| 1 | M&L for Checking, testing Taking out all the LT cables by cutting old rusted nuts,bolts etc, refreshing all the cables (one incomming and 4 to 8 out going) by providing new lugs, MS nuts, bolts & washers and required excavation work, returning filling, removal and making good. welding of panels hings including making proper locking arrangement of LT panel front and rear doors and proper opening and clossing. Wiring of voltmeter or ammeter with copper conductor single core 1.5 Sqmm size,Die cast resin CT for digital Amp meter of any capacity andratio of CT, complete all as specified and directed Engineer-in-Charge. complete all as specified and as directed.Painting of LT Panels with smoke gray paint over a paint of redoxide. Marking incoming & out going feeder to particular block/ Bldg Nos with white paint etc. complete all as directed by engineer -in -charge. a) Excavtion and earth work for taking out cable loop will be included in the rate of the same deemed included in the quoted rate by the contractor, not paid seperately.Note:a)Voltmeter and ameter will be paid separately if required at site. b)If contractor not execute work after one week of site order than 3000 Rrs/day recovery shall be float from RAR |
| 2 | M&L for Opening /disconnecting the electrical connection of defective/burnt out underground LT cable of any size2 to 4 core from main switch/DB/junction box / LT panel/ L T O/H line etc. Taking out the required length of cable from existing loop, cutting the defective portion of cable ,providing required thimbles/connectors at cable end and reconnecting the cable in previous location with existing main switch/DB/Junctionbox/LT panel/O/H line etc all as directed. Note:- (I) the cost of required earth work ie excavation,returning filling,relaying of sand/bricks and cost of drawing the required length from protection pipe ,breaking of required brick work/plaster/concrete and redoing the required cement work to match the existing surface is deemed to be included in quoted rates and nothing extra should be paid on this account.(ii)Additional cable/ protection pipe required at site shall be measured and paid seperatly.Note:a)Voltmeter and ameter will be paid separately if required at site. b)If contractor not execute work after one week of site order than 3000 Rs/day recovery shall be float from RAR. |
| 3 | S&F in repair/ replacement for GI pipe light grade 50mm dia bore with all fittings complete all as specified and as directed. |
| 4 | S&F in repair/ rplacement for GI pipe light grade 80mm dia bore with all reqd fittings complete all as speciifed and as directed. |
| 5 | M&L in replacementforframe type panel board suitable for incomming and outgpoing as MCCB,wall mounted type double door having suitable provision for incoming MCCB 4 pole 400 amp and outgoing MCCB G frame TP 6 way complete all as specified and directd. |
| 6 | Taking down/ out unserviceable UG cables of any cross sectional area, any type, any make from trench/ from wall/pole/fixed with walls/ incl pulling through pipe by opening connections and joints including removing pipe, carefully getting out bricks etc keeping aside for re-use complete all as specified and as directed.Note : Earthwork shall be measured and paid under relevant items of BOQ. |
| 7 | Supplying, laying, jointing and testing of 1100 volts grade XLPE insulated, PVC sheathed (heavy duty) electric strip/ wire armoured electric cable of size 240 Sqmm 3.5 core with stranded aluminium conductor, laid in trenches, in floor, in duct, through pipes or along the pole complete all as specified and as directed. |
| 8 | Ditto all as per above item No 7 above, but of size 185 Sqmm 3.5 core complete. |
| 9 | Ditto all as per above item No 7 above, but of size 95 Sqmm 3.5 core complete. |
| 10 | Ditto all as per above item No 7 above, but of size 70 Sqmm 3.5 core complete. |
| 11 | Ditto all as per above item No 7 above, but of size 50 Sqmm 3.5 core complete. |
| 12 | Ditto all as per above item No 7 above, but of size 35 Sqmm 3.5 core complete. |
| 13 | Ditto all as per above item No 7 above, but of size 25 Sqmm 3.5 core complete. |
| 14 | Ditto all as per above item No 7 above, but of size 16 Sqmm 4 corecomplete. |
| 15 | S&F in replacement1100 volts grade heavy duty PVC insulated & PVC sheathed stranded aluminium conductor of size 10 Sqmm twin core flat cable in service incl taking down/ out unserviceable cable all as directed. |
| 16 | S&F in replacement1100 volts grade heavy duty PVC insulated & PVC sheathed stranded aluminium conductor of size 16 Sqmm twin core flat cable in service incl taking down/ out unserviceablecable all as directed. |
| 17 | M&L for excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for laying of cables and gettingout complete all as specifiedand directed by Engineer-in-Charge. |
| 18 | Returning, filling in,soft/loose soil, including spreading, leveling watering and well ramming in layers not exceeding 25 cms thick each layer compete all as specified and directed by Engineer-in-Charge. |
