out by the contractor for \\"SEWAGE DISPOSAL/NETWORK \\" as listed in Schedule ‘A’ Part-V representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 6 | Lump sum price worked out by the contractor for \\"AREA DRAINAGE \\" as listed in Schedule ‘A’ Part-VI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 7 | Lump sum price worked out by the contractor for \\"FENCING & STEEL GATE \\" as listed in Schedule ‘A’ Part-VII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 8 | Lump sum price worked out by the contractor for \\"EXTERNAL WATER SUPPLY\\" as listed in Schedule ‘A’ Part-VIII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 9 | Lump sum price worked out by the contractor for \\"EXTERNAL ELECTRIFICATION\\" as listed in Schedule ‘A’ Part-IX representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 10 | Lump sum price worked out by the contractor for \\" DG SETS \\" as listed in Schedule ‘A’ Part-X representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 11 | Lump sum price worked out by the contractor for \\" SCADA SYSTEM AND E/M WORKS OF INTERMEDIATE PUMPING STATION \\" as listed in Schedule ‘A’ Part-XI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 12 | Lump sum price worked out by the contractor for \\"UTILISATION OF TREATED WATER \\" as listed in Schedule ‘A’ Part-XII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 13 | Lump sum price worked out by the contractor for \\"SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK\\" as listed in Schedule ‘A’ Part-XIII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 14 | Sch 'A' Part-XIV MISC ITEMS (TO BE QUOTED BY CONTRACTOR) Notes: (i) This schedule is not pre-priced by MES and the pre-priced rate indicated as \\"Rs 0.00\\" under column 5 signifies this fact only. (ii) Excavation and earth work except for the items which categorically includes for same shall be measured and paid separately under SCH A PART-XIV (SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK schedule). |
| 15 | ROAD, PATH AND CULVERT |
| 16 | Dismantling paver block/interlocking tiles any shape and size etc complete as specified and directed. |
| 17 | Fixing only interlocking paver (any shape and thickness) obtained from dismantling as in foot path, parks, lawns,drive,ways or light traffic parking etc proper embedding/laying of interlocking paver blocks into the 50mm thick sand bedding layer through vibratory compaction by using plate vibrator,filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and seeping extra sand etc complete as specified and directed. |
| 18 | SEWAGE DISPOSAL/NETWORK |
| 19 | Designing (hydraulically, structurally and aesthetically), and constructing RCC sumps in M-30 mix of required capacity including excavation in all types of strata, foundation concrete, container walls, bottom slab, top RCC roof slab with CI manhole covers and with plaster and water proofing as per zonal specification including epoxy paint inside, refilling of earth and disposal of surplus earth within 50 m lead, including all piping connections, valves, internal electrification, MS ladder, ventilation shaft, BB chambers with 5m of outer wall of tank complete including test for water tightness and hydraulic functioning. Top room as per zonal specifications included. Overall depth of sump 8.0 mIL of incoming sewer 4.0 m - 5.0 mInner Dia of sump well 3.0 m |
| 20 | Designing (hydraulically, structurally and aesthetically), and constructing RCC sumps in M-30 mix of required capacity including excavation in all types of strata, foundation concrete, container walls, bottom slab, top RCC roof slab with CI manhole covers and with plaster and water proofing as per zonal specification including epoxy paint inside, refilling of earth and disposal of surplus earth within 50 m lead, including all piping connections, valves, internal electrification, MS ladder, ventilation shaft, BB chambers with 5m of outer wall of tank complete including test for water tightness and hydraulic functioning. Top room as per zonal specifications included. Overall depth of sump 8.5 mIL of incoming sewer 5.0 m - 6.0 mInner Dia of sump well 3.0 m |
