| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell pointwith 1.5 sq.mm FRLS PVC insulated copper conductor singlecore cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthingthe point with 1.5 sq.mm FRLS PVC insulated copper conductorsingle core cable etc. as required. |
| 2 | Group C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, singlecore cable in surface/ recessed medium class PVC conduit as required. Make-L&T/Finolex/Polycab |
| 4 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 5 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 6 | 4 X 10sq. mm + 2 X 6 sq. mm earth wire |
| 7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. Make-L&T/LEGRAND/ABB |
| 8 | Supplying and fixing suitable size GI/PVC box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. Make-L&T/LEGRAND/ABB |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.Make-L&T/LEGRAND/ABB |
| 10 | Supplying & fixing suitable size GI/PVC box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required. Make-L&T/LEGRAND/ABB |
| 11 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 12 | 8 way (4+24), Double door |
| 13 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Make-L&T/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 14 | Single Pole |
| 15 | Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. |
| 16 | 100 A TP&N |
| 17 | Supply and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. |
| 18 | 50 sq. mm |
| 19 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 20 | 3½ X 50sq. mm |
| 21 | Four Pole MCB 40/63 A Make-L&T/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 22 | Supplying ,fixing Connecting & Testing ,36W LED batten Make-Philips/Syska/Wipro/CG |
| 23 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%,suitable for operation withregulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019fani/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor singlecorecableandearthingetc.asrequired. |
| 24 | 1400mm,service value≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) |
| 25 | Supplying and fixing of 230VAC 1Ph.Two module steeped type fan electronic regulator |
| 26 | Supplying,Cutting of huck , painting and fixing ofMS Down conduit forinstallation of ceiling fan upto 5 to 8 feet |
| 27 | Supplying,Installation,Testing&CommissioningofFloodLight, powdercoatedpressuredie cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,Eas per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95,IP-66,IK-10,CRI>70,undervoltageandovervoltageprotection, EMI-EMCasper CISPR-15,lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained tilllife ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K/6500°K(AsperANSIBin), SDCM(Standard Deviation Colour Matching) <5,Maximumpowerconsumptionshouldnotmore than the specified rating and Fixture shall be ofrelevant BIS standardcompleteinallrespect i/cexternalconnectionswith1.5sq.mmFRLS/HFFR,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report andalltestingrequiredforLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsinkof aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 28 | Supplying,Installation,Testing&CommissioningofFloodLight 100 Watt Make-CROMPTON/PHILIPSE/WIPRO |