| 19 | Removal of surplus soft/loose soil soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point completeall as specified and directed by Engr-in-charge. |
| 20 | S & F double wall corrugated HDPE pipeSN8 100 mm dia for protection of cable from ingress of moisture and high impact bearing capacityin trenches complete all as specified and as directed. |
| 21 | S & F double wall corrugated HDPE pipe SN8 50 to 63 mmmm dia for protection of cable from ingress of moisture and high impact bearing capacityin trenches complete all as specified and as directed. |
| 22 | S & Fin replacement MCCB 630 Amps, 4 pole, 50kA with protection unitIcs = 100% Icu, 415 volts, 50 Hz with,with phase barrier/phase seperator/spacer with copper spreader links and required nut, bolts or other fixing accessories complete. |
| 23 | S & Ffor in replacement MCCB 400 Amps, 4 pole, 35 kA, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolts or other fixing accessories complete. |
| 24 | S & Ffor in replacement MCCB 315 / 320/ 350 Amps, 4 pole, 35 kA with Adjustable thermal magnetic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolts or other fixing accessories complete. |
| 25 | S & Ffor in replacement MCCB 250 Amps, 4 pole, 25 kA with energy metering devices, Ics = 100% Icu, 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolt or other fixing accessories complete. |
| 26 | S & Ffor in replacement MCCB 250 Amps, 4 pole, 35 kA adjustable thermal magentic, Ics = 100% Icu, 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolt or other fixing accessories complete. |
| 27 | S & Fin replacement MCCB 200 Amps, 4 pole, 25 kA with Adjustable thermal magnetic release, Ics = 100% Icu , 415 volts, 50 Hzwith phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolts or other fixing accessories complete. |
| 28 | S & F in replacement MCCB 160 Amps, 4 pole, 25 kA with Adjustable thermalmagnetic release, Ics = 100% Icu , 415 volts, 50 Hzwith phase barrier/phase seperator/spacer with copper spreader links and required nut, bolts or other fixing accessories complete. |
| 29 | S & Fin replacement MCCB 125 Amps, 4 pole, 25 kA with Adjustable thermal magnetic release, Ics = 75% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolts or other fixing accessories complete. |
| 30 | S & Fin replacement MCCB 100 Amps, 4 pole, 25 kA with compatible energy metring unit , Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolts or other fixing accessories complete. |
| 31 | S & Fin replacement MCCB 63 Amps, 4 pole, 16 kA with fixed thermalmagnetic release, Ics = 100% Icu , 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolts or other fixing accessories complete. |
| 32 | S & Ffor in replacement TPN MCB, 415 Volts, 50 Hz, having rupturing capacity 10 kA, of rating 63 Amps. |
| 33 | M&L in replacement Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thickness buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanised earth strip 32x6 mm as earthing strip by means of GI bolts, nuts, check nuts and washers incl surrounded on all sides by 15cm thick layer of charcoal dust, salt, incl earth stripprotected by 40mm dia GI light grade pipe, PCC pit of 1:2:4 & reinforced PCC top cover 50mm thick, earth pit angle frame of size 25mmx25mmx3mm with excavation and earth work in any type of soil, light grade GIwatering pipe 20mm dia with funnel and wire-mesh complete all to as shown in electrical plate no 3 of SSR Part I 2020 connected main switch board or as reqd at site all as specified and testing on completion. (Note: The rate quoted include the cost of GI strip & GI protection pipe light 40mm dia bore light grade upto 7.5 metres. PCC Chamber shall be constructed at least 0.50 mtr away from on the earth pit electrode and pipe for watering shall be provided in slanting manner .(2) If the results are not found satisfactory, then 2nd earthing will be re-done without any cost payable to Contractor. |
| 34 | S&F heat shrinkable straight through joint suitable for 1100 V XLPE/ PVC cable of size 240 Sqmm 3.5 core to 400 Sqmm 3.5 core complete incl disconnecting cable and re-connecting all as specified and as directed. |
| 35 | S&F heat shrinkable straight through joint suitable for 1100 V XLPE/ PVC cable of size 150 - 185 Sqmm 3.5 core complete incl disconnecting cable and re-connecting all as specified and as directed. |
| 36 | S&F heat shrinkable straight through joint suitable for 1100 V XLPE/ PVC cable of size 70 - 120 Sqmm 3.5 core complete incl disconnecting cable and re-connecting all as specified and as directed. |
| 37 | S&F heat shrinkable straight through joint suitable for 1100 V XLPE/ PVC cable of size 25 -50 Sqmm 3.5/4 core complete incl disconnecting cable and re-connecting all as specified and as directed. |
| 38 | Taking down LT cable of any size frompole/ panel or any location by opening cable connections and cleaning the cable bycleaning tissue, gel and supply & fixwith gland to panel and restore the power supply complete all as specified and as directed. |