| 21 | Designing (hydraulically, structurally and aesthetically), and constructing RCC sumps in M-30 mix of required capacity including excavation in all types of strata, foundation concrete, container walls, bottom slab, top RCC roof slab with CI manhole covers and with plaster and water proofing as per zonal specification including epoxy paint inside, refilling of earth and disposal of surplus earth within 50 m lead, including all piping connections, valves, internal electrification, MS ladder, ventilation shaft, BB chambers with 5m of outer wall of tank complete including test for water tightness and hydraulic functioning. Top room as per zonal specifications included. Overall depth of sump 8.5 mIL of incoming sewer 4.0 m - 5.0 mInner Dia of sump well 3.50 m |
| 22 | Designing (hydraulically, structurally and aesthetically), and constructing RCC sumps in M-30 mix of required capacity including excavation in all types of strata, foundation concrete, container walls, bottom slab, top RCC roof slab with CI manhole covers and with plaster and water proofing as per zonal specification including epoxy paint inside, refilling of earth and disposal of surplus earth within 50 m lead, including all piping connections, valves, internal electrification, MS ladder, ventilation shaft, BB chambers with 5m of outer wall of tank complete including test for water tightness and hydraulic functioning. Top room as per zonal specifications included. Overall depth of sump 9.0 mIL of incoming sewer upto 5.0 mInner Dia of sump well 4 m |
| 23 | M & L for sign board size of ( 300 x300 ) mm made by MS angle (35x35x5)mm and 1 mm thick MS sheet with warning letters , painting, fixing of PCC (1:3:6) type C-2 size of (300x300x400) mm including necessary earth work etc complete as specified and directed. |
| 24 | M&L for cement concrete(1:4:8) type D-2 (using 40 mm graded stone aggregate) as in concrete bed to drain pipes of size 250mm bore of pipe including packing under and haunching against the sides of pipes after they are laid and tested etc complete all as specified and directed. |
| 25 | M&L for boring of holes under road,pavement , hard standing by trenchless technology (HDD) using ultra sounding technique and necessary machine including supply and laying of high density polyethylene pipes (HDPE) IS-4984/95 pressure rating of pipe PN-10 and max permissible working pressure 1.00 Mpa or 10Kgf/cm2 of size 300mm (ID) underground for depth upto 2.0m to 3.5m etc complete all as specified and directed. |
| 26 | EXTERNAL WATER SUPPLY |
| 27 | Cutting the existing CI/DI pipes in trenches 100 mm dia from making connection to proposed 50mm dia GI/CI/DI pipe including provision of CI Tee of size 100 x 100 x 50mm coller lead joints etc as required at site. |
| 28 | Construction of valve chamber of internal size 750 x 750 x 750mm suitable for 80mm dia sluice valve including necessary earth work excavation PCC 1:4:8 in foundation type D2 using 40mm graded stone aggregate, brick wall in CM 1:4, PCC 1:2:4 type B1 for coping, 15mm thick rendering in CM 1:4 including provision of MS sheet cover 3.0mm thick with MS angle frame 25 x 25 x 3mm all round and at diagonals of size 40 x 40 x 6mm and also MS plate welded to MS angle, embedded in concrete with suitable hinges and locking arrangements, including two coats of synthetic enamel paint over a coat of red oxide primer necessary excavation earth work etc, all as specified and as directed. |
| 29 | EXTERNAL ELECTRIFICATION |
| 30 | Supply and fix lightning arrestor HT 11 KV 10 KA station class etc complete all as specified and directed. |
| 31 | Cable route / path indicators made out of 40x40x4mm angle iron 1.2 mtr long and plate of size 100x150x6mm welded only on one side end havinng embossed on plate as cable HT including PCC 1:4:8 of size 30cmx30cmx 30cm duly embedded the angle iron in PCC including excavation / earth work complete all as specified and directed. |
| 32 | Supply and fixing of sheet moulding compound junction box shock and rust proof, termite resistant, tamper proof , front openable type for single phase, two wire rating of size 250x200x105mm complete with one no. MCB SP 6 Amp including non metallic clamps and GI nut bolts and washers of suitable size and fixed on pole / wall complete all as specified and directed. |
