| 1 | \\" Estimate for Providing 3 Phase Power Supply of 54 KW/60 KVA to Odisha Adarsha Vidyalaya Fatki under ESO Chandahandi . |
| 2 | SCOPE OF THE WORK- 1.Installation of 100 KVA 11/0.4 KV DP Mounted Sub-Station with Brick Boundary wall as per TPSODL Specification=01 Nos. (Handed over to TPSODL). 2.3 3 W 11 KV line with 55 mm2 AAAC =0.03 Km(1 Spans). 3.Extension of LT line with 3X95+1X70 +1X16 mm2 XLPE AB Cable =0.29 Km(8 Spans). 4. 3 Service Connection =01 No. |
| 3 | S/F of 9 Mtr long 300 Kg PSC Pole. |
| 4 | S/F of RCC Base Plate |
| 5 | S/F of Pressure Channel 100X50X6 mm ,2.8 mtr 2 No with Galvanisation charges. |
| 6 | S/F of Transformer mounting channel 100X50X6mm, 2.8 mtr long 2 Nos.(9.2Kg/Mtr.) with Galvanisation charges. |
| 7 | S/F of Support Channel of 100x50x6 mm ,0.5 Mtr long 2 Nos.(9.2 Kg/Mtr) with Galvanisation charges. |
| 8 | S/F of Transformer belting 50X50X6mm,angle 3.5 long 2 Nos.(4.5Kg/Mtr.) with side angle total (7mtr) |
| 9 | S/F of AB switch and HG fuse mounting GI channel 75x40x6mm. 2.8 mtr long 4 Nos(6.8kg/mtr) with Galvanisation charges. |
| 10 | S/F of Support Channel of 75x40x6 mm for AB Switch mounting channel 75x40x6 mm ,0.5 Mtr long 4 Nos.(6.8 Kg/Mtr) with Galvanisation charges. |
| 11 | S/F of Cantilever channel for supporting HG fuse 75x40x6 mm MS Angle 1 meter long 2 Nos.(6.8 Kg/mtr) with Galvanisation charges. |
| 12 | S/F of Angle for cantilever arrangement for HG fuse 50X50X6mm 2mtr long each, 2Nos(4.5Kg/Mtr)with Galvanisation charges |
| 13 | S/F of Angle for mounting of LT distribution box 50X50X6mm 3mtr long each, (4.5Kg/Mtr) with Galvanisation charges |
| 14 | S/F of Channel for AB Switch Handle 75X40X6 mm,1 Mtr.Long 1 Nos.(6.8Kg/mtr) with Galvanisation charges |
| 15 | S/F of Disc insulator (B&S) 45KN Polymer |
| 16 | S/F of Hardware fitting (B&S) 45KN |
| 17 | S/F of 11 KV Pin Insulator polymer |
| 18 | S/F of 11KV AB switch 3 Pole,400 A |
| 19 | S/F of 11KV HG fuse 3 Pole,400A |
| 20 | S/F of Lightning Arrester(9KV,10KA) Station Class |
| 21 | S/F of PG clamp for 55 mm2 AAA conductor |
| 22 | S/F of LT Distribution Box with MCCB, Aluminium Busbar for 2 Bay with kit kat fuse for 100 KVA S/S |
| 23 | S/F of 3.5 Cx95 mm2 LT PVC Cable (Un armoured) |
| 24 | S/F of 100 KVA,11/0.4KV(AL)Transformer BIS Energy Level-II |
| 25 | S/F of G.I Pipe Earthing 40mm Dia medium gauge 3mtr long for Earthing device |
| 26 | S/F of GI Flat (25x6mm) for Neutral & body Earting of DTR with all other Part . |
| 27 | S/F of GI Bolts,Nuts & washers |
| 28 | S/F of Earthing for Supports(Coil type) |
| 29 | S/F of No.6 G.I wire for earthing |
| 30 | S/F of Danger Board |
| 31 | S/F of Back Clamp for Danger Board . |
| 32 | S/F of ANTICLIMBING DEVICE / Barbed wire (3 KG per supprot ) |
| 33 | S/F of Back Clamp for ACD . |
| 34 | S/F of Fish Plate for LA Fixing (50x8mm of Flat ,0.97Kg/Mtr & 0.28Mtr Long for Each ) |
