| 1 | Excavation in trenches not exceeding 1.5 metre wide and not exc 1.5 metre in depth for foundation or cable trenches, shafts, wells cesspits, manholes, pier holes etc. n. exc. 10 Sqm on plan and getting out in soft/loose soil, complete all as specified and directed. |
| 2 | Removing of excavated materials to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 metre above the starting point in any type of soil, complete all as specified and directed. |
| 3 | Returning filling in incl spreading, leveling watering and well ramming in layers not exceeding 25cm in soft/loose soil, complete all as specified and directed. |
| 4 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 400 Sqmm 3.5 core including taking down old unserviceable UG cable of any size, complete all as specified and directed. |
| 5 | All as per item No 4.00 here-in-before but size cable 240 Sqmm 3.5 core, complete all as specified and directed. |
| 6 | All as per item No 4.00 here-in-before but size cable 150 Sqmm 3.5 core, complete all as specified and directed. |
| 7 | All as per item No 4.00 here-in-before but size cable 50 Sqmm 3.5 core, complete all as specified and directed. |
| 8 | All as per item No 4.00 here-in-before but size cable 25 Sqmm 3.5 core, complete all as specified and directed. |
| 9 | S & F junction box made from SMC/FRP sheet ready made of size 370 x 270 x 210mm with aluminium bus bar of 100 Amp capacity for RYB and neutral made in suitablesize fixed inside the junction box with necessary supporting insulators steped type as per junction box OEM fixed on hylem sheet, entire assemblyfixed to pole /Wall with GI clamp 25 X 4mm with GI strip and nuts & bolts two sets alongwith inside the copping of pole /Post top including MCB SP 6 Amp 10 KA 240 V - 2 Nos, with necessary sizecopper lug/ thimbles for connecting cables from junction box to fittings, complete all as specified and directed.Note:- 1. Necessary earthworks for taking out cable loop and existing cables from octagonal security light poles including reconnection the same cable to the junction box by using suitable size lugs and thimbles etc. 2. Relaying of cable loops by using obtained Sand, Bricks/slabs etc. |
| 10 | Design, Fabrication & Testing of indoor type double door both side openable with locking handle for 250 KVA DG AMF panel (for I lab/ AOC office) of size 1825(H) x 1400(W) x 450(D)mm,made of 1.6mm thick CRCA sheet supported on 75 x 40mm U-channel base frame painted with extured powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheetprocess system with seimens Gray RAL-7032, Aluminum Busbar & strips\" current capacity is calculated using the formula :- Current Capacity (Amperes) = Cross-Sectional Area (mm2) x 0.8 A/mm*. All outgoing switchgears shall have extended strips (for Ampere rating more than 63A) or extended wires with terminals (for Ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring will be done by 1.5sqmm copper wire. Internal connect on with suitable size Cu. strip/Cu. wire, complete all as specified and directed.Note:- Necessary Earthworks for taking out cable loop from trench/ duct/under ground etcincluding reconnection the same cable to the LT panel by using suitable size lugs, thimbles and cable grands etc.Complete with following accessories:-(i) MCCB 400 Amp 4P 36KA TM - 03 Nos(for main supply, generator supply and for changeover supply).(ii) Spreader link 400 Amp 4P (Both Side)(iii) 3 phase heavy duty 4 pole power contactors 400 Amps, 415 volt, 4 pole 2 NO + 2 NC conforming to IS/ IEC 60947-4-1 & IEC 60947 -4-A complete - 02 Nos.(iv) C T Coil 400/5 - 06 Nos.(v) R-2, A-2, G-2indicator lamps LED.(vi) R-2, G-2 Indicator Lamp LED.(viI) B-2 Indicator Lamp LED.(viii) DigitalMultifunction Meter 4405 - 02 Nos.(ix) MX0 22E Contactor 2NO + 2NC - 03 Nos.(x) MCB 6 Amp-32 Amp SP/DP 10KA- 01 No.(xi) Buzzer 240V/24V DC - 01 No.(xii) 12 V Auto Battery Charge w/Trickle, Boost- 01 No.(xiii) Complete with all necessary protection relays, metering and indication accessories. |
