| 1 | Disconnecting of HT/LT connections of transformer, including disconnecting of earthing lead, unscrewing nuts, bolts and washers, testing their un-serviceability (open and closed circuit test) with the help of composite unit of transformer of capacity 100 to 350 KVA, 6600/433 Volt, and isolation transformer of any capacity, refixing all connection and testing on load. complete all as specified and directed. |
| 2 | Material and labour for opening of top lid cover of transformer of capacity 100 to 350 KVA, 6600/433 volts indoor /outdoor, disconnecting all internal connections of HT/LT side for periodical maintenance such as cleaning of core and winding by means of washing by hosing down with clean dry oil to remove thedust/sludge on core and coil, cleaning of oil tank to remove sludge deposited, replacement of rusted gasket set, burnt spindle, broken/ unserviceable HT/LT ceramic bushing, broken arc horn, surge arrestor, replacement of silica gel etc , refixing all connection and testing on load complete all as specified and directed. |
| 3 | Taking down carefully defective transformer of capacity 100 to 350 KVA 6600/433 Volt indoor/outdoor and from foundation baseincluding draining out old transformer oil complete carefully and keeping the same in a cleaned container in safe custody for re use after repair works of transformer and transportation from site to workshop and back to site after repair, connecting HT as well as LT side to existing system, testing and commisioning after repair complete all as specified and directed.Note: - Transformer Oil to be re-used shall be dehydrated/ filtered under respective items. |
| 4 | Material and labour for open the top cover of transformer of capacity 100 KVA to 315 KVA, after disconnecting HT/LT connection, drain out of transformer oil and preserve it in container, replacement of all gasket for prevention of leaking, replacement of broken HT/LT bushes complete as per existing and refixing all connection and testing on load complete all as specified and directed.Note- For item No 1.00 to 4.00.(a) Cost of transformer oil for cleaning by Hosing down shall deem to be included in the quoted rates.(b) Gasket set, LT/HT side ceramic bushing, spindle for HT/LT side and horn surge arrester etc. for replacement shall be measured and paid under relevant item. |
| 5 | Material and labour for rewinding of LT copper strip coil for off sizes transformer after removing unserviceable insulating materials, re-insulation and re-winding with new copper wire as per existing size of core of transformer including heating, varnishing, etc., complete all as specified and directed. |
| 6 | Material and labour for rewinding of HT wire coil foroff sizes transformer using proper size new copper wire and HV Insulating materials suitable for working voltage 6.6 KV complete all as specified and directed. |
| 7 | Supply and fix in repair ceramic bushing and gasket on HT Side of transformer 100KVA to 350KVA, 6600/433 Volt or 11000/433 Volt complete all as specified and directed. |
| 8 | Supply and fix in repair ceramic bushing and gasket on LT side of transformer 100 KVA to 350KVA,6600/433 volt complete all as specified and directed. |
| 9 | Supply and fix in repair breather assembly filled with silica gel500 gm of metal body as Approvedcomplete all as specified and directed. |
| 10 | Supply and fix in repair brass spindle for terminal on HT side threaded complete with nut, washers, etc. of dia as ordered, as approved and suitable for transformer 100 to 350 KVA, 11000/433 volt or 6600/433 Volt, complete all as specified and directed. |
| 11 | Supply and fix in repair brass spindle for terminal on LT side threaded complete with nut, washers, etc. of dia as ordered, as approved and suitable for transformer 100 KVA to 350KVA, 6600/433 volt, complete all as specified and directed. |
| 12 | Supply and fix in repair gasket (cork sheet) 6 mm thick with conical rubber bush complete as approved and suitable for transformer 100KVA to 350 KVA,6600/433 Volt complete all as specified and directed. |
| 13 | Material and labour for applying one coat of synthetic enamel paint by spray painting including preparation of body of transformer 100KVA to 350 KVA, 6600/433 volt complete all as specified and directed. |
| 14 | Supply and fix in repair cable jointing kit for 11 KV (Earthedgrade) cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed. |
| 15 | Supply and fix in repair cable jointing kit for 11 KV (Earthed grade) cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed. |
| 16 | Supply and topping up new transformer oil having di-electric strength not less than 60MV complete all as specified and directed. |
| 17 | Material and labour for dehydrartion of transformer oil after dehydration di-electric strength not less than 40MV in 2.5mm gap complete all as specified and directed. Note:- Rate to be quoted will be inclusive of transportation of dehydration machine at various location where transformer installed. |
| 18 | Supply and fix in repair cable jointing kit for 11 KV (Earthed grade) cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified anddirected. |
