| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthingthe point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. (Make: Polycab/ Finolex/ L&T) |
| 2 | Group C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (Make: Polycab/ Finolex/ L&T) |
| 4 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 5 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 6 | 2 X6sq. mm + 1 X 6 sq. mm earth wire |
| 7 | 2 X10sq. mm + 1 X 6 sq. mm earth wire |
| 8 | 4 X 10sq. mm + 2 X 6 sq. mm earth wire |
| 9 | Supplying and fixing suitable size GI/PVC box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required Make- L& T/ABB/LEGRAND /INDOASEAN |
| 10 | Supplying and fixing suitable size GI/PVC box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. Make- L& T/ABB/LEGRAND /INDOASEAN |
| 11 | Supplying & fixing suitable size GI/PVC box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required. Make- L & T/ABB/LEGRAND /INDOASEAN |
| 12 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) Make- L& T/ABB/LEGRAND /INDOASEAN |
| 13 | 4 way (4 + 12), Double door |
| 14 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Make L&T/ABB/C&S/Legrand/Hagger/Schneider |
| 15 | Single Pole MCB Make-L&T/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 16 | Double Pole 32/63 Amp MCB Make-L&T/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 17 | Triple Pole 63 Amp MCB Make-L&T/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 18 | FP MCB 40/63 A Make-L&T/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 19 | 4 Way Enclosure Metal Box |
| 20 | 2 Way Enclosure Metal Box |
| 21 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 22 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 23 | LED Batten light (System lumen efficacy ≥105 85%, Operating voltage AC 140 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3,Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BISstandard.Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete inallrespecti/c external connectionswith1.5sqmm FRLS/HFFR,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy≥105 <120lm/Watt output . LM79 & LM80 Test report andalltestingrequiredforLED fixtures as per BISshall be submitted.Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermalmanagement:heatsinkofaluminiumhousing such that LED junction temperature shall not rise above 90°C). |
| 24 | Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) watt Make: Wipro/ Philipse/CG/Polycab/) |
| 25 | LED Panellight 2x2ft., (System lumen efficacy>135 lm/Watt)Supplying, installation, Testing & Commissioning of Panellight 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirementwith Driver efficiency >85%, Operating voltage AC140-270 Volt,frequency50/60hz,Operatingtemprange-50Cto40 0C,internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95,IP20, CRI >80,UGR (Unified Glare Rating) < 19, Flicker free,(flicker should be below 5 %), life time (LED, Driver & electrical circuitry),of minimum50000 Burning Hours with , 70% of initial Lumenmaintained tilllife ends ,CCT 3000°K /4000°K /5700°K /6500°K(As perANSI Bin), SDCM(Standard Deviation Colour Matching) <3,Maximumpower consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete inallrespecti/c external connectionswith1.5sq.mm FRLS/HFFR, PVC insulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy>135lm/Watt output . LM79 & LM80 Test report andalltestingrequiredforLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in Charge as per requirement. (Thermal management:heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 26 | Powdercoateddiecast/Extruded aluminiumBody (Thickness > 1.20 mm) 36 watt Make-Phillipse/Wipro/CG/Polycab |
| 27 | Supplying and fixing of 230VAC 1Ph.400 mm ,900 rpm Wall FanMake: Usha / Crompton / Orient |
| 28 | Supply of powder coated of Siemens grey ofapproved colourcompartmentlised cubicle MV Panel fabricated outof 14/16 SWG thick CRCA sheet steelsuitable for operation on 415 Volts, 50Hz, 3 Phase 4 wireACsupply.Thepanelshalllbe Indoor Type, freestanding,floormounting,dust andverminprooftype,adeqatesizecablealleywithfront operatedrotary handles for MCCB\"s complete with gland plates, lifting hooks, ventillating louvers, busbars, Inter connections, earthing, labelling electrical ,as per specification and drawings, suitable for termination of cables as per single line diagram including. supply and fixing of following switchgear and accessories complete as required. A separate earth aluminium bus bar of size 25 mm x 5 mm to be provided throughout thelengthofthepanel.ThePanelshouldbeextendabletype. (Make of Switchgears- L&T/Schnieder/Seimens/ABB)(a) FEEDER PILLER PANEL IP-65 ( Outdoor Type) MAIN INCOMER - 2 (Electrically & Mechanically Interlocked With each other)MCCB FP 400A.36KA. WITHO/L, & S/C ,PROTECTIONTM BASED-2 NoSPREADER SET-2 No , EXTENDED ROTARY HANDLE-2 No ,DIGITAL VIF METER-2 No , R,Y, B PHASE INDICATING LAMP 240V AC-2 No ,R , INDICATING LAMP 240V AC-6 No ,6A. SP CONTROL MCB -12 ,CT`s 400/5A. CL-1 15VA RESIN CAST/ NYLON CASING -6 No,NEUTRAL LINK -8 No (b) OUTGOING FEEDER MCCB TP 250A. 36KA. TM Based with O/L, & S/C Protection -4 No, SPREADER SET-4No ,EXTENDED ROTARY HANDLE -4 No, MCCB TP125A. 36KA. TM Based with O/L, & S/C Protection -4No ,SPREADER SET -4No ,EXTENDED ROTARY HANDLE -4 No, MCCB TP 160A. 36KA. TM Based with O/L, & S/C Protection -2 No ,SPREADER SET-2 No ,EXTENDED ROTARY HANDLE -2 NoMCCB TP 63A. 36KA. TM Basedwith O/L, & S/C Protection -2 No, SPREADER SET -2 No, EXTENDED ROTARY HANDLE -2 No(c) PANEL ENCLOSURE & ACCESSORIESFABRICATION IN 2.0/1.6MM CRCA SHEET POWDER COATING IN SIEMENS GRAYSHADE,CABLEENTRY ,ENTRYWILLBETOP&BOTTOMSUITABLE FORCABLE ,LOCK, RUBBER GASKET,HARDWAREETC.mENTRYWILLBETOP&BOTTOMSUITABLE FORCABLE ,LOCK, RUBBER GASKET,HARDWAREETC. (d) BUS BAR & HARDWARE 500A. TPNALUMINIUM MAINBUSBAR,LOADWISESUBFEEDERBUSBAR COLOUR COATED HEAT,SHRINK BUSBARSLEAVENUT BOLT, WASHER, HARDWAREETC. (e) WIRING & ACCESSORIESPOWER&CONTROLWIRINGWILLBE(ISI1100V)FLAMERETARDENTLOW SMOKEPVCSINGLECORE ,COPPERWIRE,COPPERLUGGS,PVC SLEEVE, FERRULES, NUMBERS, HARDWARE & LABOUR ETC. (f) On Load Change over 400 Amp = 01 Nos. |