| 1 | Taking down copper/aluminium point wiring (light. Fan, ocket or pwer) complete, including fixture and fittings such as switches,ceiling roses,pendants, regulators, sockets, lightfitting etc, removing materialsare as schedule of credit, and making good disturbed surfaces of walls, floors etc all as specified and directed. |
| 2 | Point wiring using approved colour coding as per IS, with stranded copper conductor 1.5 sqmm (nominal area), single core, flame retardant low smoke(FRLS), PVC insulated and unsheathed cable 1100 volts grade, ISI 694 marked TEC and FIA approved in and including PVC casing and caping/PVC conduit and its fittings ISI marked, with metal flush boxes suitable for modular/normal switch/sockets etc with earth dolly duly painted with two coats of anti corrosive paint over a coat of red oxide primer internally, incl covered with suitable module cover plate with frame including flame retardant low smoke (FRLS) PVC insulated unsheathed stranded copper conductor 1.5 sqmm (nominal are) single core cable as earth continuity conductor to common earth and connected to earth dolly complete all as specified for one light/fan point controlled by one switch & regulator. |
| 3 | All as per item No-2. and above but one 3 pin socket outlet, 5 mps on the same board with other switches, with cables 1.5sqmm all as specified and directed. |
| 4 | All as per item No-2. and above but one 3 pin socket outlet, 5 mps on the independent board with other switches, with cables 1.5sqmm all as specified and directed. |
| 5 | All as per item No 2 above but one 3 pin socket outlet 15 Amps independent with cables 4 sqmm size |
| 6 | Supply & fix switch piano, flush type single pole one way 5/6 amps all as specifiedand directed. |
| 7 | Supply & fix switch piano, flush type single pole one way 16 amps all as specifiedand directed. |
| 8 | Supply and fixing socket outlet 3 pin, 6ampsall as specifiedand directed. |
| 9 | Supply and fixing socket outlet 2 in 1 , 3 pin, 6 and 16 ampsall as specifiedand directed. |
| 10 | Supply and fixingswitch socket combination , 3 pin, 6 amps flush type universalall as specifiedand directed. |
| 11 | Supply & fix switch socket combination multipurpose flush type 2 in 1 type (3 and 3 pin ) 6/16 Amps, 230V, AC. |
| 12 | S & F in repairs bell push flush type5 amp |
| 13 | Supply and fixing stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc as required all as specified and directed. |
| 14 | Supply & fix modular switch1 way 6 amps , 1 module all as specifiedand directed. Make : Havells/Anchor or equivalent |
| 15 | Supply & fix modular socket 6A-2/3 pin combined 2 module all as specifiedand directed. |
| 16 | Supply & fix modular switch1 way 16 amps , 1 module all as specifiedand directed. Make : Havells/Anchor or equivalent |
| 17 | Supply & fix modular socket 6A/16 A-2/3 pin combined 2 module all as specifiedand directed. |
| 18 | Supply & fix modular fan step regulator, 120W- 2 module all as specifiedand directed. |
| 19 | Supply and fixing Buzzer, ding dong AC, 230 volts single pole all as specifiedand directed |
| 20 | Supply and fixingBell AC 230Volts single pole all as specifiedand directed. |
| 21 | Supply and fixing Lamp holder, PVC/polycaronate type with cord grip cap sitable for pendant fittings all as specified and directed. |
| 22 | Supply & fix ceiling rose surface bakelite 65x50mm two to three terminal all specified and directed. |
| 23 | Taking down FTL/LED light fittings any type or any watt all as specified and directed |
| 24 | Supply and fixing LED light fitting 1X20 watts, 220 V AC decorative box type with driver, holder including LED tubelight conneting upto three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed. |
| 25 | Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watts 220 volts, AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable sizecomplete all as specified and directed. |
| 26 | Supply and fixinground shape 15 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable sizecomplete all as specified and directed. |
