| 1 | Dismantling of old unserviceable/ ACSR conductors of any size from overhead lines, poles by removing binding wire, service wire, cables and removal from site complete all as specified and as directed. |
| 2 | Dismantling corroded rusted /defected cross-arms of M.S. channel or angle of any sections Complete all as specified and as directed. |
| 3 | Dismantling of oldunserviceable insulator of any size/type complete all as specified and as directed. |
| 4 | M&L for Cross arms, bracings, supports, clamps, eye hook and back plates fabricated from structural steel sections including pole clamps, stay clamps, D clamps nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and including two coats of aluminuum paint over a coat of red oxide primercomplete all as specified and as directed. |
| 5 | Dismantling of old existing unserviceable steel pole 7.5 to 9.5 metres long of any type from the PCC foundation, coping and including carefully taking down existingACSR conductor, cables, Street light, Security light fitting, GI brackets, looping boxes, stay assembly of any type & patten etc, after disconnection of electric supply by using necessary T&P/crane/ any mechanical methodwill be applied and debris disposal upto distance not exc 100 metre at defence landcomplete all as specified and as directed. |
| 6 | Supplying, erecting & fixing in true vertical position, steel tubular swaged poles 9 metre long, pole weight approximately 113 kgs, pole should be in one piece only and smooth finishing, ISI markedcomplete with all accessories such as cast iron base plate, finial taper plug, bolts, nuts, screws, washers and drilling of holes for continuous GI earth wire as specifiedtype 410 SP-28 ) including painting of pole with two coats of aluminiumpaint over a coat of red oxide zinc chrome primer from top of the pole to 1.5m above the bottom of the pole and painting with two coats of black bituminous paint over a coat of red oxide zinc chrome primer upto 1.5m from bottom of the pole including numbering of poles complete all as specified and as directed.Note: PCC 1:3:6 type C2 for foundation and 1:2:4 type B1 as in coping including Painting work deemed to be included in quoted rate. |
| 7 | M&L for Stay assembly complete with 16mm dia Rodfor standing a pole or support to any heavy eqpt/ Spare parts/ Heavy channel accessories etcas shown in electrical plate No. 1 diagram including loop type insulator, stay clamps, ,including all excavation/earth work in any strata and returning filling, removal of surplus soil, PCC 1:3:6 type C1 and 1:2:4 type B1 for required value completeall as per site requirement includind dismantling of old stay assembly complete all as specified and as directed. |
| 8 | S&F in repairs, three phase IP-65 GRP junction box of Minimum size 182X180X111mm with terminals for incoming and outgoing connector/terminals and comprising of one No.MCB SP 6 Amps, 240V, 10KA, \"C\" Series and including MS flat iron clamps of size 25X5mm thick -02 Nos, nuts, bolts & washers etc for fixing on PCC/Steel tubular pole/ wall surface etc complete all as specified and as directed.Make:- Sintex/Hensel/Cape |
| 9 | M &L for preparing surfaces of existing LT steel tubular poles 9 m long including scrapping, brushing down old paint with emery paper and applying one coat of aluminium paint including cross arms, street light brackets etc and making strip upto 1.5m above ground level by black/yellow paint in alternate layers with numbering of poles complete all as specified and as directed. |
| 10 | M &L for preparing surfaces of existing LT feeder pillar panel indoor type double door/single door both side open of size Upto1800mmx1400mmx1200mm capacity, canopy/flat with Two coat of synthetic enamel paint as per existing colour of panel including all accessories after cleaning, scraping, and filling of cavities complete internal and external complete all as specified and as directed. |
| 11 | M &L for preparing surfaces of existing LT feeder pillar panel Outdoor type double door/single door both side open of size Upto1800mmx1400mmx1200mm capacity, canopy/flat with Two coat of synthetic enamel paint using Spray method as per existing colour of panel including all accessories after cleaning, scraping, and filling of cavities complete internal and external complete all as specified and as directed. |