| 11 | Design, Fabrication & Testing of indoor type double door both side openable with locking handle for 160 KVA DG AMF panel (for 11 ORP) of size 1825(H) x 1400(W) x 450(D)mm,made of 1.6mm thick CRCA sheet supported on 75 x 40mm U-channel base frame painted with extured powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheetprocess system with seimens Gray RAL-7032, Aluminum Busbar & strips\" current capacity is calculated using the formula :- Current Capacity (Amperes) = Cross-Sectional Area (mm2) x 0.8 A/mm*. All outgoing switchgears shall have extended strips (for Ampere rating more than 63A) or extended wires with terminals (for Ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring will be done by 1.5sqmm copper wire. Internal connect on with suitable size Cu. strip/Cu. wire, complete all as specified and directed.Note:- Necessary Earthworks for taking out cable loop from trench/ duct/under ground etcincluding reconnection the same cable to the LT panel by using suitable size lugs, thimbles and cable grands etc.Complete with following accessories:-(i) MCCB 250 Amp 4P 36KA TM - 03 Nos(for main supply, generator supply and for changeover supply).(ii) Spreader link 250 Amp 4P (Both Side)(iii) 3 phase heavy duty 4 pole power contactors 250 Amps, 415 volt, 4 pole 2 NO + 2 NC conforming to IS/ IEC 60947-4-1 & IEC 60947 -4-A complete - 02 Nos.(iv) C T Coil 400/5 - 06 Nos.(v) R-2, A-2, G-2indicator lamps LED.(vi) R-2, G-2 Indicator Lamp LED.(viI) B-2 Indicator Lamp LED.(viii) DigitalMultifunction Meter 4405 - 02 Nos.(ix) MX0 22E Contactor 2NO + 2NC - 03 Nos.(x) MCB 6 Amp-32 Amp SP/DP 10KA- 01 No.(xi) Buzzer 240V/24V DC - 01 No.(xii) 12 V Auto Battery Charge w/Trickle, Boost- 01 No.(xiii) Complete with all necessary protection relays, metering and indication accessories. |
| 12 | Design, Fabrication & Testing of indoor type double door both side openable with locking handle for 125 KVA DG AMF panel (for BOMB DUMP) of size 1625(H) x 1300(W) x 450(D)mm,made of 1.6mm thick CRCA sheet supported on 75 x 40mm U-channel base frame painted with extured powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheetprocess system with seimens Gray RAL-7032, Aluminum Busbar & strips\" current capacity is calculated using the formula :- Current Capacity (Amperes) = Cross-Sectional Area (mm2) x 0.8 A/mm*. All outgoing switchgears shall have extended strips (for Ampere rating more than 63A) or extended wires with terminals (for Ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring will be done by 1.5sqmm copper wire. Internal connect on with suitable size Cu. strip/Cu. wire, complete all as specified and directed.Note:- Necessary Earthworks for taking out cable loop from trench/ duct/under ground etcincluding reconnection the same cable to the LT panel by using suitable size lugs, thimbles and cable grands etc.Complete with following accessories:-(i) MCCB 200 Amp 4P 36KA TM - 03 Nos(for main supply, generator supply and for changeover supply).(ii) Spreader link 200 Amp 4P (Both Side)(iii) 3 phase heavy duty 4 pole power contactors 200 Amps, 415 volt, 4 pole 2 NO + 2 NC conforming to IS/ IEC 60947-4-1 & IEC 60947 -4-A complete - 02 Nos.(iv) C T Coil 400/5 - 06 Nos.(v) R-2, A-2, G-2indicator lamps LED.(vi) R-2, G-2 Indicator Lamp LED.(viI) B-2 Indicator Lamp LED.(viii) DigitalMultifunction Meter 4405 - 02 Nos.(ix) MX0 22E Contactor 2NO + 2NC - 03 Nos.(x) MCB 6 Amp-32 Amp SP/DP 10KA- 01 No.(xi) Buzzer 240V/24V DC - 01 No.(xii) 12 V Auto Battery Charge w/Trickle, Boost- 01 No.(xiii) Complete with all necessary protection relays, metering and indication accessories. |