| 27 | Supply and fixing LEDLuminaire 600mm X 600mm, 35/36 watts, 220 Volts, AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders and LED lamp suitable for roof ceilling including connecting up with drive three core flexible copper conductorcases of suitable size completeall as specified and directed. |
| 28 | Supply and fixing LEDlight fitting 1x9W/1x10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 29 | Taking down old unseriveable MCB DBs alongwith MCBs TPN/TP/SPN/SP, two pin earth plug of any size all as specified and directed. |
| 30 | Supply and fixing sheet metal enclosure for DB\"s Double door, single pole and neutral, 4 way including blacking plate with 200 amp rated bus bar, 240 volts fixed sunk/flush to the wall complete all as specified and directed. |
| 31 | Supply and fixing sheet metal enclosure for DB\"s Double door, single pole and neutral, 8 way including blacking plate with 200 amp rated bus bar, 240 volts fixed sunk/flush to the wall complete all as specified and directed. |
| 32 | Supply and fixing sheet metal enclosure for DB\"s Double door, single pole and neutral, 12 way including blacking plate with 200 amp rated bus bar, 240 volts fixed sunk/flush to the wall complete all as specified and directed. |
| 33 | Supply and fixing single pole and nutral enclosure with a two pin and earth plug and socket complete with one single pole 20 amps MCB complete all as specified and directed. |
| 34 | Supply and fixing sheet metal enclosure for DB\"s Double door, triplepole and neutral, 4 way including blacking plate with 200 amp rated bus bar, 240 volts fixed sunk/flush to the wall complete all as specified and directed. |
| 35 | S & F in repair MCB SP 5 to 32 Amps, 240 Volts, minimum 10 KA, \"C\" series rupturing capacity and to be housed in DBs catered here in before complete all as specified and directed. |
| 36 | Supply and fixing SPN 40-63 Amps , 240 volts,, 10 KA, C\" curve complete with connection, testing and commissioning all as specififed and directed. |
| 37 | Supply and fixing 415 Volts, 10KA \"B\" curve miniture circuit breaker (MCB) of Triple pole current carring capcity 25 to 63 Amps, in the MCB DB complte with connection testing and commissioning all as specified and directed . |
| 38 | S & F in repair MCB TPN 40 to 100 Amps, 415 Volts, minimum 10 KA, \"B\" series rupturing capacity and to be housed in DBs catered here in before complete all as specified and directed |
| 39 | S & F rigid non metallic PVC conduit 20mm dia exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hook etc all as specified and as directed |
| 40 | S & F rigid non metallic PVC conduit 25mm dia exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hook etc all as specified and as directed |
| 41 | Taking down old unseriveable sub-mainwiring 4.0sqmm and 6.0 sqmm all as specified and directed |
| 42 | M&L for sub main wiring with 2 runs of 4.0 sqmm PVC insulated unseathed copper cable multistandard 1100 volts. FRLS RM 301 grade with drawn in PVC casing caping and one run of 4 sqmm PVC insulated copper cable as earth continuity conductorin drawn in PVC casing capping all as specified and directed. Note: 3 runs of 4 sqmm copper cable and 1 run of PVC casingn capping will be measured as one unit i.e RM all as specified and directed. |
| 43 | M&L for sub main wiring with 2 runs of 6.0 sqmm PVC insulated unseathed copper cable multistandard 1100 volts. FRLS RM 301 grade with drawn in PVC casing caping and one run of 6 sqmm PVC insulated copper cable as earth continuity conductorin drawn in PVC casing capping all as specified and directed. Note: 3 runs of 6 sqmm copper cable and 1 run of PVC casingn capping will be measured as one unit i.e RM all as specified and directed. |
| 44 | M&L for earthing complete with Galvanised steel earth plate eletrode 60 cm x 60 cm x 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filled in alternate layers and electrode connections by usingGalvanised earth wire4.00mm diaconnected by means of bolts, nuts, check nuts and washer of galvanised iron or steel, provision of 15 mm dia GI pipe medium grade for protection of GI earth wire and 20mm dia GI pipe medium grade for watering arrangement and PCC (1:3:6) , type C1 chamber, MS funnel, wire mesh, 50 mm thick RCC 1:2:4, type B1earth pit cover with 6 Nos, 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance n exc 50 mtr, provision of charcoal and salt complete all as shown in electrical plate No 5 of schedule Part-I, incl taking down old one allas specified and directed. |