| 12 | M&L for repairs/replacementof unserviceable/broken hinges-08 Nos fixed with lead-04 Nos with New hingesinany type feeder pillar panel/ bus bar door indoor/outdoor type of size Upto1800mmx1400mmx1200mm capacity, canopy/flatwith brazing/welding , including painting two coat of synthetic enamel paintas per existing colour of panelincluding all accessories after cleaning, scraping, and filling ofcavitiescomplete internal and external complete all as specified and as directed. |
| 13 | Fixing only security light/Street light of capacity upto 120 watt LED fitting upto 12 metre height from the normal ground level complete all as specified and as directed.Note: Items will be issued from MESStore Yard free for fixing only. |
| 14 | S&F GI bracket, pipe of size 32 mm dia mediumgrade of 1.2 metre long bent to shape hot or cold suitable for street light fitting and making the one end of GI pipe bracket suitable for fixing of any type street light fitting and shall be fixedon PCC & Steel poles/on wall surfaces and including suitable fabricate MS flat ironclamps of 40X6 mm thick-02 Nossuitable for fixing any place of poles with nuts, bolts & washers or grouting on wall etc and painting with one coat of aluminium paint over a coat of red oxide primer Including taking down old one complete all as specified and as directed. |
| 15 | M& for PVC conduit heavy duty of size 20 mm diafrom looping box to Street light connector holding inMS clamp of size 25X2 mm thickat every one metre used in each pole 04 Nos of clamps with necessary nut, bolts and washers etc and including PVC sheathed three core multistranded copper conductor cable of size 1.5 sqmmfrom looping box to light fitting connector including dismantling of old conduit with wire complete all as specified and as directed. |
| 16 | Excavation in trenches not exc 1.50 m wide and not exc 1.50 m deep for foundation, laying of pipe or for shafts, wells cesspits, man holes, pier holes, laying of cable etc not exc 10 Sqm on plan and n exc 1.5m in depth and getting out in soft / loose soil complete all as specified and as directed. |
| 17 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc. 25 cm in soft / loose soil complete all as specified and as directed. |
| 18 | Removing excavated soil to distance not exc. 50 m and depositing where directed at a level not exc. 1.5 m above the starting point etc complete all as specified and as directed. |
| 19 | Taking out old underground LT XLPE / PVC cable of size 300sqmm 3.5core from trenches / wall / roof / road / pipe / pole / DB including taking out of brick layer of cable protection and relaying the same in existing or new location complete all as per specified and as directed by Engr-in-Charge.Note: For Item No 19 to 27 Earth work shall be measured and paid separately under respective item. |
| 20 | All as per item No 19 here in before but for size 240Sqmm 3.5 core complete all as specified and as directed. |
| 21 | All as per item No 19 here in before but for size 95 Sqmm 3.5 core complete all as specified and as directed. |
| 22 | Labour only for laying of LT UG cable of size 400 Sqmm 3.5 core complete all as specified and directed by Engr-in-charge.Note:-Cable will be issued from MES store Yard for Free for Laying only. |
| 23 | All as per item No 22 here in before but for size 300 Sqmm 3.5 core complete all as specified and as directed.Note:-Cable will be issued from MES store Yard for Free for Laying only. |
| 24 | All as per item No 22 here in before but for size 150 Sqmm to 185sqmm,3.5 core complete all as specified and as directed.Note:-Cable will be issued from MES store Yard for Free for Laying only. |
| 25 | All as per item No 22 here in before but for size 95Sqmm to 120sqmm,3.5 core complete all as specified and as directed.Note:-Cable will be issued from MES store Yard for Free for Laying only. |
| 26 | All as per item No 22 here in before but for size 50Sqmm to 70sqmm,3.5 core complete all as specified and as directed.Note:-Cable will be issued from MES store Yard for Free for Laying only. |
| 27 | All as per item No 22 here in before but for size 10Sqmm 3.5/4 core to 35sqmm,3.5 core complete all as specified and as directed.Note:-Cable will be issued from MES store Yard for Free for Laying only. |
| 28 | M&L for sub class ‘B’ old size well burnt brick laid flat in trenches with length of brick perpendicular to length of cable, over the cable forprotection of LT cable complete all as specified and as directed. |
| 29 | M&L for sand cushioning with dry river sand in trenches for cushioning of underground cable including spreading, leveling, punning down the thickness of sand upto 18cm and consolidated complete all as specified and as directed.Note: Punned thickness of sand cushioning will be measured and paid. |
