| 1 | M&L for excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole in hard/dense soil, complete all as specified and as directed by Engr-in-Charge. |
| 2 | M&L for crushed stone sand cushioning to UG cable, provide with the layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable, complete all as specified and as directed by Engr-in-Charge.Note : Only punned thickness shall be measured. |
| 3 | Supply and layingof factory made, machine pressed, unreinforced, pre-cast concrete cable cover class LV type-1 flate size 250mm x 150mm x 40mm, complete all as specified and as directed by Engr-in-Charge. |
| 4 | Labour only for laying of old serviceable cable covers retrieved from excavation, complete all as specified and as directed by Engr-in-Charge. |
| 5 | M&L for returning, filling in, including spreading, leveling watering, and well ramming in layers not exc 25 cm in hard/dense soil, complete all as specified and as directed by Engr-in-Charge. |
| 6 | M&l for removing excavated material n.exc 50m and depositing where directed at a level exc. 1.5 cm above the starting point, complete all as specified and as directed by Engr-in-Charge. |
| 7 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanizedsteel strip or wire armoured, electric power cables with stranded aluminium conductor,1100 volts grade, of size 120 sqmm 3.5 core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable,complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 8 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanizedsteel strip or wire armoured, electric power cables with stranded aluminium conductor,1100 volts grade, of size 400 sqmm 3.5 core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable,complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 9 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanizedsteel strip or wire armoured, electric power cables with stranded aluminium conductor,1100 volts grade, of size 150 sqmm 3.5 core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable,complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 10 | M & L for earthing complete with Galvanized Steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level, connected to and including GI iron strip of size 32x6 mm flat by means of GI bolts, nuts, and washers, protected by 40mm bore Gl light grade ISI marked pipe upto and including test points. Earthing plate shall be surrounded by alternate layers 15cm thick of charcoal or coke and common salt all around bottom and top, 20mm dia Gl medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C2 (using 20mm graded crushed store aggrgate) including necessary form work, excavation and earth work in any type of soil, returning filling in and disposal of surplus soil to a distance not exceed ing 50 M, pit cover 40 mm thick made with RCC (1:2:4) type B-1 (using 20mm graded crushed store aggrgate) including TMT reinforcement 80 mm dia @ 75 mm C/C both way, MS handle of 12 mm dia, cover rest on MS angle iron frame 40x40x6mm embeded in concrete duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as as shown in electrical plate No-3 of SSR Part-l,complete all as specified and as directed by Engr-in-Charge. |
| 11 | Supply & Installation ,testing and Commissioning in replacement of LT Panel cubical type out door floor mounted weather proof totally enclosed, (CPRI approved) factory made and made out of 3.15 mm thick CRCA powder coated sheet and angle iron complete with bus bar of aluminium of suitable size for capacity 1600 Amps 3 Phase and Neutral 415 Volts 50 Hz mounted on epoxy type insulators with PCC flooring and angle iron base frame complete all as directed by the Engr-in-charge including fallowing accessories:- a) MCCB 4P 630 Amps Cap 4 Pole -1No for( I/C) b) Change over switch open execution type 630 Amp 4 pole - 01 No Outgoing:- a) 4 Pole MCCB250 Amp, 50 Hz, 415 V with rupturing capacity 36 KA-04 No b) 3 Pole MCCB160Amp, 50 Hz, 415 V with rupturing capacity 25 KA-01 Nos c) 3 Pole MCCB100Amp, 50 Hz, 415 V with rupturing capacity 25 KA-02 Nosd) Digital Volt meter with sellector switch(0-500V) - 02 Sete) Digital Amp meter with sellector switch with necessary CT (0-500A) - 02 Setf) LED indicating lamp - 02 SetNote : (i) The Make of Change over and MCCB considered are Havells/Standard/Indo Asian/HPL (ii) The rates deemed to be inclusive of suitable size copper wirinng/copper stripsfrom Main I/C MCCBs to Channge over switch, Change over switch to Main Bus bar and Bus Bar to Outgoing MCCBs complete all as specified and directed. (iii) The design of Panel, Make of complete accessories and drawing of the LT Panel should be submitted by the contractor for pre-approval from the Engineer-in-cfharge before order and execution at site. |
| 12 | Supply & Installation ,testing and Commissioning in replacement of LT Panel cubical type out door floor mounted weather proof totally enclosed, (CPRI approved) factory made and made out of 3.15 mm thick CRCA powder coated sheet and angle iron complete with bus bar of Aluminium of suitable size for capacity 1600 Amps 3 Phase and Neutral 415 Volts 50 Hz mounted on epoxy type insulators with PCC flooring and angle iron base frame complete all as directed by the Engr-in-charge including fallowing accessories:-a) MCCB 4P 630 Amps Cap 4 Pole -1No for( I/C), 4 Pole change over of capacity - 630Amps -01 a) 4 Pole MCCB250 Amp, 50 Hz, 415 V with rupturing capacity 36 KA-04 No d) Digital Volt meter with sellector switch(0-500V) - 02 Sete) Digital Amp meter with sellector switch with necessary CT (0-500A) - 02 Setf) LED indicating lamp - 02 SetNote : (i) The Make of MCCB considered are Havells/Standard/Indo Asian/HPL (ii) The rates deemed to be inclusive of suitable size copper wirinng/copper stripsfrom Main I/C MCCBs to Main Bus bar and Bus Bar to Outgoing MCCBs complete all as specified and directed.(iii) The design of Panel, Make of complete accessories and drawing of the LT Panel should be submitted by the contractor for pre-approval from the Engineer-in-cfharge before order and execution at site. |
| 13 | M&L for taking down old unserviceable feeder pillar box and supply and fix in replacement feeder pillar box of suitable size, with angle for grout in including PCC work of 415 volts with4 Nos aluminium bus bar, complete all as specified and asdirected by Engr-in-Charge. |
| 14 | Deduct Schedule of Credit of Rs (-) 43470.00 (Minus) as listed in Schedule \"A\" (Contd). Contract Sum shall be arrived after deducting the credit amount.Note :- Tenderers will not quote against this item being a firm amount. |