| 45 | Taking down old unseriveable PVC rectangular block any type/any sizecomplete all as specified and directed . |
| 46 | Supply and fixing PVC rectangular block for mounting, switches, sockets, fan regulator etc, with 3mm thick plastic laminated sheet cover of size 100mmx100mm and 50mm deep all as specified and directed. |
| 47 | Supply and fixing PVC rectangular block for mounting, switches, sockets, fan regulator etc, with 3mm thick plastic laminated sheet cover of size 175mmx100mm x 50mm deep all as specified and directed . |
| 48 | Supply and fixing PVC rectangular block for mounting, switches, sockets, fan regulator etc, with 3mm thick plastic laminated sheet cover of size 200mmx150mm x50mm deep all as specified and directed . |
| 49 | Supply and fixing PVC rectangular block for mounting, switches, sockets, fan regulator etc, with 3mm thick plastic laminated sheet cover of size 250mmx200mmx 50mm deep all as specified and directed. |
| 50 | Taking down old unseriveableceiling/exhaust fan, sealing cable end, dismentaling blades and remving fan and blades to store any size/capcity etc all as specified and directed . |
| 51 | Supply and fixingCeilingfans complete with bldades, down rods, electronic regulator and accessories, 230 volts, 1200mm sweep, min air delivery 210 CFM with service value 6.00 BEE, Five star rated with brushless direct current motor(BLDC) all as specified and directed . |
| 52 | Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300m sweep with, blades, and frame and louvers all as specified and directed.. |
| 53 | Supply and fix exhaust fan made of sturdy engineering plastic complete with louvers shutter, voltage 230V, 50Hz, RPM 1200, copper winding of sweep 300mm all as specified and directed . |
| 54 | M&L for shifting of ceiling fan/exhaust fan any size from one place to another place and making good disturbed susrface of wall all as specified and directed . |
| 55 | M&L for painting of ceiling fans in situ with one coat of synthetic enamel paint by spraying including filling cavities with filler, after cleaning dust etc. |
| 56 | Supply only of condenser 2.5 MFD of apporved make for ceiling fan complete. |
| 57 | Supply only of condenser 3.5/ 4 MFD of apporved make for echaust fan complete. |
| 58 | Supply only GI pipe light grade with all fitting and fixed complete for ceiling fan as down rod .75 cm long of 15 mm bore. |
| 59 | M&L in replacement for clamps and back plates fabricated from steel section conforming to Gde Fe 410-0 or Fe 310-0 includingnuts, bolts, washers, drilling holes for bolts in any shape or size for fixing ceiling fan complete weighing not more than 2Kg. |
| 60 | Taking down old unseriveable electric water heater any type/any size/capacity complete all as specified and directed. |
| 61 | Supply and fixing electric water heater, storage type steel body with copper inner tank and heating element upto 2KW capacity 25 liters, BEE 5 star rated complete with all accessories such as safety valve, thermostate, NRV, connection pice etc all as specified and directed. |
| 62 | S&F in replacement of PVC flexible 3 core 1.5 sqmm cable hrfr with copper con-ductor of size 16/0.20 mm from ceiling rose to fan including connection complete. |
| 63 | M & L for Inspection and maintenance of water heater (Geyser) of capacity, 25 ltrs to 50 litres including performing the following task at different locations of COSA Mil Stn. (a) Removing the heather plate assembly and descaling the heating element/pipe either by use of acid or equa cleaner to make it functional complete (b) Checking and setting of thermostat between 70 to 80 degree Celsius (c) Check working of NRV stop cock, pressure release valve and servicing carefully to make it functional (d) Repairing of earthing connection, power switch, socket connection replacement of indicator lamp to make it functional (e) Examine water leakage and rectifying as required and replacement of rubber washer gasket etc to make it functional(f) Inspect over flow vent pipe, safety valve and remove blockage if required to make it functional. |