| 30 | M& L for straight through type cable joint kit, for 1.1 KV epoxy PVC /XLPE cable with all jointing materials & accessories suitable for cable of size 6Sqmm 3.5 or 4 Core complete all as specified and as directed. |
| 31 | M& L for straight through type cable joint kit, for 1.1 KV epoxy PVC /XLPE cable with all jointing materials & accessories suitable for cable of size 10Sqmm to 16Sqmm 3.5 or 4 Core complete all as specified and as directed. |
| 32 | M& L for straight through type cable joint kit, for 1.1 KV epoxy PVC /XLPE cable with all jointing materials & accessories suitable for cable of size 25Sqmm to 35Sqmm 3.5 or 4 Core complete all as specified and as directed. |
| 33 | M& L for straight through type cable joint kit, for 1.1 KV epoxy PVC /XLPE cable with all jointing materials & accessories suitable for cable of size 50Sqmm 3.5 or 4 Core complete all as specified and as directed. |
| 34 | M& L for straight through type cable joint kit, for 1.1 KV epoxy PVC /XLPE cable with all jointing materials & accessories suitable for cable of size 70Sqmm 3.5 or 4 Core complete all as specified and as directed. |
| 35 | M& L for straight through type cable joint kit, for 1.1 KV epoxy PVC /XLPE cable with all jointing materials & accessories suitable for cable of size 95Sqmm 3.5 or 4 Core complete all as specified and as directed. |
| 36 | M& L for straight through type cable joint kit, for 1.1 KV epoxy PVC /XLPE cable with all jointing materials & accessories suitable for cable of size 120Sqmm to 150Sqmm 3.5 or 4 Core complete all as specified and as directed. |
| 37 | M& L for straight through type cable joint kit, for 1.1 KV epoxy PVC /XLPE cable with all jointing materials & accessories suitable for cable of size 185Sqmm 3.5 or 4 Core complete all as specified and as directed. |
| 38 | M& L for straight through type cable joint kit, for 1.1 KV epoxy PVC /XLPE cable with all jointing materials & accessories suitable for cable of size 225Sqmm 3.5 or 4 Core complete all as specified and as directed. |
| 39 | M& L for straight through type cable joint kit, for 1.1 KV epoxy PVC /XLPE cable with all jointing materials & accessories suitable for cable of size 240Sqmm 3.5 or 4 Core complete all as specified and as directed. |
| 40 | M& L for straight through type cable joint kit, for 1.1 KV epoxy PVC /XLPE cable with all jointing materials & accessories suitable for cable of size 300Sqmm 3.5 or 4 Core complete all as specified and as directed. |
| 41 | M& L for straight through type cable joint kit, for 1.1 KV epoxy PVC /XLPE cable with all jointing materials & accessories suitable for cable of size 400Sqmm 3.5 or 4 Core complete all as specified and as directed. |
| 42 | M&L for fault finding on 1100 Volt LT cables in trenches ofsize upto 400 sqmm 3.5 core and any length with fault detective(fault finding) machine by thumbing method andinjection suitable high voltageproper fault finding equipment and all as manufactures instructions and including necessary excavation, returning filling, removing surplus soil, sand, existing bricksetc where find the location of cable faulty complete all as directed by Engineer-in-charge. Note: LT joints, additional LT cable etc will be measured and paid separately under respective item. |
| 43 | M& L for manual boring under roads/hard standing using required T&P without disturbing the top surface of the road, inserting GI pipe n exc 80 mm dia for cable protection complete all as specified and as directed. Note : - GI pipe will be measured & paid separately. |
| 44 | Supply and laying GI tubing 40mm bore light grade with fittings laid in trenches, on pole and road crossing for protection of LT underground cables complete all as specified and as directed. |
| 45 | Supply and laying GI tubing 50mm bore light grade with fittings laid in trenches, on pole and road crossing for protection of LT underground cables complete all as specified and as directed. |
| 46 | Supply and laying GI tubing 80mm bore light grade with fittings laid in trenches, on pole and road crossing for protection of LT underground cables complete all as specified and as directed. |
