| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. a) Group C |
| 2 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 4 | a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required |
| 6 | a)5/6 A switch |
| 7 | b) 3 pin 5/6 A socket outlet |
| 8 | c) 15/16 A switch |
| 9 | d) 6 pin 15/16 A socket outlet |
| 10 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 11 | b) 6 Module (200 mm x 75 mm) |
| 12 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 13 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 14 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 15 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 16 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 17 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 18 | a) 8 way (4 + 24), Double door |
| 19 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 20 | a)Single pole |
| 21 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete, connections, testing and commissioning etc. as required. |
| 22 | a)63 A |
| 23 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 24 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 25 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 26 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/ DWC pipe as required. |
| 27 | Upto 35 sq. mm |
| 28 | Supplying of AC Ceiling Fan (1200 mm) Sweep with Socket Type Electronic regulator i/c wiring down rod of standard length (upto 30 cm) with all accessories etc., as required. Similar to makeCrompton Empower50 - 1 Star(ISI Marked) or its equivalent etc., as required as directed by Engineer-in-charge |
| 29 | Supplying of prewired LED tube lamp 20 W Essential Bright Batten Similar to make Philips Cat :BN170C LED20S-6500 SU L120 or Similar in make :Havels,Syska ,Bajaj,Crompton. etc as required and directed in Engineer-in-charge |
| 30 | Supplying, Installation, Testing and Commissioning of LED Bulkhead fitting 10W Similar to Havells HEXA 10 W Cat No. HEXAFT10WLED857SSYMBOPC or similar in bajaj, philips, crompton etc as suitable for indoor and outdoor applications as required and directed by Engineer-in-charge |
| 31 | Supplying and Fixing of LED Lamp 10W B22 of Make:Havells LED Adore10W or similar etc., as required for Batten Holder as directed by Engineer-in-charge |
| 32 | Supplying and Fixing ofexhaust fan 200 mm sweepLight Duty Make:- Havells Smart Ventilair White Colour or similar etc complete with all accessories etc. asdirected by Engineer-in-charge |
| 33 | Supplying and fixing of LED Mirror light fitting or LED Batten as required Similar to make Bajaj Cat :BCLSB 05 WHcomplete etc. as required. Similar inmake: Philips,Havels,Syska. ,Crompton |
| 34 | Supplying of following sizes of XLPE/PVC insulated armoured Aluminium conductor cable of 1.1 KV grade conforming to IS: 7098 (Part-I) and IS No. 1554 (Part-I) 1988 as applicable Make: CCI/ Gloster/ Havells/ Polycab/ Finolex as required as directed by Engineer-in-charge |
| 35 | a) 16sqmm x 4 core ( Panel to TPN DB) |
| 36 | SITC of indoor type, single front and floor mounted cubical panel board of size suitable size, preferably 1800 mm x 800 mm x 400 mm, G-Frame Panel Board with enclosures,non extendable type L.T - 3 phase 440V , 100A Incoming Panel Board and04 Nos. 63A Outgoing with load bearing member & gland plate of 2mm thick CRCA MS Sheet, non-load bearing members of 1.6mm thick CRCA MS Sheet, with suitable IP Rating Protection, with cable entry opening, terimination though cable alley, with copper bus bar of Current Density 1.0-1.2A/sqmm with 100A Capacity, earth and neutral busbar of suitable sizinghaving short circuit level of minimum 25kA with colour coded heat shrinkable PVC sleeves, Powder coacted painting, with copper control wiring , CT, Power Wiring, bus bar supports, shrouds,lugsand other accessories and connections as required in complete shape and directed by Engineer in Charge.100 Amps , 4 Pole MCCB, 25kA Breaking Capacity of Make: Legrand DPX3 160, Model Code: 4220 55 - 01 Nos63 Amps , 4 Pole MCCB, 25kA Breaking Capacity of Make: Legrand DPX3 160, Model Code: 4200 53 - 04 Nos.Meter Modules i/c indicator lamps, ON/TRIP lamps, Ammeter, Voltmeter, Amps/Volt Selector Switch , 03 Nos. CT Coil 150/5 A Class, Control Fuse - 01 Unit |
| 37 | Inter connection with PVC copper cable of suitable size etc. as required.-01 Job |
| 38 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in wall/ceiling clamping or in ground (75 cm below ground level) including excavation and refilling the trench if required but excluding sand cushioning and protective covering etc., complete as required. |
| 39 | a) 50 mm dia (OD-50 mm & ID-38 mm nominal) |
| 40 | SITC of 2 Ton 5 Star as per latest rating of BEE High Wall Mounted Inverter Split Type Air Conditioner unit complete with indoor unit (IDU), outdoor unit (ODU) single phase 230V ± 10% with R32/R410A refrigerant, copper condenser coil and Rotary compressor i/c providing required length of refrigerant copper pipe of std. sizeas per recommendation of manufacturer of Air Conditioner with insulation, cordless remote control, cutting and drilling holes on the wallwith smooth finish etcas required Similar to make Hitachi Model No.2.0TR CLASS HITACHI YOSHI 5400FXL FROST WASH INVERTER - R32 - RAS G522PCAISF - 5 STAR or its equivalent as per the direction of Engineer-In-Charge. |
| 41 | Supplying and Fixing of 5 KVA Voltage stabilizer suitable for 2.0 Ton Air Conditionerwith working Voltage of 140V to 270V, Make: PREMIER ECO 5 DBor its equivalent as required. |
| 42 | Providing and fixing of Pre-fabricated stand for keeping outdoor units of 1.5 Ton/ 2.0 Ton capacity Split type AC etc. as required. |
| 43 | Supplying and Fixing of MCB Protected Socket in Plastic enclosure for surface mounting with MCB 20 Amps Similarto Havells DBOXxCat No. DHDTCSN0251020 or its equivalent |