| 64 | S & F in repairs of heating element of rating 1.5/2 KW to geyser 25 to 50 litres capacity, any type, make complete all as specified and as directed. |
| 65 | S & F in repairs of Thermostate for geyser of capacity 25 to 50 litres any type, make complete all as specified and as directed. |
| 66 | S & F in repairs inner copper tank made out of cold rolled pure electrode type copper sheet double lapped welded internally and hydraulically tested for geyser 25 litres capacity complete all as specified and as directed |
| 67 | S&F multi function safety valve suitable for Geysers 25/50 ltrs all as specified an as directed. |
| 68 | EXTERNAL ELECTRIC SUPPY:Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m deep and getting it out in soft/loose soil including forming bottom surface to required level for laying pipes/ cables all as specified. |
| 69 | Returning, filling in excavated soil including spreading, leveling, watering, well ramming in layers not exceeding 25cm all as specified. |
| 70 | Removing the surplus excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above starting point all as directed. |
| 71 | M&L cement concrete in foundation Type B1 (20mm graded stone) 1:2:4 in foundations all as specified |
| 72 | M&L for cement concrete 40 mm grade Type B2 , 1:2:4 in foundations all as specified |
| 73 | Supply and laying in replace of light grade GI pipe 40 mm dia with all fittings/fixtures or laying in trenches all as specified and as directed. |
| 74 | Supply and laying in replace of light grade GI pipe 80 mm dia with all fittings/fixtures or laying in trenches all as specified and as directed. |
| 75 | Supply and laying in replace of light grade GI pipe 100 mm dia with all fittings/fixtures or laying in trenches all as specified and as directed. |
| 76 | Supply and laying of DWC pipe, ISI marked of outer dia 50mm and inner dia 38mm with smooth internal and profiled external surface for non pressure under ground cable including all connected accessories like coupler,\"O\" Ring etc, for protection of cable complete all as specified and as directed. |
| 77 | ditto all as per item No above but outer dia 90mm inner dia 75mm |
| 78 | ditto all as per item No above but outer dia 110mm inner dia 95mm |
| 79 | M & L for disconnecting and taking down the existing burnt out UG cable of size 6 sqmm to 25 sqmm of any core along with DWC Pipe from trenches all as specified and as directed. |
| 80 | M & L for disconnecting and taking down the existing burnt out UG cable of size 35 sqmm to 95 sqmm of any core along with DWC Pipe from trenches all as specified and as directed. |
| 81 | M & L for disconnecting and taking down the existing burnt out UG cable of size 120 sqmm to 300 sqmm of any core along with DWC Pipe from trenches all as specified and as directed. |
| 82 | Supply and lay XLPE Insulated armoured heavy duty electrical cable with aluminium conductor, 1100 volts grade of size 6 sqmm 2 core all as specified and as directed. Note : Earthwork and other connected items like DWC/GI Pipe measured and paid separately |
| 83 | - ditto all as per item No 15 above but cable size 10 sqmm x 2 core |
| 84 | - ditto all as per item No 15 above but cable size 10 sqmm x 4 core |
| 85 | - ditto all as per item No 15 above but cable size 16 sqmm x 2 core |
| 86 | - ditto all as per item No 15 above but cable size 16 sqmm x 4 core |
| 87 | - ditto all as per item No 15 above but cable size 25 sqmm x 4 core |
| 88 | - ditto all as per item No 15 above but cable size 35 sqmm x 3.5 core |
| 89 | - ditto all as per item No 15 above but cable size 50 sqmm x 3.5 core |
| 90 | - ditto all as per item No 15 above but cable size 70 sqmm x 3.5 core |
| 91 | - ditto all as per item No 15 above but cable size 95 sqmm x 3.5 core |
| 92 | - ditto all as per item No 15 above but cable size 120 sqmm x 3.5 core |
