| 1 | Dismantling of broken/dislodged pre-stressed concrete poles/steel tubular poles, of any description including earthwork for removal of concrete foundation, removal of unserviceable poles from site, complete all as specified and directed. |
| 2 | Supply and erection, in truly vertical position, LT Steel tubular swaged pole complete with cast iron base plate finial taper plug, bolt, nut and screwed type 410 SP-31 (9 Meter long) Class -10 including painting of poles with two coats of synthatic enamel paint in black and white strips upto 1.5 mtr height from coping over a coat of red oxide primer including numbering of poles as directed by Engineer in charge.Note : PCC, Earth work and MS work as cross arms clamps etc will be measured and paid separately. |
| 3 | Material and labour for PCC 1:4:8 type D-2, using stone aggregate 40mm graded as in foundation for electric poles and making of cable duct including necessary form work where required and fair finish to the exposed surfaces all as specified & directed. |
| 4 | All as per srl item No. 3.00 here-in-before but PCC 1:3:6 type C-2 as coping of poles. |
| 5 | S&F in repair 1100 Volts grade heavy duty cable, flat or circular PVC insulated aluminium stranded conductor of following sizes served with inner sheathing of PVC tapes and overall PVC sheathed in service connection from pole to Main Switch complete all as specified and directed. |
| 6 | All as per srl item No. 5 here in before but 4 sqmm twin core |
| 7 | All as per srl item No. 5 here in before but 6 sqmm twin core |
| 8 | All as per srl item No. 5 here in before but 10 sqmm twin core |
| 9 | Taking out existing unserviceable Street Light fitting / Flood Light fitting / High bay light fitting of any wattage from poles/high mast (including taking down of high mast fitting), dismantling the complete fittings of checking out the defects, trace out damage/ unserviceable parts like driver, wire,led lamp etc and clean thoroughly the complete set and re-fixing in its original position after replacing defective parts including testing complete all as specified and as directed by Engr-in-Charge.Notes:-(a) Spares shall be measured & paid separately as given here-in-after.(b) Contractor shall provide minimum 1 Electrician and 1 helperto carry out the repair / Maint work of security lights in day shift (900 Hrs-1700 Hrs) and they have to report AGE E/M yard for daily assingment/task(c) Contractor shall provide all tools and plants and minor spares such as Ladder, nuts & bolts, jumper wire, insulation tape etc required for doing the job related with electric supply including mobile phones for communication and will be fully responsible for safety and security of their man. |
| 10 | Supply only of Electronic Driver with Input Voltage 220 to 240 Volt and Output Voltage suitable for LED Light Fitting, complete all as specified and directed for the following types and capacities:- |
| 11 | 30 Watt to 50 Watt Street Light Luminaire |
| 12 | 60 Watt to 72 Watt Street Light Luminaire |
| 13 | 90 Watt and above Street Light Luminaire |
| 14 | 50 Watt to 80 Watt Flood Light Luminaire |
| 15 | 100 Watt to 150 Watt Flood Light Luminaire |
| 16 | 200 Watt Flood Light Luminaire |
| 17 | Supply only of PCB Card suitable for Multi LED Light Fitting complete all as specified and as directed. |
| 18 | 30 Watt to 50 Watt Street Light Luminaire |
| 19 | 60 Watt to 72 Watt Street Light Luminaire |
| 20 | 90 Watt and above Street Light Luminaire |
| 21 | 50 Watt to 80 Watt Flood Light Luminaire |
| 22 | 100 Watt to 150 Watt Flood Light Luminaire |
| 23 | 200 Watt Flood Light Luminaire |
| 24 | Supply Only of Surge Protection Device of capacity 10 KV Single Phase 50 Hz complete all as specified and as directed. |
| 25 | M&L for replacement of PVC insulated Multi Stranded Copper Conductor Cable 1.5 Sqmm 3 Core, Round Flexible for connection of Street Light Fitting complete all as specified and as directed. |
| 26 | S&F in replacement MCBs TPN 63 Amps,415 Volts16 KA all as specified and directed. |
| 27 | S&F in replacement MCBs SPN 32/40 Amps,220 Volts 10 KA all as specified and directed. |
| 28 | S&F in replacement MCBs Single Pole 6-32 Amps 10 KA ,220 Volts all as specified and directed. |
| 29 | Supply and fix in repairs LED Street Light fitting, of various capacity as mentioned under, in high pressure die cast aluminium housing with lens and toughened sealed glass cover with integrated constant current electronic driver, incl taking down existing fitting complete all as specified and directed and complying with the following specifications:-.(a) minimum efficacy 120 lumen/watt(b) CRI not less than 70, (c) THD < 10%(d) Power Factor not less than 0.95(e) Having in built short circuit and surge protection upto 5 kV(f) Colour temperature not less than 5700 degree K(g) Life not less than 50000 hours of operation(h) Weather protection grade: IP66(NOTE: (1) Contractor shall ensure that luminaire provided comply with the aforesaid specifications. No claim shall be entertained during currency of work..(2) Wire for electric connection shall be measured and paid separately) |
