| 1 | Providing & repairing of 50 HP Kirloskar make pump 65 mtr. Head & 1470 RPM 35 LPS discharge pump installed at Dashehra maidan pump house (Pump unit) |
| 2 | Complete dismantling of pump i/c fitting after repairing with motor pump alignment trail testing etc. loading & unloading site to work shop to site. Complete job. |
| 3 | Providing & fixing of hardware materials including nut bolt, packing, rubber sheet, gland etc. complete. |
| 4 | Providing & fixing of G.M. Long bush. |
| 5 | Providing & fixing of C.I. Gland plate & bush. |
| 6 | Providing & fixing of neck ring. |
| 7 | Providing & fixing cooling water pipe |
| 8 | Providing & changing of coupling pulley rubber star tight fit with pump & motor couling |
| 9 | Providing & fixing of bearing no. SKF 3307 ATN 9 AUSTRIA 132 L |
| 10 | Providing & complete servicing of pump chamber fully movement of impuler unit with as per required fitting work including check nut, nut-bolt, wiser, oil paper etc. complete. |
| 11 | Providing & making of bearing sheet both side of pump & required maching lath work complete. |
| 12 | Providing and fixing of new heavy duty compressed lather for pumps 200 m.m. dia foot valve i/c complete opening, fitting, replacing lather with as per required G.I., nut bolt, wiser etc complete. |
| 13 | Complete rewinding and repairing of 50 HP three phase, 440 volts, 50 Hz, 1470 RPM 3 set Kirlosker make induction motor having following works. (Motor unit) |
| 14 | Dismating of burnt winding wires from slots cleaning and straightening of slots. |
| 15 | Complete rewinding of motor by using super enmamlled copper wire with F-class insulation materials and varnishing, drying by heating process. |
| 16 | Providing and fitting ball bearing no 6313 ZZ of any standard make. |
| 17 | Providing and fitting of terminal plate. |
| 18 | Providing and fitting of C.I housing sleeve. |
| 19 | Making of bearing seat by welding & lathe machine turning & knurling by chiesting, polishing on rotor shaft. |
| 20 | Complete reinsulation for Taking out of motor for foundation sepration of motor and pump for base plate and opening the motor taken out rotor from stator cleaning and drcarborizing rotor and stator and stator 3 ohase winding reinsulation, heating etc. complete |
| 21 | Providing and making of diamatrically balacing rotor assembley |
| 22 | Providing & fixing of C.I. motor cooling fan |
| 23 | Complete refitting on motor and base plate checking of horizintal and vertical alignment of motor pump set, coupling with pump and trial testing etc. i/c including loading and unloading charge site to work shop and back. |
| 24 | Providing for complete repairing & replacing burnet equipment for 3 nos. 50 HP auto transformer starter i/c the following equipment & works. |
| 25 | ML-4 L & T make contactor 50 hr, 415 volt. |
| 26 | ML-2 L & T make contactor 50 hr, 415 volt. |
| 27 | Volt meter 0-500 volt for starter. |
| 28 | Digital amp. meter 0-150 amp. for starter. |
| 29 | Current transformer coil range 50-100 amp. for starter |
| 30 | Selector switch for amp. meter. |
| 31 | Selector switch for volt meter. |
| 32 | LED indacator lamp unit for starter |
| 33 | Relay unit range 0-100 amp. |
| 34 | Timer assembly unit for starter |
| 35 | On/Off switch unit for starter |
| 36 | Electro control pump guard aux. supply 415 volt amp range 20 (Phase failure + dry run + over load protection system) |
| 37 | Providing for complete replacing 250/300 ampere, 415 volt 50 Hz moulded case cricuit breaker (MCCB) of any standard make for main power supply equipment. |
| 38 | Providing & fixing of 100 amp. MCCB, 415 v., 50 hz., for star delta starter |
| 39 | Providing & fixing of incoming & outgoing fiber connection terminal plate with complete copper nut bolt & wiser. |
| 40 | Complete overhauling of panel & starter for using power circuit wiring & control circuit wiring as per required wire & lugs etc. trail & testing on load complete. |
| 41 | Loading & unloading complete job repairing for site to work shop & work shop to site. |
| 42 | Providing labor charges for scraping of old paint from main panel & starter embring & red oxide coating 2 coat & enameled paint for complete job. |
| 43 | Providing and fixing of heavy duty capacitor 440 V. 15 KVAR capacitor with complete as per required work. |
| 44 | Labor charge for complete repairing opening & refitting of 150 mm dia non return valve & sluice valve i/c cutting of old damaged nut bolt & providing recasting finishing, machining of gate plate holding rod assembly as per sample & required packing, complete nut bolt for fitting on delivery pipe line at site as per following items. |
| 45 | Supply of S.S. 410 spindle rod without G.M. check nut for 150 mm. dia. |
| 46 | Recasting of 150 mm dia sluice valve G.M. check nut i/c recasting, finishing, machining & threading as per sample & cost of extra material complete work. |
| 47 | Repairing of 150 mm. dia. sluice valve C.I. fixture check nut catcher both side i/c welding, finishing cutting as per size of check nut. |
| 48 | Labor charge of opening & refitting of 150 mm. dia. sluice valve i/c cutting of old damaged nut bolt, removal of damaged gland packing, rubber packing, providing, fixing of new by fabricated parts & greasing properly cost of nut bolt, over hanting the valve transportation of material T&P testing & making with risk cover as per requirement. |
| 49 | Providing & fixing of presure gauge meter 0.0 to 7 or 0.0 to 10 Kg./cm2 size 150 mm dia with presure control tube, nut bolt, socket, GI nipple with GM valve 150 mm dia etc complete work. Please Enable Macros to View BoQ information |