| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit with modular switch, modular plate, suitable G.I. box & earthing the point with 1.5 sq.mm. FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group A |
| 2 | Wiring for twin control light with 1.5 Sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable G.I. box & earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 3 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 4 | 2 X 2.5 sq. mm + 1 x 2.5 sq. mm earth wire |
| 5 | 2 X 4 sq. mm + 1 x 4 sq. mm earth wire |
| 6 | 2 X 6 sq. mm + 1 x 6 sq. mm earth wire |
| 7 | 2 X 16 sq. mm + 1 x 6 sq. mm earth wire |
| 8 | Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required. |
| 9 | 100 mm X 100 mm X 60 mm deep |
| 10 | 180 mm X 100 mm X 60 mm deep |
| 11 | 200 mm X 250 mm X 60 mm deep |
| 12 | Supplying and fixing of suitable size G.I. box with modular plate and cover in front on surface or in racess, including providing & fixing 3 pin 5/6 Amp. modular socket outlet & 5/6 Amp. modular switch, connections etc. as required. |
| 13 | Supplying and fixing of suitable size G.I. box with modular plate and cover in front on surface or in racess, including providing & fixing 6 pin 15/16 Amp. modular socket outlet & 15/16 Amp. modular switch, connections etc. as required. |
| 14 | Supplying and fixing 3 pin, 5 A celling rose on the existing junction box/wooden block including connection etc. as required. |
| 15 | Supplying and fixing brass batten / angle holder including connection etc. as required. |
| 16 | Installation, Testing, Commissioning of wall bracket / celling fittings of all sizes and shapes contaning upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connection etc. as required. |
| 17 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required. |
| 18 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 19 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 20 | 8 way, Double door |
| 21 | 12 way, Double door |
| 22 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 23 | Single Pole |
| 24 | Double Pole |
| 25 | Supplying and fixing single pole blanking plate in the existion MCB DB Complete etc. as required. |
| 26 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \"C\" curve including connections, painting etc. as required. |
| 27 | Supplying and fixing Cable End Box (Loose wire box) (IP 43) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 28 | for 8 way, Double door SPN MCB DB |
| 29 | for 10 way, Double door SPN MCB DB |
| 30 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 31 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 32 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required(For inverter wiring). |
| 33 | 1 X 1.5 sq. mm |
| 34 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 35 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5°C to 40°C, internal surge protection of 2. 5 KV with Short & Open circuit protection, THD < 10%, P. F>0. 95, IP20, CRI >80, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1. 5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) 18- 22 watt |
| 36 | Supply & fixing of water tight oblong 10 watt LED Bulkhead luminaire having pressure die cast housing with driver set confirming to IP65 and above protection, IK 08, High purity /transmisivity UV Stabilized Non yellowish diffuser/ for uniform light distribution, detachable driver set, open and short circuit protection, suitable for 24 Hr Continuous Operation, Complete in all respect. compelete in all respect. CAT-AAA1200 system lumens, >120 Lm/W, PF>0.95, CRI >70, >300V over voltage protection, 4 KV internal Surge Protection, metal housing with 5 years warrantee |
| 37 | Brush Less Direct Current (BLDC) Fan without Remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0. 9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1. 5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value = 6. 0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 38 | Supply of Heavy Duty Exhaust Fan 300 mm. sweep 900 RPM complete in all respect.Havells or Eq. |
| 39 | Supply of Metallic body fresh air fan 230 mm. sweep complete in all respect. Havells or Eq. |
| 40 | Supply and fixing of 7 Watt LED Bulb. Havells or Eq. |
| 41 | Supply and fixing of Wall Bracket light with glass, diffuser suitable for 7.5/9 W LED. Havells or Eq. |
| 42 | Supply and fixing of DP Sheet Steel enclosure Busbar, Neutral link, Earthbar and Din Rail Make:-Legrand or Eq. |
| 43 | Supply and fixing of 80 Amp. DP MCB (10 KA) C-Series Havells or Eq. |
| 44 | Dismantalling Old wiring, D.B. Main switch etc. |
| 45 | Cost of 01 No. Residence |
| 46 | Cost of 12 No. Residence Please Enable Macros to View BoQ information |