| 33 | M&L for street light bracket made out of 40mm dia medium grade GI pipe of 1.2m length bent to required shape suitable for fixing street light / security light fitting on Steel tubular pole / RCC pole / building wall including two Nos clamps made out 30mm X 5mm flat with suitable nuts and bolts (clamp type - as per site requirement ) including two coats of aluminium paint over a coating of red oxide primer complete all as specified and directed. |
| 34 | M&L for angle iron frame/stand suitable for mounting fire buckets (06 Nos) and including (06 Nos) of buckets, fire hook with bamboo -01 No and fire beater with bamboo -02 No complete with GI sheet, including fire buckets, painted with two coats of red colour paint over a coat of red oxide primer complete showing \\"fire\\" in english and hindi word complete all as specified and directed. |
| 35 | Supply only multi purpose fire extinguisher, capacity 9Kg, dry powder stored pressure type complete following latests ISI norms complete all as specified and directed. |
| 36 | Supply,installation,commissioning and testing of LT outdoor panel board Kiosk type (factory made of approved CPRI) made out of CRCA sheet 3.15mm thickness for outer sheet and 2mm thicness for inner sheet dust proof, powder coated from both side, individual door, factory locking system with two side ventilation suitable for working on 415 volt AC supply including bus bar chamber and water proof duly supported on 40 x 40 x 6 mm angle iron frame,opening arrangement from front & rear both duly fitted with compression cable glands for entry & exit of cables having minimun clearance of 450 mm above ground level complete comprising of the following :- (a) Aluminium busbar of 400 Amp for three phase and 200Amp for neutral.(b) MCCB 4 Pole 415 volts 300 Amp.(adjustable type) 36 KA.-01 No (for incoming)(c) MCCB 4 Pole 415 volts, 250 Amp, 25 KA.- 01 No. (for outgoing for STP )(d) MCCB 4 Pole 415 volts, 63 Amp, 16 KA.- 03 Nos. (for outgoing )(e) MCCB 4 Pole 415 volts, 25 Amp, 16 KA.- 03 Nos. (for outgoing )(f) MCB SPN 220 volts, 32 Amp, 16 KA.- 02 Nos.(for outgoing )(g) Digital type volt meter (0-500V) with selector switch - 01 No.(h) Digital type Ammeter (0- 600A ) with selector switch and CTs -01 No.(j) Indicating lamp LED cluster type set of three in RED/BLUE/ GREEN colour - 01 No. |
| 37 | Supply,installation,commissioning and testing of LT outdoor panel board Kiosk type (factory made of approved CPRI) made out of CRCA sheet 3.15mm thickness for outer sheet and 2mm thicness for inner sheet dust proof, powder coated from both side, individual door, factory locking system with two side ventilation suitable for working on 415 volt AC supply including bus bar chamber and water proof duly supported on 40 x 40 x 6 mm angle iron frame,opening arrangement from front & rear both duly fitted with compression cable glands for entry & exit of cables having minimun clearance of 450 mm above ground level complete comprising of the following : - (a) Aluminium busbar of 400 Amp for three phase and 200Amp for neutral.(b) MCCB 4 Pole 415 volts 250 Amp.(adjustable type) 36 KA.-01 No (for incoming) |
| 38 | Contd... item No. 18.08 above:- (c) MCCB 4 Pole 415 volts, 200 Amp, 25 KA.- 01 No. (for outgoing for STP)(d) MCCB 4 Pole 415 volts, 63 Amp, 16 KA.- 02 Nos. (for outgoing )(e) MCCB 4 Pole 415 volts, 25 Amp, 16 KA.- 04 Nos. (for outgoing )(f) MCB TPN Pole 415 volts, 32 Amp, 16 KA.- 02 Nos. (for outgoing )(g) Digital type volt meter (0-500V) with selector switch - 01 No.(h) Digital type Ammeter (0- 600A ) with selector switch and CTs -01 No.(j) Indicating lamp LED cluster type set of three in RED/BLUE/ GREEN colour - 01 No. |
| 39 | Supply,installation,commissioning and testing of LT outdoor panel board Kiosk type (factory made of approved CPRI) made out of CRCA sheet 3.15mm thickness for outer sheet and 2mm thicness for inner sheet dust proof, powder coated from both side, individual door, factory locking system with two side ventilation suitable for working on 415 volt AC supply including bus bar chamber and water proof duly supported on 40 x 40 x 6 mm angle iron frame,opening arrangement from front & rear both duly fitted with compression cable glands for entry & exit of cables having minimun clearance of 450 mm above ground level complete comprising of the following : - (a) Aluminium busbar of 400 Amp for three phase and 200Amp for neutral.(b) MCCB 4 Pole 415 volts 200 Amp.(adjustable type) 36 KA.-01 No (for incoming)(c) MCCB 4 Pole 415 volts, 160 Amp, 25 KA.- 01 No. (for outgoing STP )(d) MCCB 4 Pole 415 volts, 63Amp,16 KA.-01 No. (for outgoing)(e) MCCB 4 Pole 415 volts, 25 Amp, 16 KA.- 05 Nos. (for outgoing )(f) MCB TPN Pole 415 volts, 32 Amp, 16 KA.- 02 Nos. (for outgoing )(g) Digital type volt meter (0-500V) with selector switch - 01 No.(h) Digital type Ammeter (0- 600A ) with selector switch and CTs -01 No.(j) Indicating lamp LED cluster type set of three in RED/BLUE/ GREEN colour - 01 No. |