| 93 | - ditto all as per item No 15 above but cable size 150 sqmm x 3.5 core |
| 94 | - ditto all as per item No 15 above but cable size 185 sqmm x 3.5 core |
| 95 | - ditto all as per item No 15 above but cable size 240 sqmm x 3.5 core |
| 96 | - ditto all as per item No 15 above but cable size 300 sqmm x 3.5 core |
| 97 | Supply and fixing aluminum lugs 10 sqmm to 25 sqmm. |
| 98 | Supply and fixing of lugs aluminum of sizes 35 sqmm to 70 sqmm. |
| 99 | Supply and fixing of lugs aluminum of sizes 95 sqmm to 150 sqmm. |
| 100 | Supply and fixing of lugs aluminum of sizes 240 sqmm to 300 sqmm. |
| 101 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material heat shrink type and accessories suitable for 3.5 core /4 core XLPE, Armoured.Al conductor cable of size 25 to 50 sqmm, indoor/out type |
| 102 | ditto all as per item No 34 above but cable size 70 to 120 sqmm |
| 103 | -ditto all as per item No 34 above but cable size 150 to 185 sqmm |
| 104 | -ditto all as per item No 34 above but cable size 240 to 300 sqmm |
| 105 | Supply and fix cable jointing kit for 1.1 KV grade cable for end termination joint complete with jointing material heat shrink type and accessories suitable for 3.5 core /4 core XLPE, Armoured.Al conductor cable of size 25 to 50 sqmm, indoor/out type |
| 106 | ditto all as per item No 38 above but cable size 70 to 120 sqmm |
| 107 | -ditto all as per item No 38 above but cable size 150 to 185 sqmm |
| 108 | -ditto all as per item No 38 above but cable size 240 to 300 sqmm |
| 109 | M& L for Painting of street light poles, by removing of old paint & applying one coat of red oxide metal primerand two coats of approved aluminium paint to steel tubular swaged pole, cross arm and service bracket complete all as specified and directed |
| 110 | M& L for Painting of RCCpole by Cement wash with Portland cement slurry to a smooth bodied opaque finish all as specified and as directed. |
| 111 | M & L for dismantling steel poles/ struts,any size, supply and errecting Steel tubular swaged poles with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 mtr long).Note :- Necessary earth work and PCC foundation, coping measured and paid separately. |
| 112 | M & L for dismantling concrete poles/ struts, any size, supply and errecting Prestressed concrete pole, 9.0 mtr long, 102mm x 172mm at top and l2mm x 279 mm at bottom, class 10 all as specified and as directed.Note : Necessary earth work and PCC foundation, coping measured and paid separately. |
| 113 | M&L for Copper strip 20 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground including taking down with all fitting and as directed. |
| 114 | M&L for Galvanized iron strip 32 x 6mm buried in ground or fitted with wall/Pole including taking down with all fitting and as directed. |
| 115 | Supply and fixing Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire |
| 116 | Dismantling and taking down any wattage or size of street light/flood light/post top lantern fittings for repair or replacement all as specified and directed. |
| 117 | S & F in repairs LED bollard light fitting 10W IP 66 sustainble performance all as specified and as directed. |
| 118 | Supply and fixing LED street light fitting 35/45 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete. |
| 119 | -ditto- all as per item No 51 above but 70 Watt |
| 120 | -ditto- all as per item No 51 above but 120 Watt |
| 121 | Supply and fixing LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp |
| 122 | -ditto- all as per item No 54 above but 100 Watt |
| 123 | -ditto- all as per item No 54 above but 120 Watt |
| 124 | Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete. |
| 125 | -ditto- all as per item No 57 above but 40 Watt |
| 126 | Supply and fixing all in one series solar street light 24W High efficiency mono crystaline solar PV modules. lituium ferro phosphate battery with in built BMS technology, High efficeincy LED, MPPT solar charge controller and aluminium extruded body, authomatically control the dimming and brigtness of light all as specified and directed. |
