| 1 | Design, supply, installation, testing & commissioning of Electrical distribution panel (including supply and installation of glands and APFC panel and termination of all type CNG cable as per site requirements) as per specifications & single line diagram (Drg. No. MNGL/PANEL/01, ) |
| 2 | Electrical Emergency Panel for CNG Station 125 A |
| 3 | UPS /LDB Panel/Online Station CNG Panel |
| 4 | Supply, laying , testing and termination ofPVC insulated & sheathed, 1100V grade,armoured ,Copper conductor cable of follwing sizes & type in surfacetrench./on wall/structural surface/in G.I. Pipes/conduit as specified / required as per the tender document, technical specification, drawings and direction of EIC. |
| 5 | 4 x 35 mm2 YRY |
| 6 | 4 x 25 mm2 YRY |
| 7 | 4 x 2.5 mm2 YRY |
| 8 | 2 x 2.5 mm2 YRY |
| 9 | 16 mm2 PVC insulated green colour copper conductor single core wire for earthing connections to equipments including supply, installation of lugs and cable connections to all type of CNG equipments as per site requirements |
| 10 | Supply & laying of Copper Strip (for earthing) of following sizes, clamped to wall/structure& laying in trenches (as reqd.) including termination at the required points by welding/nut bolts including all earthing material as per the tender document, technical specification, drawings and direction of EIC. |
| 11 | 25 x 3 mm |
| 12 | Supply & laying of GI Strip (for earthing) of following sizes, clamped to wall/structure& laying in trenches (as reqd.) including termination at the required points by welding/nut boltsincluding all earthing material as per technical specification & drawings. |
| 13 | 25 x6 mm |
| 14 | Construction of Copper earthpit |
| 15 | Construction of Earthpits as per the drawing using GI pipe medium (class-B) 3M long, Copper plate of 600x600x3 mm size including supply of all material required and testing ofearth pits as per latest version of IS:3043, specification and drawing. |
| 16 | Construction of G.I. earthpit |
| 17 | Construction of Earthpits as per the drawing using GI pipe medium (class-B) 3M long,including supply of all material required and testing ofearth pits as per latest version of IS:3043 & specification & drawing. |
| 18 | Supply, installation and commissioning of 3 KVA UPS |
| 19 | a)3KVA, non-redundant, single, manufacturer\"s standard design UPS System suitable for input power supply voltage of 415V , +10%, -20%, Three phase and output voltage of 230V +- 1% single phase with 2 hours battery back-up (VRLA maintenance free 2.0V battery) and all interconnecting cables between UPS & Battery Bank,Stands for UPS and battery etc. 3 KVA UPS system comprising of 13KW rectifier/Charger and 200Ah, 2.0 volt per battery(VRLA type) |
| 20 | Supply & laying of perforated G.I.trays of following sizes as per technical specification. |
| 21 | 600 mm wide |
| 22 | Supply & laying of HD PVC. Pipes buried for drainage/other work. |
| 23 | 100 mm NB |
| 24 | PCC |
| 25 | Providing, laying in position, construction and handing over of PCC in foundations, substructure, superstructure and under floor, etc complete in all respects as per scope of work, detailed construction drawings, technical specifications and direction of EIC. |
| 26 | a) PCC 1:2:4[1 Cement: 2 coarse sand : 4 stone aggregate 20 mm nominal size] |
| 27 | Electrical & Water Pit chamber Construction: |
| 28 | Providing and construction of Electrical Cable Pit of size 600x600x900 including PCC to be carried out at base, brickwork, SFRC cover and its frame over the chamber, leaving space for GI pipe fixing complete in all respect as per technical specification, construction drawings and direction of Engineer In Charge |
| 29 | Earth work in excavation/site grading |
| 30 | Earth work in excavation in all kinds of soil except rock in any plan dimension up to 3.0 M depth including disposal of excavated earth up to any lead in all conditions, and disposal of surplus and unserviceable earth. Soil to be leveled and neatly dressed complete in all respect as per scope of work, detailed construction drawings, as per technical specifications and directions of the Engineer-in-charge. |
| 31 | Supply, installation and termination of crocodile clamp with insulation for LCV/HCV earthing |