| 35 | S/F of HT Stay Set (Complete) REC Construction standard |
| 36 | S/F of HT Stay Insulator Type-C |
| 37 | S/F of Stay Clamp(1.9 Kg /pair) |
| 38 | S/F of 7/10 G.I.Stay Wire(Grade-2) |
| 39 | Sundries (Paint ,AI Binding tape ,wire insulating tape,anti climbing device,Clamp connector,Jumpering materials,Socket & other accessories etc. |
| 40 | Civil Work |
| 41 | Concreting of support C.C. 1:1.5:3 (I). |
| 42 | Couping with C.C. 1:1.5:3 (J) |
| 43 | Material for earthing including masonary work for earth pit, and cement plate cover including salt, Charcoal etc. |
| 44 | Cement concreting for stay anchor plate with C.C. 1:3:6(L) |
| 45 | Brick boundary wall for fencing,Sand Filling,Spreading of Aggregate & also inclding Fixing of MS Grill Gate |
| 46 | Part-II(Estimate for erection of 3 3W 11 kV Line with 55 Sqmm AAAC conductor =0.03 Km (1 Span). |
| 47 | S/F of Disc insulator (B&S) 45KN Polymer |
| 48 | S/F of Hardware fitting (B&S) 45KN |
| 49 | S/F of 55 mm2 AAAC |
| 50 | S/F of PG clamp for 55 mm2 AAA conductor |
| 51 | S/F of Straight Cross arm Channel of 100x50x6 mm,9.2Kg /Mtr,Each Channel length of 1.2 Mtr.of Bottom Channel & 0.206 Mtr of Top Channel .(2 Nos). |
| 52 | S/F of Fish Plate for LA Fixing (50x8mm of Flat ,0.97Kg/Mtr & 0.28Mtr Long for Each ) |
| 53 | S/F of GI Nuts,bolts and washers of different Sizes |
| 54 | Sundries (Paint ,AI Binding tape ,wire insulating tape ,Clamp connector ,Jumpering materials ,Socket & Other accessories etc . |
| 55 | Part-III(Estimate for erection of LT Line using 3x95+1x70+1x16 Sqmm LT AB Cable with 8 Mtr Long PSC Pole = 0.29 Km )(8 Spans) |
| 56 | S/F of 8 Mtr long 200kg PSC pole (including Transportation cost) |
| 57 | S/F of Base Plate |
| 58 | S/F of 3x95+1x70+1x16 mm2 LT XLPE Aerial bunched Cable |
| 59 | S/F of Pole Clamp for I hook. |
| 60 | S/F of Susspension Clamp with 'I' Hook. |
| 61 | S/F of Dead end clamp I hook |
| 62 | S/F of I hook for Dead end clamp . |
| 63 | S/ F of Piercing Connector. |
| 64 | S/ F of Neutral Connector. |
| 65 | S/F of Earthing for Supports(Coil type) |
| 66 | S/F of No.6 G.I wire for earthing |
| 67 | S/F of L.T stay Set (Complete) |
| 68 | S/F of Stay insulator. |
| 69 | S/F of L.T stay clamp |
| 70 | S/F of 7/12 G.I. stay wire |
| 71 | S/F of Danger Bord |
| 72 | S/F of Back Clamp for Danger Board . |
| 73 | S/F of ANTICLIMBING DEVICE / Barbed wire (3 KG per supprot ) |
| 74 | S/F of Back Clamp for ACD . |
| 75 | S/F of GI Nuts,bolt of Assorted Size. |
| 76 | Sundries & minor materials |
| 77 | Civil Work |
| 78 | Concreting of support C.C. 1:1.5:3 (I). |
| 79 | Couping with C.C. 1:1.5:3 (J) |
| 80 | Cement concreting for stud pole/ stay anchor plate with C.C. 1:1.5:3 |
| 81 | Part-IV(Estimate for Service Connection with LTCT Meter ). |
| 82 | S/F of No.8 G.I Wire. |
| 83 | S/F of 200A Kit Kat fuse |
| 84 | S/F of 40 mm G.I S/C Bracket Please Enable Macros to View BoQ information |