| 47 | Supply, installation, testing and commissioning Outdoor type LT Feeder Panel of size 1800 x 1300 x 600 mm,Base Dimension MS Iron Angle 50 x 50 x 6 x 450 mm (4 Nos)3 phase ,4 wire ,415 volts, AC ,50Hz ,outdoor cubical type, sloping canopy top roof, floor mounted, free standing, dust and vermin proof, air ventilation with IP-54 made out of 3.15 mm thick CRCA sheet and suitable sizedangle iron and flat duly epoxy powder coated with seven tank process and any manufacturer shall befollowed CPRI norms and as approved by GE. Panel shall have front and rear opening, locking arrangement, cable alleys, bus bar chamber and switch gear compartment ,hinged double door with rubber gasket, bottom cable entry holes for incoming and outgoing cables, earthing terminals, affix danger notice plate, aluminium bus bar of size 950 Amp (100X10 mm RYBN) with Epoxy insulators and duly covered with heat shrink sleeves colour coded , housed in a separate bus bar chamber, see through glass and control wiring with copper conductor cables of adequate size and length, incoming and outgoing MCCBs shall have extended bus bar links and civil work/PCC foundation as per site requirement and removing of old unserviceable item from existing location after disconnecting of existing cables complete all as specified and directed including comprising of following:-(a) MCCB 630 Amps, FP, 50KA,415 volts,50Hz- 01 No(b) MCCB 400 Amps, FP, 36KA,415 volts,50Hz- 03 No(c) MCCB250 Amps, FP,36KA,415 volts,50Hz- 04 Nos(d) MCB TPN 40Amps, FP,16KA,415 volts,50Hz- 02 Nos(e) Analogue time switch (Daily time switch) with suitable power contactor 63 Amps ML-2 type,3Phase,415 volts, Auto/Manual operating switches -01No\"s (f)Multifunction meter -01 No (g) LED phase indication lamps RYB-01 set (h)Aluminium bus bar TPN950 Amps (04 Nos) rating -01 setNote: - The contractor shall be submitting drawings (General& circuit lay out drawings) the Accepting Officer/Engineer -in-charge before procurement. |
| 48 | Fixing only MCCB 4 pole 200 Ampsbreaking capacity 36KAadjustable typebased on LT panel/feeder pillar including dismantling/taking down existing serviceable MCCB complete all as specified and as directed. |
| 49 | Fixing only MCCB 4 pole 350/315 Ampsbreaking capacity 36KAadjustable typebased on LT panel/feeder pillar including dismantling/taking down existing serviceable MCCB complete all as specified and as directed. |
| 50 | Fixing only MCCB 4 pole 400 Ampsbreaking capacity 36KAadjustable typebased on LT panel/feeder pillar including dismantling/taking down existing serviceable MCCB complete all as specified and as directed. |
| 51 | Fixing only MCCB 4 pole 630 Ampsbreaking capacity 50KAadjustable typebased on LT panel/feeder pillar including dismantling/taking down existing serviceable MCCB complete all as specified and as directed. |
| 52 | M&L for Earthing complete with GI earth plate electrode of size 60cm x 60cm x 6mm burieddirectly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers etc and connected to GI strip 32mmx6mm upto 7.5 metre by means of bolts, nuts, check nuts and washers made of galvanised iron and protected by light grade 15mm dia GI pipe connected to main control board and GI pipe medium grade 20mm bore for watering and including funnel, wire mesh, charcoal salt etcRCC pit cover flush to earth pit 50mm thick reinforced with 8mm TMT bar 100mmC/C and PCC chamber pit with PCC (1:2:4) type B1 (using 20mm graded crushed stoneaggregate), excavation and earthwork disposal of surplus soil to distance not exceeding 50 metre) and testing after completion completeall as specified and shown on plate No 3 of SSR Part-I 2009 including dismantling of old earthingcomplete all as specified and as directed. |
| 53 | M & Lfor earthing in replacement complete with galvanised steel earth plate electrode 60 Cm X 60 Cm X 6 mm buried directly in ground vertically to a depth not less than 2.25 mtr deep below ground level with top edge of earth plate at a depth not less than 1.5 m below normal ground level connected to galvanised earth lead wire 4.0 mm dia by means of bolts, check nuts and washers, galvanised steel and protected by GI pipe 15 mm bore light grade & connected to main switch board or main control board as directed and including concrete pit in PCC (1:3:6) type C1, precast RCC (1:2:4) type B1 cover slab 30 cm X 30 cm X 5 cm with 10mm dia TMT bars 8 cm C/c both ways andone handle for lifting made out of 8 mm dia TMTbar, funnel, wire mesh, 20mm bore galvanised iron pipe (medium grade) for watering, charcoal or coke and salt in alternative layers, necessary excavation and earth work in any type of soil and including necessary testing complete all as shown in Electrical Plate No 3 of SSR part -I including dismantling of old earthing complete all as specified and as directed. |