| 127 | Supply and Fixing of Street Light fitting GI bracket suitable for fixing of street light fitting by fabricating the size of25/32 mm dia Light grade GI pipe of length 1.2 mtr and suitable bend,complete all as specified and directed. |
| 128 | Supply and fix LT Junction box for street lights, Sheet Moulding Compound (SMC), hinged door type and locking arrangenment, off white colour of size 140 x 140 x 95 mm (internal daimention) comprising 02 Nos Al busbar of adequate capacity including suitable size MS clamps, all as directed. |
| 129 | -ditto all as per item No 61 above but SMC box size 240x130x95 |
| 130 | Supply,fixing,connecting and testing on load change over switch, 4 pole, 415 volts, AC with SS enclosure, side handle operated including necessary electrical connection of 125 Amps capacity complete all as specified and directed. |
| 131 | Disconnecting and taking down the existing oldunserviceable MCCB/ MCB for existing Feeder piller box. |
| 132 | S & F MCCB 3 pole 415 Volts fixed type 25 to 100 Amps with breaking capacity 16 KA all as specified and directed |
| 133 | S & F MCCB 4 pole 415 Volts 16 KA 16 A to 63 Amps all as specified and directed. |
| 134 | S & F MCCB 4 pole 415 Volts 16 KA 100Amps all as specified and directed |
| 135 | S & F MCCB 4 pole 415 Volts 16 KA 125Amps all as specified and directed. |
| 136 | S&F MCCB 4 pole 415V adjustable type 160 Amps with breaking capacity 36 KA . |
| 137 | S&F MCCB 4 pole 415V adjustable type 200 Amps with breaking capacity 36 KA . |
| 138 | S&F MCCB 4 pole 415V adjustable type 250 Amps with breaking capacity 36 KA |
| 139 | S & F 415V 10 KA MCB TPN/FP 16 to 32 Amps capacity |
| 140 | M&L for wiring with 1100 volt grade, 2 runs of 1.5 sqmm single core FRLSH PVC insulated unsheathed multi stranded copper conductor cable drawn through rigid PVC conduit from street light in box/looping box to street light fitting along with 1.5 sqmm single core FRLSH PVC multi stranded copper conductor cable green in colour as contineous earth wire complet all as specified and as directed . |
| 141 | M&L for earthing complete with galvanised steel earth plate electrod 60cmx60cmx60mm thick buried directly in ground ( each pit not less than 2.25 mtr below ground level) with Top edge of earth plate not less than 1.5 mtrbelow normal ground level, including provision of gakvnised earth strip 32x6 mm connected by means of bolts, nuts, check nuts and washers of galvanised iron steel, provision of 40mm dia GI pipes medium grade for earth wire protection connected from earth plate electrode to main switch board, provision of 15 mm dia GI pipe perforated medium medium grade for glatering arrangement and PCC 1:3:6 type C1 chamber, MS funnel, wire mesh, 50 mm thick RCC 1:2:4 type B1 for earth pit. Cover with 6 No\"s 8 mm dia high strength deformed steel TMT bars on both ways, including test terminal block made of gun metal or phosphorous bronze 75x75x25 mm and drilled and screwed including 3 nos 8 mm dia, 25 mm long at hex head screw also necessary excavation in any type of soil, returning, filling in, removal of surplus soil to a distance n. exc. 50 mtr, provision of char coal and salt complete all as shown in electrical plate No 3 of scedule Part-1 of 2009 all as specified, directed and Testing on completion. |
| 142 | M&L for painting of LT Panel of any type ( indoor/outdoor) by removing of old paint & applying one coat of red oxide metal primerand two coats of approved eanmel paint to LT Panel complete all as specied and directed. |
| 143 | Servicingof solar power generating PV modules for security lighting system, mounted on poles of approx height 5.0mtr by cleaning the photo voltaic panel using soft cloth and cleaning agent, adjusting to the proper direction and preperation of old paited surfaces of Galvanized iron pole painting with two coats of aluminium paint on poles and on all iron surfaces/steel surfaces,complete all as cpecified..Note- replacing the defective parts/components required will be measured and paid seperately .under relevant items as \"supply only\", |
| 144 | S & F in repair tubular lead battery 12V,100 AH. |