| 39 | M&L for reshifting of existing LT panel within 5 mtr distance after taken out panel/cables with demolition of existing PCC and brick work, re-fixing panel at new loc with PCC of 1:2:4 in such a way that each leg of iron angle must be 30cm in ground complete with nay type of cvil work involved. |
| 40 | Supply & fix new angle iron, cross arms, structural steel any cross section reqd at site of any size includingi.e. cutting, welding, bending, cold or hot, drilling holes, grinding or bolt in any shape or size including 2 coats of aluminium paint over one coat of red oxide including taking out unserviceablecomplete and fix to damaged angle iron legs of LT panel or as specifiedand directed by Engineer-in-charge. |
| 41 | Material and labour for Boring hole under the road/ pavement/ hard standingand inserting HDPE pipe of 100mm at a depth not less than one metre below ground level complete all as specified & directed. Note: The quoted rate includes cost of HDPE pipe 100mm pipe min |
| 42 | S&F butt hinges, heavyweight, cold rolled mild steel of size 125 mm and fixed properly on MS CRCA sheet of thickness 2 to 3.15 mm after dismantling old one frompanel and fixing panel door on other side complete all as directed. |
| 43 | M&L for Mild steel sliding door bolts, plate type, stainless steel finish, with bright bolt not less than 12mm dia, length 250mm with and including a minimum of 6 bolts and nuts, four on bolt plate and two on staple plate and fixed complete to LT panel door with welding or suitable means with any type of wk involved all as directed. |
| 44 | M&L for PCC work (1:4:8)type D-2 (using 40 mm graded stone aggregate) for necessary form work and fair finish to exposed surfaces without using extra cement etc.complete all as specified. |
| 45 | M&L for PCC work (1:3:6)type C-2 (using 40 mm gradedaggregate) for necessary form work and fair finish to exposed surfaces without using extra cement etc. complete all as specified. |
| 46 | S & F Volt meter digital, 96 x 96mm size, 0-500 volts, AC,complete all as specified and as directed. |
| 47 | S & F Ampere meter digital, 96 x 96mm size, 0-100A size, AC, complete all as specified and as directed. |
| 48 | Taking down old UNSV LT panel from the site and make complete good to disturbed sufaces all as specified and directed by EIC.Note :All MCCB will be deposit in store yard of old UNSV panel for BER or reuse |
| 49 | Supply, installation, commissioningpiller box outdoor type IP 66 protectionfabricated out of CRCA sheet and thickness not less than 3.15 mm powder coated andangle of size 40x40x6mm grouted in PCC 1:2:4 Type B-1 prewired from CPRI approved manufacturer complete with following (a) MCCB 4 Pole 200 Amp 25 kA with Adjustable thermal magnetic release,Ics = 100% Icu , 415 volts, 50 Hzwith phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolts or other fixing accessories complete. (b) Bus bar chamber with Alluminium Bus bar three phase and neutral cap 400 Amp |
| 50 | S&F thimble Aluminium type suitable for cable upto 70Sqmmincluding necessary crimping with crimping tool complete all as specified and as directed. |
| 51 | S&F thimble Aluminiumeye type suitable for cable from 95 Sqmm to 185 Sqmmincluding necessary crimping with crimping tool complete all as specified and as directed. |
| 52 | S&F thimble Aluminium type suitable for cable from 185 Sqmm to 240 Sqmmincluding necessary crimping with crimping tool complete all as specified and as directed. |
| 53 | M & L for Cutting/removing of bushes/small trees/vegetationgrowth upto a distance of appx 20 mtr around the LT panel, not exc 30cms deep incl drains all around the plant incl rough surface leveling/cutting,filling upto 12\" height/ depth all around the plant and burning at a distance of 50mtr (minimum) in the presence of Engr-in-charge including sprinkling the round up chemicals for drying/killing the bushes,shrubs etc. |
| 54 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening,and having provision for front and rear side opening with rubber beading and brasscable glands for each cable to make it weather and vermin proof.double door hinged type,both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of 750mm long, 300mm grouted in plaincement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 450 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connectionsincoming / out goingcomplete all as directed by Engineer-in-charge. comprising of following accessories.Location:G Pocket(i) Bus bar strip,four pole and capacity 200 AmpsCu bus bar of suitable size based on 1.0 Amps per Sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelaininsulators with necessary nuts and bolts and washers etc |
| 55 | (ii) INCOMING : -(a) MCCB 200 Amps, 4 pole,50 kA with adjustable thermal magentic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolts or other fixing accessories complete. -01 No.(b) Multifunctionmeter with LCD display, accuracy class 1.0,having parameters KW,KVA, KVAh & PF duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three-01 set(iii) OUTGOING:-(a) Star delta starter suitable for 25 HP-03 No. (b) DOL starter for 05 HP-01 No. (c) MCB SPN 63 A,10 KA B series complete all as specified and as directed.-01 No. |
