| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bellpoint with 1.5 sq.mm FRLS PVC insulated copper conductorsingle core cable in surface / recessed medium class PVCconduit, with modular switch, modular plate, suitable GI boxand earthing the point with 1.5 sq.mm FRLS PVC insulatedcopper conductor single core cable etc. as required. a) Group -C |
| 2 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required |
| 3 | Wiring for circuit/ submain wiring along with earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, singlecore cable in surface/ recessed medium class PVC conduit asrequired.a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4 | b) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 5 | Supplying and fixingtwo module stepped type electronic fanregulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 6 | Supplying and fixing suitable size GI box with modular plate andcover in front on surface or in recess, including providing andfixing 3 pin 5/6 A modular socket outlet and 5/6 A modularswitch, connections etc. as required. |
| 7 | Supplying and fixing suitable size GI box with modular plate andcover in front on surface or in recess, including providing andfixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 Amodular switch, connections etc. as required. |
| 8 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 9 | Installation, Testing, Commissioning of wall bracket /ceilingfittings of all sizes and shapes containing upto two GLS/CFL/LEDlamps per fitting, complete with all accessories includingconnectionsetc. as required. |
| 10 | Supplying of LED Bulkhead fitting 9 Watt Make: Pressfit, Model:Sierra - LED Code: L0216311, etc or its equivalent etc.as required. |
| 11 | Supplying of LED Recess Mounted Square Fitting, 18 Watt, cool white .Similar to Make: Havells, Model: OCTANE+ LED PANEL SQUARE, Code:LHEBAEP6IZ1W018 or equivalent in,etc or its equivalent etc. as required. |
| 12 | Supplying of LED batten fitting 20Watt 4 Feet Make: Pressfit, Code: L1301314, etc or its equivalent etc.as required. |
| 13 | Supplying of LED mirror light batten fitting 5 Watt 2 Feet Make: Havells, Model:LED PRIDE ULTRA/NXT Code: LHEXAZP7PN1W005, etc or its equivalent etc.as required. |
| 14 | Installation, testing and commissioning of ceiling fan, includingwiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cableetc. as required. |
| 15 | Supplying of A.C Ceiling Fan 1200MM BLDC Model: TECHNIX- BLDC ISI 5 STAR – 28W (W/O Remote) Make: USHA, etc or its equivalent etc.as required. |
| 16 | Installation of exhaust fan in the existing opening, includingmaking good the damage, connection, testing, commissioningetc. as required. a) Upto 450 mm sweep |
| 17 | Supplying of Exhaust Fan 200MM Plastic Body Make: USHA,Model:CRISP AIR VX EXH FAN, etc or its equivalent etc.as required. |
| 18 | Supplying & fixing suitable size GI box with modular plate andcover in front on surface or in recess including providing andfixing 25 A modular socket outlet and 25 A modular SP MCB, \"C\"curve including connections, painting etc. as required. |
| 19 | Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earthbar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/ RCCB/Isolator)a) 8 way, Double Door |
| 20 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) Single Pole |
| 21 | Supplying and fixing following rating, double pole, 240 V,isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. a)40 A |
| 22 | Providing Earthing with safe earthing electrode of galvanization 80 to 100 microns Type-19,length 1500 mm, 48 mm diaand inner space to be filled with crystalline conductive mixture including filling - up with electrodite 25 Kg (Back fill Compound) as required for safe earth electrode and providing masonry enclosure with cover plate having locking arrangement etc. as required. (Similar to ASHLOK make SEE brand safe earthing or equivalent) |
| 23 | Providing and laying earth connection from earth electrodewith 4.00 mm dia copper wire in 15 mm dia G.I. pipe from earthelectrode including connection with copper thimble excavation and re-filling as required |
| 24 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 25 | Removingand re-installation, testing and commissioning of following capacity split type Air Conditioner suitable for wall mounting/ floor standing complete i/c servicing the unit, cutting/ drilling holes on the wall for passing gas pipes , drain pipe, cable & extra refrigerant gas for making up for leakage from the unit etc through the walland cementing, painting to give an even look and smooth finish as required and as per the direction of E-in-C. 1.5/2/0 Ton Split AC |
| 26 | Providing and fixingof refrigerant copperpipes of following sizes (Suction & delivery) of split type AC i/c providing 2.5 sqmm 4 core electrical cable, PVC drain pipe, insulation, extra gas chargingto make up for length of pipe added and covering with PVC non adhessive tape over the insulation of refrigerant pipes and as per the direction of E-in-C.Refrigerant pipes of Sizes 1/2\" & 1/4\" |