| 1 | \\" Estimate for Providing 3 Phase Power Supply load of 60 KW/66.66 KVA for Automobile Workshop Purposes to the Principal,Govt. Polytechnic at Automobile Work shop ,Triliambaguda under ESO-II, Nabarangpur. |
| 2 | SCOPE OF THE WORK- 1. 100 KVA 11/0.4 KV DP mounted Sub-station =01 No.(Handed Over to TPSODL). 2.3 3 W 11 KV line with 55 mm2 AAAC =0.16 Km 3.3 Service Connection =01 No |
| 3 | PART-I(Estimate of DP mounted 11/0.4 KV 100 KVA S/S with Bricks boundry & MS Iron grill gate). |
| 4 | S/F of 9 Mtr long 300 Kg PSC Pole. |
| 5 | S/F of Rcc Base Plate |
| 6 | S/F of Pressure channel 100X50X6mm,2.8mtr 2 Nos with Galvanisation charges |
| 7 | S/F of Transformer mounting channel 100X50X6mm,2.8mtr long 2 Nos.(9.2Kg/Mtr.)with Galvanisation charges |
| 8 | S/F of Suport channel of 100X50X6mm, 0.5 Mtr long 2 Nos.(9.2Kg/Mtr.) for Transformer Mounting Channel with Galvanisation charges |
| 9 | S/F of Transformer belting 50X50X6mm,angle 3.5 long 2 Nos.(4.5Kg/Mtr.) with side angle total (7mtr) |
| 10 | S/F of AB Switch & HG fuse mounting channel 75X40X6 mm,2.8mtr.Long 4 Nos.(6.8Kg/mtr) with Galvanisation charges |
| 11 | S/F of Support Channel of 75x40x6 mm for AB Switch mounting channel 75X40X6 mm,0.5 Mtr.Long 4 Nos.(6.8Kg/mtr) with Galvanisation charges |
| 12 | S/F of Cantilever channel for supporting HG fuse 75X40X6mm MS Angle 1 mtr.Long 2 Nos.(6.8Kg/mtr) with Galvanisation charges |
| 13 | S/F of Angle for cantilever arrangement for HG fuse 50X50X6mm 2mtr long each,2Nos(4.5Kg/Mtr)with Galvanisation charges |
| 14 | S/F of Angle for mounting of LT distribution box 50X50X6mm 3mtr long each,(4.5Kg/Mtr) with Galvanisation charges |
| 15 | S/F of Channel for AB Switch Handle 75X40X6 mm,1 Mtr.Long 1 No.(6.8Kg/mtr) with Galvanisation charges |
| 16 | S/F of Disc insulator(B&S) 45KN Polymer |
| 17 | S/F of Hardware fitting (B&S) 45KN |
| 18 | S/F of 11 KV Pin Insulator polymer |
| 19 | S/F of 11KV AB switch 3 Pole,400A |
| 20 | S/F of 11KV HG fuse 3 Pole,400A |
| 21 | S/F of Lightning Arrester(9KV,10KA) Station Class |
| 22 | S/F of PG clamp for 55 mm2 AAA conductor |
| 23 | S/F of LT Distribution Box with MCCB,Alluminium busbar of 2 bay with Kit Kat fuse for 100 Kva S/s |
| 24 | S/F of 3.5x95 mm2 LT PVC Cable(un armoured) |
| 25 | S/F of 100 KVA,11/0.4 KV Transformer BIS Energy level-II |
| 26 | S/F of G.I Pipe Earthing 40 mm Dia medium gauge 3mtr long for Earthing device |
| 27 | S/F of GI Flat(25x6mm) for Neutral & body Earting of DTR |
| 28 | S/F of GI Bolts,Nuts & washers |
| 29 | S/F of Earthing for Supports(Coil type) |
| 30 | S/F of No.6 G.I wire for earthing |
| 31 | S/F of Danger Board |
| 32 | S/F of Back Clamp for Danger Board. |
| 33 | S/F of ANTICLIMBING DEVICE / Barbed wire(3 KG per supprot) |
| 34 | S/F of Back Clamp for ACD. |