| 56 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening,and having provision for front and rear side opening with rubber beading and brasscable glands for each cable to make it weather and vermin proof.double door hinged type,both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of 750mm long, 300mm grouted in plaincement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 450 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connectionsincoming / out goingcomplete all as directed by Engineer-in-charge. comprising of following accessories.Location:Thimmaya park Sewage well two pole(i) Bus bar strip,four pole and capacity 525 Amps Al bus bar of suitable size based on 1.0 Amps per Sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelaininsulators with necessary nuts and bolts and washers etc |
| 57 | (ii) INCOMING : - (a) MCCB 350 Amps, 4 pole,50 kA with adjustable thermal magentic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolts or other fixing accessories complete. -01 No.(b) Multifunctionmeter with LCD display, accuracy class 1.0,having parameters KW,KVA, KVAh & PF duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three-01 set(iii) OUTGOING:-(a) MCCB 200 Amps, 4 pole,50 kA with adjustable thermal magentic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolts or other fixing accessories complete. -02 No.(b) MCCB 160 Amps, 4 pole, 35 kA Adjustable Thermal magnetic, Ics = 100% Icu, 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolt or other fixing accessories complete.-01 No.(c)MCCB 63 Amps, 4 pole, 35 kA Adjustable Thermal magnetic, Ics = 100% Icu, 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolt or other fixing accessories complete.-01 No.(d)MCB SPN 63 A,10 KA B series complete all as specified and as directed.-01 No. |
| 58 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size indoor wall mounted type 415 Volts, dust proof,vermin proof made out of CRCA sheet 2.00 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening,and having provision for front opening with rubber beading and brasscable glands for each cable to make it weather and vermin proof. door hinged type,air fins for ventilation, duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supportedas per manufacturer instruction and including notice board & Danger plate complete with all connectionsincoming / out goingcomplete all as directed by Engineer-in-charge. comprising of following accessories.Location:MH sewage well (i) Bus bar strip,four pole and capacity200 Amps Cu bus bar of suitable size based on 1.5 Amps per Sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelaininsulators with necessary nuts and bolts and washers etc (ii) INCOMING : -(a) MCCB 200Amps, 4 pole,50 kA with adjustable thermal magentic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolts or other fixing accessories complete. -01 No. |
| 59 | (b) Multifunctionmeter with LCD display, accuracy class 1.0,having parameters KW,KVA, KVAh & PF duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three-01 set (iii) OUTGOING:-(a) Star delta starter suitable for 25 HP-02 No.(b) DOL starter suitbale for 5.0 HP-01 No.(c) MCB SPN 63 A,10 KA B series complete all as specified and as directed.-01 No. |
| 60 | Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel Board of Suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening,and having provision for front and rear side opening with rubber beading and brasscable glands for each cable to make it weather and vermin proof.double door hinged type,both side openable, air fins for ventilation, panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of 750mm long, 300mm grouted in plaincement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 450 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connectionsincoming / out goingcomplete all as directed by Engineer-in-charge. comprising of following accessories.Location:MAIN LT PANEL STP(2.0X3.0 MLD)(i) Bus bar strip,four pole and capacity 800Amps CU bus bar of suitable size based on 1.0 Amps per Sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow , blue and black ) fixed on porcelaininsulators with necessary nuts and bolts and washers etc |