| 13 | Design, Fabrication & Testing of indoor type double door both side openable with locking handle for 35 KVA DG AMF panel (for New Pump House) of size 1625(H) x 1300(W) x 450(D)mm,made of 1.6mm thick CRCA sheet supported on 75 x 40mm U-channel base frame painted with extured powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheetprocess system with seimens Gray RAL-7032, Aluminum Busbar & strips\" current capacity is calculated using the formula :- Current Capacity (Amperes) = Cross-Sectional Area (mm2) x 0.8 A/mm*. All outgoing switchgears shall have extended strips (for Ampere rating more than 63A) or extended wires with terminals (for Ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring will be done by 1.5sqmm copper wire. Internal connect on with suitable size Cu. strip/Cu. wire, complete all as specified and directed.Note:- Necessary Earthworks for taking out cable loop from trench/ duct/under ground etcincluding reconnection the same cable to the LT panel by using suitable size lugs, thimbles and cable grands etc.Complete with following accessories:-(i) MCCB 63 Amp 4P 36KA TM - 03 Nos(for main supply, generator supply and for changeover supply).(ii) Spreader link 63 Amp 4P (Both Side)(iii) 3 phase heavy duty 4 pole power contactors 63 Amps, 415 volt, 4 pole 2 NO + 2 NC conforming to IS/ IEC 60947-4-1 & IEC 60947 -4-A complete - 02 Nos.(iv) C T Coil 400/5 - 06 Nos.(v) R-2, A-2, G-2indicator lamps LED.(vi) R-2, G-2 Indicator Lamp LED.(viI) B-2 Indicator Lamp LED.(viii) DigitalMultifunction Meter 4405 - 02 Nos.(ix) MX0 22E Contactor 2NO + 2NC - 03 Nos.(x) MCB 6 Amp-32 Amp SP/DP 10KA- 01 No.(xi) Buzzer 240V/24V DC - 01 No.(xii) 12 V Auto Battery Charge w/Trickle, Boost- 01 No.(xiii) Complete with all necessary protection relays, metering and indication accessories. |
| 14 | Design, Fabrication & Testing of Outdoor type LT Panel of size 1400(H) x 1200(W) x 600(D)mm, double layer door, both side openable inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having Rain canopy type-4 side slope top, supported on 50 x 50 x 6mm angle iron base frame and legs of 500mm height, painted with textured powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system with seimens Gray RAL- 7032, Alu. Busbar & strips\" current capacity is calculated using the formula :- Current Capacity (Amperes) = Cross- Sectional Area (mm2)x 0.8 A/mm2.All outgoing switchgears shall have extended strips (for Ampere rating more than 63A) or extended wires with terminals (for Ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring will be done by 1.5sqmm copper wire. Internal connection with suitable size Alu. strip/Cu. wire, complete all as specified and directed. (For CADMO OFFICE)Incoming:-(i) MCCB 630 A 4P 50 KA TM- 1 No(ii) Spreader link 630A 4P- 1 No(iii) Extended Rotary Handle 630A- 1 No(iv) C T Coil 630/5- 3nos(v) R Y indicator lamps LED- 2 Nos(vi) Blue Indicator Lamp LED- 1 No(vii) Digital Multifunction Meter- 1 No(viii) MCB 6A SP for meter Protection- 1 NoOutgoing:-(i) MCCB 630 A 4P 50 KA TM- 1 No(ii) Spreader link 630A 4P- 1 Noc) Extended Rotary Handle 630A- 1 No |
| 15 | Design, Fabrication & Testing of Outdoor type LT Panel of size 1400(H) x 1200(W) x 600(D)mm, double layer door, both side openable inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having Rain canopy type-4 side slope top, supported on 50 x 50 x 6mm angle iron base frame and legs of 500mm height, painted with textured powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system with seimens Gray RAL- 7032, Alu. Busbar & strips\" current capacity is calculated using the formula :- Current Capacity (Amperes) = Cross- Sectional Area (mm2)x 0.8 A/mm2.All outgoing switchgears shall have extended strips (for Ampere rating more than 63A) or extended wires with terminals (for Ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring will be done by 1.5sqmm copper wire. Internal connection with suitable size Alu. strip/Cu. wire, complete all as specified and directed. (For Dog squard and Transmitter S/S)Incoming:-(i) MCCB 160 A 4P 36 KA TM- 1 No(ii) Spreader link 160 A 4P- 1 No(iii) Extended Rotary Handle 160 A- 1 No(iv) C T Coil 160/5- 3 Nos(v) R Y indicator lamps LED- 2 Nos(vi) Blue Indicator Lamp LED- 1 No(vii) Digital Multifunction Meter- 1 No(viii) MCB 6 A SP for meter Protection- 1 NoOutgoing:-(i) MCCB 160 A 4P 36 KA TM- 1 No(ii) Spreader link 160 A 4P- 1 Noc) Extended Rotary Handle 160 A- 1 No |
