| 1 | (67.1) Supply and erection of Galvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 2 | (67.1.1.5) Poles with Octagonal Cross Section 7 Mtr. |
| 3 | (67.1.1.8) Poles with Octagonal Cross Section 10 Mtr. |
| 4 | (67.7) Supply installation testing & Commissioning of high mast lighting system (as per PLG 07 of ILP UK techinical report no 7 of ILE UK /IS:875 Part-1 – 2015//BSEN10025/and IS:2062 )consisting of totally hot dip galvanised by piecewise single dipped method high mast, lantern carriage suitable for up to 12 nos luminaries with welded arm (excluding luminares), mast head frame assembly with full cover, including 1 No. LED 15 Watts aviation obstruction lights, double drum type self sustaining winch, integral power tool accesible from door with padlocking arrangement (winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, Stainless steel 6 mm dia. wire ropes (AISI 316, 7 / 19 costruction 3 no. rope for lantern carrage & 2 no. rope for winch assembly ) foundation bolt, torque limiter,EPR insulated PCP sheathed 5 core x 2.5 Sq.mm trailing cable, including outdoor type control panel for auto on / off, reverse / forward motor operation. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510 ) cut and folded to form a polygonal section, telescopic jointed and welding as per BS 5135.etc. as required on Existing Foundation. ( See table P - 03 for specs.) OEM Must have Type test certificate for wind tunnel test . All as per pre approved by Engineer in-charge. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 5 | (67.7.1) 12.5 Mtr HM (in 2 section) suitable for 6 No. Luminaries 2 no. rope for lantern carrage & 2 no. rope for winch assembly |
| 6 | (67.7.2) 16.0 Mtr HM (in 2 section) suitable for 9 No. Luminaries |
| 7 | (67.8) Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles, High mast Poles as per Drawing attach at Table P-4 with Following Procedure & All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . A) Excavation of Pit for Foundation Size upto required depth from Ground levelB) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete. C) Providing and laying in position cement concrete of M-10 grade of 75 mm thicknessD) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete. E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal F) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommendations. G) Providing and Laying Reinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days. H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face. |
| 8 | (67.8.2) Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr. |
| 9 | (67.8.3) Pole Foundation for Octagonal pole from 10 Mtr. To 12 Mtr. |
| 10 | (67.11) Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 11 | (67.11.7) High Power LED Flood Light Minimum lumen output 18650 lm |
| 12 | (67.11.8) High Power LED Flood Light Minimum lumen output 22400 lm |
| 13 | (60.2) Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 14 | (60.2.3.3) 10.0 Sq. mm X 4 core |
| 15 | (60.2.4.3) 16.0 Sq. mm X 4 core |
| 16 | (61.13) P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 17 | (61.13.1) 50 mm |
| 18 | (63.1) Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. \" B \" class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 with perforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in-charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 19 | (63.5) Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 20 | (63.5.14) 25mm x 3mm G.I. ( Hot Dipped ) Strip |
| 21 | (60.3) Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 22 | (60.3.2.1) 2.5 Sq. mm X 2 core |
| 23 | (57.14) Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor as per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 24 | (57.14.2.1) 4 pole Power contactors with following AC 1 Rating X16 Amp. |
| 25 | (57.2) Providing & Fixing of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |
| 26 | (57.20.3) One day & week reserve (digital type ) |
| 27 | (42.32) SITC of Cutting back up surface up to 2 Mtr. Depth by digging by Bogie including all layers of crust for laying pipe line etc. and making good to original condition (excluding cost bitumen) |
| 28 | (E140500) SITC of chemical Gel earthing system of Dual Pipe Technologymade of with \"B\" Class G I Pipe as per IS 1239 ( part-1):2004 ofMedium duty of following sizes as per points mentioned (a), (b), [c),(d), (e) below :-(a) filled with anti corrosive conductive compounds with thepermanent sealings at both the ends, CPRI/ ERDA tested with RMScapacity of minimum 35- 40 KA for withstanding 1 second .(b) To ensure the moisture content and electrical conductivity, 25 kgfor 2000 mm & 50 Kgs for 3000mm of resistance lowering earthenhancement material shall be used as a backfill compound. Thecompound shall be tested form NABL acredeated lab for lowresistivity ( less than 0.12 Ohm - meter) & high conductivity in naturewith carbon as a major content as per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 withlatest amendemnts(c) Heavy duty weather proof poly-propylene earth pit chamber withlockable Jam free lid suitable for safe working load 5000 Kg or moreof size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. andHeight 250 to 300 mm.(d) Testing of earth resistance for value of 5 ohms or less asrequired & must record by engineer in charge during site visit andensure to enter in measurment book.(e) Self certificate for confirming above standards from OEM ismandatory. All as per pre approved by Engineer in charge. Foradditional technical parameters of products/ work , refer Annexure\"A\" attached with this BSR . |
| 29 | (E140510) With Pipe in Pipe Technology (Outer pipe dia. / Inner pipe dia. ) Minimum 100 mm dia borewell |
| 30 | (E140511) GI pipe 2000 mm long, 50 / 25mm, Terminal 40mm x 6 mm GI Strip |
| 31 | P&F to mounting circular ring made out from OEM fabricated hot dipped galvanised M.S. Circular ring (48.3X3.25mm) with cap (400 X 88.9/114.3X3.25mm) over the existing poles in circle shape of 2 Mtr. Length duly attached/welded with four nos. of support G.I. pipe of 48.3mm dia to housing pipe made out of 88.9 mm dia 450 mm long G.I. Pipe with 3 no. of ftighting bolt. complete circular shape top ring bracket having arrangement to fix 6 Nos. of LED Flood light. |
| 32 | Feeder Pillar: P&F of feeder pillar box for street light made out of CRCA sheet of 10/12 SWG of size 450X450X400mm duly paint with powder coating paint of grey colour. With fixing frame made out of ms Angle of size 25X3mm of required size and height. feeder pillar shall baove following material. 1 MCB 16 Amp single pole 2 nos. 2 with locking Arreangment and all required glend, lugs of cable size 3 Earthing Terminal- 1 nos. 4 Timer and contactor should be fitted in feeder pillar. Please Enable Macros to View BoQ information |