| 40 | DG SETS |
| 41 | Supply, installation, testing and commissioning Silent diesel driven engine generating set , 4 cylinder, Bore x stroke 105 x 125, 415 Volts ,3 Phase 4 wire, 50 Hz ,0.8PF,100 KVA speed variation of engine 1500 RPM, continuous rating directly coupled alternator at 1500 RPM,water cooled turbo charged ,with common base plate frame flexible coupling ,electronic control panel for engine ,control panel having meter and sound proof canopy as per CPCB norms-IV(+), displaying battery voltage, coolant water temperature ,lubricating oil pressure engine speed and engine hours ,safety trip and indication for high water temperature, low lubricating oil pressure and over speed, alternator self excited, self regulated brushless excitation. Voltage regulation (+/-1%)of related voltage from no load to full load, including AMF Panel indoor type, acoustic enclosure, Fuel piping ,Exhaust piping ,control wiring cable from engine to control panel ,all as specified and as directed by Engineer-in-charge.The generator set shall be Skid mounting type base frame fabricated from suitable MS channel suitably machined to ensure perfect alignment of the engine & alternator with rigid construction & necessary reinforcement to ensure minimum vibrations. AVM Pads: Suitable number of AVM pads shall be supplied with Silent DG Set. |
| 42 | (a) Diesel Engine: The Engine as per IS : 10001/10002, shall be vertical 4 cylinder (1500 PM. Radiator water cooled ,turbo charged /naturally not less than 90 BHP @ at 1500 RPM under NTP conditions of BS: 5514. The engine shall be provided with electrical starting arrangement & shall give the electrical output of 100 KVA/80 KW at 0.8 power factor, 415 volts at the alternator terminal.(i) A1 class Governor(ii) Battery charging Alternator(iii) Fuel filter.(iv) Lube oil filter(v) Air cleaner(vi) Engine safety sensors (LLOP & HWT)(vii) Radiator Assembly, Radiator cooling fan ,water pump ,thermostat.(viii) RPM/Hour meter.(ix) Water Temp gauge, Oil pressure gauge, Oil temp gauge. (x) Fuel hoses.(xi) Protection Guard for safety of person from moving/rotating parts of generating set coupling |
| 43 | (b) Alternator: The alternator as per IS : 13364 shall be designed for an output of 100 KVA at 1500 RPM, 415 volts, 0.8 PF suitable for 50 Hz, 3 phase, 4 wire system. The alternator is brushless type, screen protected, revolving field, self exited, self regulated with insulation class H band of voltage regulation (+/- 1%) in static condition complete all as specified and as directed by Engineer-in-charge. (c) AMF Panel :- The AMF panel shall be in door type with 14/16 gauge CRCA sheet and is powder coated for weather proof and long lasting finish and comprises of main supply failure ,monitor, voltage sensors ,supply failure times, restoration timer control unit incorporating automatic engine start/stop and failure to start ,Off/Manual /Auto test ,selector indicators for Main on load on Generator ,Low tube Please Enable Macros to View BoQ information |
| 44 | (b) Alternator: The alternator as per IS : 13364 shall be designed for an output of 100 KVA at 1500 RPM, 415 volts, 0.8 PF suitable for 50 Hz, 3 phase, 4 wire system. The alternator is brushless type, screen protected, revolving field, self exited, self regulated with insulation class H band of voltage regulation (+/- 1%) in static condition complete all as specified and as directed by Engineer-in-charge. (c) AMF Panel :- The AMF panel shall be in door type with 14/16 gauge CRCA sheet and is powder coated for weather proof and long lasting finish and comprises of main supply failure ,monitor, voltage sensors ,supply failure times, restoration timer control unit incorporating automatic engine start/stop and failure to start ,Off/Manual /Auto test ,selector indicators for Main on load on Generator ,Low tube Please Enable Macros to View BoQ information |