| 30 | 35/36 Watt Street Light Luminaire |
| 31 | 60 Watt Street Light Luminaire |
| 32 | 70/72 Watt Street Light Luminaire |
| 33 | 90 Watt Street Light Luminaire |
| 34 | Supply and fix in repairs LED Flood Light fitting, of various capacity as mentioned under, in high pressure die cast aluminium housing with lens and toughened glass cover with integrated constant current electronic driver,incl taking down existing fitting complete all as specified and directed and complying with the following specifications:-.(a) minimum efficacy 120 lumen/watt(b) CRI not less than 70, (c) THD < 10%(d) Power factor not less than 0.95(e) Having in built short circuit and surge protection upto 5 kV(f) Colour temperature not less than 5700 degree K(g) Life not less than 50000 hours of operation(h) Weather protection grade: IP66(NOTE: (1) Contractor shall ensure that luminaire provided comply with the aforesaid specifications. No claim shall be entertained during currency of work..(2) Wire for electric connection shall be measured and paid separately) |
| 35 | 50 Watt Flood Light Luminaire |
| 36 | 100 Watt Flood Light Luminaire |
| 37 | 120 Watt Flood Light Luminaire |
| 38 | 180 Watt Flood Light Luminaire |
| 39 | S&F in repair loop-in-loop out box of size 30x20x20cm made out from 1.6mm thick PVC sheet weather proof, dust and vermin proof with hinged door and locking arrangements with slanting cover on top and provision of 4 Nos aluminium bus bar of size 25mm x 2mm-4 Nos fixed on insulator and one MCB of capacity 6 Amps complete fixed on pole with and including suitable size MS flat iron clamps, nuts,bolts & washers etc complete all as specified and directed |
| 40 | Supply and fixing street light bracket made out of GI pipe light grade 32/40 mm bore of length upto 1.2 mtr bent to shape required with and including 2 Nos, 50 x 6 mm MS flat iron clamps with nuts, bolts, washer etc and applying one coat of aluminium paint to clamps including dismantling of old brackets complete all as specified and directed. |
| 41 | M&L for replacement of Galvanised Steel Tubing Pipe 40mm bore, light grade, length 0.60 mtr having 50 Cm with long Bends, Each for Incoming and Outgoing Cables, grouting in Cement Concrete, complete all as specified and as directed.NOTE : Cement Concrete will be measured and paid for separately under appropriate Item. |
| 42 | Supply, fixing, commisioning and testing of Nature timer switch control Street Lights complete with MCB,Power and Panel duly complete with wiring Model : SWADEEP-02EC 05KW IP or equivalent, single phase, max load 05 KW including taking down old unsv nature timer switch complete all as specified and directed.Note:- CA No & date of installations shall be painted/marked on all timer switch provided by the contractor. |
| 43 | Supply, fixing, commisioning and testing of Nature timer switch control StreetLights complete with MCB,Power and Panel duly complete with wiring Model : SWADEEP-02EC 12KW3P,or equivalentthree phase, max load 12KW including taking down old unsv nature timer switch complete all as specified and directed.Note:- CA No & date of installations shall be painted/marked on all timer switch provided by the contractor |
| 44 | Excavation in trenches n. exc. 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of underground cable and getting out in soft/loose soil complete all as specified and directed. |
| 45 | Returning, filling in excavated soil in trenches including spreading, leveling, watering and well rammingin layers not exceeding 25 cm thick complete all as specified and directed. |
| 46 | Removing of excavated soil to a distance not exceeding 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 47 | M&L Local sand dry, filling in trenches around under ground cable complete all as specified and directed. |
| 48 | M&L for providing of new sub class \"B\" Bricks, old size, well burnt laid flat dry for protection of under ground cable complete all as specified and directed. |
| 49 | All as Pere Srl Item No 28 above but for Laying only oldbricks complete all as specified and directed. |
| 50 | S&F in replacement GI pipe light grade 40 mm borefor cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc of following sizes complete all as specified & directed. |
| 51 | S&F in replacement GI pipe light grade 50 mm borefor cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc of following sizes complete all as specified & directed. |