| 16 | M&L for PCC (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) as in coping of poles, approach path, LT panel etc. including necessary formwork (as required), complete all as specified and directed. |
| 17 | Supply and laying 50mm bore HDPE pipe pipe Heavy duty ofdia conformingto IS, approved colour complete with fittings for cable protection, complete all as specified and directed. |
| 18 | M&L for earthing complete with GI earth plate electrode 60 × 60cm × 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to existing earth lead strip by means of bolts, nuts, check nuts and washers of brass or HS steel all as shown in electrical plate No. 3 connected to earthing test point and and necessary excavation and earth work PCC (1:3:6) type C-1 as earth pit with MS angle iron frame 40 x 40 x 6mm and 40mm thick pre-cast RCC (1:2:4) type B-1 cover slab size 400 x 400 x 50mm reinforced with 8mm dia TMT bar, 75mm c/c both ways including one handle made of 12mm dia including providing charcoal or coke and common salt in alternate layer of 15cm compacted thickness all around the earth electrode with funnel and 20mm bore galvanized iron watering pipe (light grade) wire mesh, copper lugs, complete in all respect, including galvanised iron earth strip 32 x 6mm, protected by 40mm bore (medium grade) galvanized iron pipe up to earthing test point as directed, incl disposal of spoil to a distance not exc. 50 mtr and necessary testing on completion, complete all as specified and as directed.Note : (i) Proper earthing pit shall be provided with pit cover.(ii) GI earth strip beyond 7.5 mtr shall be measured and paid seperately. |
| 19 | Supply and fix Thermoplastics IP 65 Busbar Panel of size internal300 x 450 x 214 mm and outer dimension 400 x 500 x 220mm suitable for 100 Ampcapacity comprises with 32 x 6mm copper bus barin accordance with IEC 61439-2 which should be shock proof and double insulated. IP65 in accordance with IEC 60529 (EN 60529), weather proof, Corrosion free, Acid & Chemical Resistant, Impact resistant, Ultra Violet resistance, made of halogen & Silicone free recyclable material, internally embedded gasket with provision for cable entry through top, bottom and sides. Impact strength IK 08 (5 joules) in accordance with EN 50298:98, should withstand Glow wire test at 750°C in accordance with IEC 60695-2-11 flame retardant, Self Extinguishing, UL subject 94, V-2. Color: Grey, RAL 7035. The OEM of the Thermoplastic enclosure and the Panel manufacturer should be same and they should confirm the Panel is in accordance with IEC 61 439-1 & 2 and Routine Test Certificate should be from OEM only and submit according to IEC 61 439-1 & 2 along with Panel. The OEM of board shall submit a copy of type twst report (ASTA certification\" by CPRI) of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily: Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Degree of Protection Clearance & Creepage Distance, Mechanical Operation, complete all as specified and as directed. Note: 1.Cable gland and gland cut out will be included in unit quoted rate.2. Theentire junction box to befixed to pole /Wall with suitable size of fasteners/GI clamps will be included in unit quoted rate. |
| 20 | Note: An amount of Rs.8800.00 on account of Credit Schedule for schedule \"A\" part - II shall be deducted from the total amount of BOQ to arrive at the contract sum. |