| 1 | Part A :- |
| 2 | Providing, lowering, aligning, fixing in position and Jointing in pipe line, CI Body Flanged End Tamper proof Kinetic Air Valve of approved makes of following pressure rating and dia and as per following cifications: Governing standard - AWWA C512/ S:14845:2000(amended up to date),Body, High pressure cover , Low pressure cover, Cowl and Joint support ring - Grey cast iron of grade IS:210/FG200 ,Float- LP ball & HP ball : AISI 304 stainless Steel, Float Guide- HTB1,Seat ring & Gasket - EPDM/NBR, HP Orifice & HP orifice plug : HTB2/ SS ,Bush: Bronze , Flanges as per IS/ BS, Drilled as per IS:1538. Epoxy paint (Non-Toxic & suitable for drinking water) applied on body & cover inside and outside Fasteners - CS/ Galvanised steel ,Outlet of big orifice will have a screen to prevent Tamper of float, with CI metal seated D/F Non rising stem Sluice Valves as per (IS: 14846 amended up to date) PN 1.0 ratings Valves including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. Class PN 1.0 |
| 3 | 100 mm |
| 4 | 150 mm |
| 5 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specifications and layout drawings including jointing material like nuts, bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 6 | 450 mm dia. |
| 7 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (Suitable for Sluice valves etc.) as per IS specifications complete of the following sizes including all jointing material, cost of all labour, testing and commissioning Technical Specifications and as per direction of Engineer. Class PN 1.0 |
| 8 | 450 mm dia. |
| 9 | STAR DELTA STARTER 15.0 KW (20.0 HP) : For 2 motors (1 W+ 1S) I/C- MCCB 100A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (1),Spreaders (2),Extended Rotary Handle (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 100/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3) and O/G- MCCB 63A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (2), Power Cont 32A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (12-18A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 7.5Kvar (2), S/D Timer(2) |
| 10 | STAR DELTA STARTER 22.0 KW (30.0 HP) - : For 2 motors (1 W+ 1S) I/C- MCCB 125A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (1),Spreaders (2),Extended Rotary Handle (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 125/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3) and O/G- MCCB 100A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (2), Power Cont 40A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (23-32A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 12.5 Kvar (2), S/D Timer(2) |
| 11 | P & F of IP-66 protected high power LED flood light system with extruded aluminium housing , toughened glass diffuser with suitable lenses on LED to achieve various beam angles, 240 volt, 50Hz, of high power LED lamps supplied with pre wired cable of 1 mtr. Integrated driver shall be high efficiency having efficiency more than 85 % and in compliance to IEC standards. System life of 50000 burning hours with 70 % of initial lumen be maintained. Light output in red , green , blue, cool white or warm white colour as per engineers choice. Fixtures shall be CE compliance |
| 12 | High power LED flood light 80 watt |
| 13 | Supply & Fixing of ISI marked three core PVC flat submersible cable as per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980 including making connection etc. 3 core 10.0 Sq.mm |
| 14 | Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay, ampere meter with CTs, volt meter, phase preventer, suitable starting capacitors, phase indicators, lighting arrangement etc. complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM). All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheetwith powder coating. Panel should be of minimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\\" and double door including in built locking system. The legs should be embedded in M-15 cement concrete plat form. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel shouldhave opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply. Above 15 HP and up to 20 HP |
| 15 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete including all taxes, material, labour, inside lining, outside coating, testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-charge. |
| 16 | MS pipe specials up to 600mm dia (with minimum 5mm thickness sheet) |
| 17 | Supply, installation, testing & commissioning of modulating type electric actuator resistant to high pressure and robust design, torque 7-2000 Nm, motion range 0-360°, voltage 24V DC, applicable for actuating multi-turn valves, with Case Body, Opening Mete, Inlet Wire Lock, Rubber Cover of Handle Shaft, No-Bracket Installation, Gear Box Cover, Electric Cover, Wiring Cover, Handle Shaft Cover,Output Shaft & Adapter |
| 18 | Size 200 mm to 300 mm |
| 19 | Size 350 mm to 600 mm |
| 20 | Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. 35.0 Sq.mm, 3.5 core Please Enable Macros to View BoQ information |