| 52 | Taking out old unserviceable LT Cable any type and size from trenches or fixed on poles or through pipes/walls/laid under roads/paths/ drains/culverts complete all as specified and directed. |
| 53 | Supply, laying, jointing and testing XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable, heavy duty, conforming to IS - 7098 Part I - 1988 with aluminum conductor 1100 Volts of following sizes / grade laid in ducts or on walls, in trenches encased in GI pipe fixed to walls / laid under roads / drains / paths / culverts etc complete all as specified and directed. |
| 54 | 25 Sqmm 4 core |
| 55 | 16 Sqmm 4 core |
| 56 | 10 Sqmm 4 core |
| 57 | 10 Sqmm 2 core |
| 58 | S& F in repairs PVC MCB Enclosure box for DP & SP MCB complete all as specified and as directed |
| 59 | Lopping / prooning of tree branches upto the extend to obtain clearance all around the LT over head lines conductor upto 3 mtr from furthest conductor on pole including removing of cut branches and cleaning of site complete all as specified and directed.Note :-(a) The trees branches etc will be left as it is and will not be carried away by the contractor / DEL as the wood belongs to CEO / DEO and they will be responsible to lift the wood. (b)Prooning of all tree branches in one tree shall be measured as one Job.(c)Contractor will employ sufficient labour to complete the job with in time as directed.(d)Contractor will be responsible for any type of mis-happening / accident while prooning the trees. (e)Contractor supervisor will take proper shut down from MES installation before starting the work and clear it before resuming power supply . However full assistance will be provided by MES staff. (f) The contractor will provide proper tools and safety devices to his staff for prooning of trees. |
| 60 | Opening the binding wire from pin /shackle insulator on steel pole of any height for re-stretching the ACSR conductor, after re-stretching without kinks & bends, binding the pin /shackle insulator with appropriate size of aluminium binding wire complete all specified & directed by Engineer-in- charge. Note: Cost of binding wire deemed to be included in the quoted rate, No extra amount will be paid. |
| 61 | S&F in repair Astronomical time switch with USB key, 2 channel, 240 Volt AC, DIN mounting type suitable for street light operation complete all as specified an directed. |
| 62 | S&F in repairs Contactor 40 Amp, 3 module, 2 NO+2NC,Type 1, DIN mounting type suitable for street light operation complete all as specified and directed. |
| 63 | M&L for replacement of Pole Mounted Junction Box 254 x 180 x 111mm, having insulated and made out of thermoplastic Polycarbonate with glass fibre reinforced, rated for Degree ofIngress Protection IP 66 in accordance with IEC 60529, IK 07, weather proof for outdoor installation (with knockouts for cable entry) having Gasket Material shall be Polyurethane and the Gasket shall be internally embedded, Tested at 650°C, with Plastic Mounting Bracket, Din Rail, Mild Steel Flat Iron Clamp, Nuts, Bolts and Washers, with MCB SP 6 Amps, \"B\" Curve, 10 KA, complete all as specified and as directed. |
| 64 | M&L for cleaning and preparation of old painted surface of LT steel tubular pole complete and painting with one coat of aluminium paint including channels/brackets, street light brackets, cross arms and making Black/Red/Yellow & white strips with synthetic enamelled paint of 30cm height, each alternative strip upto 1.5 mtr height and writing pole numbers with yellow synthetic enamelled paint after making circular base with black synthetic enamelled paint and applying two coat of white wash on PCC coping complete all as specified and directed by Engr-in-charge. |
| 65 | M&L for earthing complete with galvanised or steel earth plate electrode of size 60cm x60cmx6mm thick burried directly in ground vertically (to a depth not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to GI wire 4mm dia with nuts, bolts, check nuts, washers, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick all around, top & bottom watering pipe 20mm bore of GI mediumgrade with funnel and wiremesh all as shown in electrical plate No. 5 of SSR -1991 Part I and connecting to earthing test point, main switch board and testing on completion including PCC chamber concrete 1:3:6 typeC-2 and RCC cover 75mm thick with MS TMT bar 8mm dia @ 150mm c/c both ways in cement concrete (1:2:4) type B-1 all as shown in electrical plate in No 5 of SSR(Pt-I)1991 complete all as specified anddirfected by Engineer-in-charge. |
| 66 | Notes:-Tenderers may note that amount as given in schedule of credit will be deducted from the total amount to worked out the net contract sum at the time of Acceptance of tender. |