| 35 | S/F of Fish Plate for LA Fixing (50x8mm of Flat,0.97Kg/Mtr & 0.28Mtr Long for Each) |
| 36 | S/F of HT Stay Set(Complete) REC Construction standard |
| 37 | S/F of HT Stay Insulator Type-C |
| 38 | S/F of Stray Clamp(1.9 Kg /pair) |
| 39 | S/F of 7/10 G.I.Stay Wire(Grade-2) |
| 40 | Sundries (Paint,AI Binding tape, wire insulating tape,Clamp connector,Jumpering materials,Socket & other accessories etc. |
| 41 | Civil Works |
| 42 | Concreting of support C.C.1:1.5:3(I) |
| 43 | Couping with C.C.1:1.5:3(J) |
| 44 | Material for earthing including masonary work for earth pit,and cement plate cover including salt,Charcoal etc.(K) |
| 45 | Cement concreting for stud pole / stay anchor plate with C.C.1:3:6 (L) |
| 46 | Construction of brick bondary wall fencing with sand and metal spreading |
| 47 | Brick boundary wall for fencing,Sand Filling,Spreading of Aggregate & also inclding Fixing of MS Grill Gate |
| 48 | PART-II(Errection of 3 3W 11 KV line with 55 mm2 AAAC=0.16 Km(4 Spans)(Incl.1 No T.Pole) |
| 49 | S/F of 9 Mtr long 300 Kg PSC Pole. |
| 50 | S/F of Rcc Base Plate |
| 51 | S/F of 11KV V Cross arm(10.2 Kg each) |
| 52 | S/F of GI Back Clamp for'V' Cros Arm (0.85 Kg each) |
| 53 | S/F of 11 KV F clamp 2.9 Kg |
| 54 | S/F of Top Bracket 100X50mm MS channel (02 Kg each) |
| 55 | S/F of Disc insulator (B&S) 45KN Polymer |
| 56 | S/F of Hardware fitting (B&S) 45KN |
| 57 | S/F of 11 KV Pin Insulator polymer |
| 58 | S/F of 55 mm2 AAAC |
| 59 | S/F of PG clamp for 55 mm2 AAA conductor |
| 60 | S/F of Straight Cross arm Channel of 100x50x6 mm,9.2Kg /Mtr,Each Channel length of 1.2 Mtr.of Bottom Channel & 0.206 Mtr of Top Channel.(2 Nos) |
| 61 | S/F of H.T Stay set(Complete) |
| 62 | S/F of Stay Insulator |
| 63 | S/F of Stay clamp or Stud Clamp |
| 64 | S/F of 7/10 SWG stay wire |
| 65 | S/F of Earthing for support (coil type) |
| 66 | S/F of No.6 G.I wire for earthing |
| 67 | S/F of Danger Board |
| 68 | S/F of Back Clamp for Danger Board. |
| 69 | S/F of ANTICLIMBING DEVICE / Barbed wire (3 KG per supprot) |
| 70 | S/F of Back Clamp for ACD. |
| 71 | S/F of Fish Plate for LA Fixing (50x8mm of Flat,0.97Kg/Mtr & 0.28Mtr Long for Each) |
| 72 | S/F of GI Nuts,bolts and washers of different Sizes |
| 73 | S/F of Sundries (Paint,AI Binding tape,wire insulating tape,Clamp connector,Jumpering materials,Socket & other accessories etc. |
| 74 | Civil Works |
| 75 | Concreting of support C.C.1:1.5:3(J) |
| 76 | Couping with C.C.1:1.5:3(K) |
| 77 | Cement concreting for stud pole / stay anchor plate with C.C.1:1.5:3(L) |
| 78 | PART-IV(Estimate for Service Connection with LTCT Meter). |
| 79 | S/F of No.8 SWG G.I wire |
| 80 | S/F of 200 A Kit kat fuse |
| 81 | S/F of 40 mm G.I S/C bracket |
| 82 | Inspection Feee Please Enable Macros to View BoQ information |