| 61 | (ii) INCOMING : -(a)S & F on load front operated change over 630 A, 50 KAcomplete all as specified and as directed.-01 No.(b) ACBs -Standard up to 800A ,50 KA“The Air Circuit Breaker shall be 4 pole 100% Neutral, 415 volt, 3 phase, 50 Hz AC ,designed operational voltage 690 V,Horizontal Draw out type motorized, front operated with microprocessor-based protection release having password protected adjustable over load, short circuit, earth fault protection and neutral protection.The breaker shall have minimum breaking capacity of 50KA (RMS) symmetrical. The ACB shall have Ics=Icu=Icw for 1 sec. ACBs shall have over-temperature protection feature with 4 NO/NC auxiliary contacts.ACB shall also confirm to IEC 60947/IS-13947/Part-II/1993 latest version).Protection unit must be with display to see current parameters & fault history (80 to 100) with USB port to access stored data of the release. Breaker shall be equipped with pre-overload & over temperature alarms complete all as specified and as directed. -01 No.(c) Multifunctionmeter with LCD display, accuracy class 1.0,having parameters KW,KVA, KVAh & PF duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete - 01 No. (d) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three-01 set |
| 62 | (iii) OUTGOING:-(a) MCCB 400 Amps, 4 pole,50 kA with adjustable thermal magentic release, Ics = 100% Icu, 415 volts, 50 Hz with with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolts or other fixing accessories complete. -02 No.(b) MCCB 160 Amps, 4 pole, 35 kA Adjustable Thermal magnetic, Ics = 100% Icu, 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolt or other fixing accessories complete.-01 No.(c)MCCB 63 Amps, 4 pole, 35 kA Adjustable Thermal magnetic, Ics = 100% Icu, 415 volts, 50 Hz with phase barrier/phase seperator/spacer with copper spreader linksand required nut, bolt or other fixing accessories complete.-02 No.(d)MCB SPN 63 A,10 KA B series complete all as specified and as directed.-03 No. |
| 63 | S & F LT panel door covers duly powder coated with hinges ,locks,operating handle for 2 No.door lock with perplex/acrylic sheet of 5mm thick of 75 percent of the door surface area and with seal bedding for water protectionincluding all fittings required at site complete alll as specified and as directed.Note work will be executeon site by rep of reputed manufacturer of LT panel subjected to prior approvalby Engr in charge.Note:a)work will be executed by authorized rep of reputed brand of panel maker.b)If contractor did not execute work after one week of site order than 3000 Rs/day recovery shall be float from RAR |
| 64 | M & L in replacementfor Factory made, machine pressed pre-cast concrete, interlocking paver block with grey cement & no pigment set and jointed over and including 25 mm thick dry sand bedding as in floors cushioning layer below interlocking paver blocks(50% grey and 50% red)including watering and consolidation complete and pavings of selectedshape and size as approved by GE conforming to(IS:15658-2006) of 60 mm thick, M-30 grade,complete all as specified and directed by Engineer-in-Charge. |
| 65 | S&F (concealed flush to wall) factory made VTPN (Vertical type), 4 Way 415V, as per IEC 61439-3, DB (made out of CRCA sheet not less than 1.2mm thick, with copper bus bar rating of suitable capacity, with two neutral bar, 2 earth bar and cable tie for cable management, suitable forMCCB 4 pole upto 125Amp,as incomer and suitable for mounting MCBs as outgoing,DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-54 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge.Note :- MCBs for outgoing shall be measured and paid separately under appropriate item of BOQ. directed. |
| 66 | S & F outdoor APFC panel 150 KVAR suitable for 400 KVA transformer having copper bus bar pan assembly super heavy duty capacitor ,capacitor duty contactor enclosure complies to minimum 7 tank coating process,intelligent power factor relay controller including all components like MCCB ,capacitor duty contactor /power contactor APFC panel relay power capacitor capacitor bank size 2(50 kVAr)+1(25 KVAr)+1(10KVAr)+2(5 KVAr)+1(3KVAr)+1(2 KVAr) minimum size of panel should1175mmx800mmx540mm panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of 750mm long, 300mm grouted in plaincement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 450 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connectionsincoming / out goingcomplete all as directed by Engineer-in-charge complete all as specified and as directed.Location :MAP pockets |
| 67 | S & F outdoor APFC panel 100 KVAR suitable for 250 KVA transformer having copper bus bar pan assembly super heavy duty capacitor ,capacitor duty contactor enclosure complies to minimum 7 tank coating process,intelligent power factor relay controller including all components like MCCB ,capacitor duty contactor /power contactor APFC panel relay power capacitor capacitor bank size 4(20 kVAr)+1(10 KVAr)+1(5KVAr)+1(3KVAr)+1(2 KVAr) minimum size of panel should1175mmx800mmx540mm panel shall be mounted on angle of size (50 x 50 x 6 mm) & duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of 750mm long, 300mm grouted in plaincement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) and 450 mm ground clearance or as per manufacturer instruction and including notice board & Danger plate complete with all connectionsincoming / out goingcomplete all as directed by Engineer-in-charge complete all as specified and as directed.Location :MAP pockets Note:Credit will be deposit in MES store yard and shall be issued on gate pass signed by Engr in charge at the time of RAR. |