| 19 | Material and labour for finding out faulty HT UG cable already laid within the 2 KM radius complete all as specified anddirected.Note :-(a) HT cable fault detector machine to be arranged / brought by the contractor without any extra cost.(b) Straightthrough joint to be measured and paid separately under respective items. (c) HT cable shall be measured and paid separately under respective items.(d) Necessary earth work to dig out the faulty location shall be deemed included in the quoted rate. |
| 20 | Disconnecting and taking out existing HT 6.6 KV VCBs of any make from housing and cleaning, rubbing and overhauling the mechanical parts and servicing of 6.6KV in door VCB, checking of quality of vacuum interrupter, insulation resistances, static contact resistance, Testing( IR value, Ratio test, Polarity test) and connection verification of 6.6 KVCurrent transformer( Set of three) by PRIMARY INJECTION KIT ,and Testingand calibration of relay ( set of two over current and one earth fault) by SECONDARY INJECTION KIT includingall other functional tests of the VCB, C&R panel and CTs, PTs. complete all as specified anddirected.Note :Spare parts shall be measured and paid seperately under respective item. |
| 21 | Supply and fix in repair vacuum interrupter type VG 2EN with TC suitable for 6.6 KV VCB Panel as per existing complete all as specified and directed. |
| 22 | Supply and fix in repair vacuum Interrupter with TC suitable for 6.6 KV VCB Panel as per sample, complete all as specified and directed. |
| 23 | Supply and fix in repair breaker chargingmotor including gear assembly 110 volt/ 220 Volt AC suitable for 6.6 KV VCB panel complete all as specified and directed. |
| 24 | Supply and fix in repair ammeter square type digital having CT ratio 50/5 of and current rating 0-50 amps and selector switch for VCB panel 6.6 KV complete all as specified and directed. |
| 25 | Supply and fix in repair digital multifunction meter square type ofsize 96 Sqmm of capacity 0 to 15 KV PT Ratio 6.6KV/110 Voltfor panel complete all as specified and directed. |
| 26 | Supply, installation, testing and commissioning of micro processor base relay (02 O/C + 01 EF)for 6.6 KV VCB panel, rating 5 Amps, auxiliary supply 20-110 Volt DC including taking down existing relay of any type and size complete all as specified and directed. |
| 27 | Supply, installion, testing and commissioning of voltage operated auxiliary relay with SR contactsfor 6.6 KV VCB panel, coil rating 24V DC with operational time 20-25 ms including taking down existing relay of any type and size complete all as specified and directed. |
| 28 | Supply and fix in repair trip and close switch for 6.6 KV VCB panel02 Amps/ 110 volt with locking arrengement complete all as specified and directed. |
| 29 | Supply and fix in repair 6.6 KV panel indicating lamp fitting LED typesuitable for24 volt/ 30volt DCcomplete with base complete all as specified and directed. |
| 30 | Supply and fix in repair 6.6 KV panel indicating lamp fitting LED type suitable for 110 volt / 230volt ACcomplete with base complete all as specified and directed. |
| 31 | Supply and fix in repair limit switch suitable for VCB Panels 6.6 KV complete all as specified and directed. |
| 32 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5m in depth and getting out in soft/loose soil for laying of under ground cable complete all as specified and as directed. |
| 33 | Returning filling in including spreading leveling wateringand well ramming in layers not exceeding 25cm in soft/loose soil complete all as specified and directed. |
| 34 | Removing of surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 35 | Supply, laying, connecting and testing XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 95 sq mm 3 core, (earth grade) confirming to IS-7098 (Part-II) laid through in trenches with brass compression cable gland, terminal lugs, etc including taking out old existing unserviceable cable complete all as specified and directed.Note : Earth work, brick protection and sand cushioning shall be measured and paid separately under respective item |
| 36 | Material and labour for sand cushioning with clean and dry river sand for protection of XLPE UG cable with approved sand of uniform thickness. laid dry, filling in trenches and punning down in proper required layers complete all as specified anddirected. Note:- Punned down thickness shall be measured for payment. |
| 37 | Supply and laying un-reinforced precast cement concretecablecover class HV, Type 1,flat,size 300mmx 180mm x 40mm complete all as specified and directed. |
| 38 | Supply and installation of HT 6.6 KV outdoor gang operated air-break switch suitable for horizontal or vertical mounting with drop out fuse having 12 insulators of rating upto 200 Amps including taking down old unserviceable GOD complete all as specified and directed. |
| 39 | Supply and fix in repair Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo Amp 6600 Volt complete all as specified and directed. |
| 40 | Material and labourfor servicing / greasing of HT Switch air break ( GOD) 6.6 KV TP with replacement of corroded nut bolts, ACSR jumpers, making alignment of operating mechanism for proper ON / OFF operationof GOD and male contact including complete all as specified and directed. |
| 41 | Supply and fix in repair cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, oneunder coat and one finishing coat of paint complete all as specified and directed. |
| 42 | Material and labour for ACSR conductor, proper jointing with suitable clamps and termination with the help of suitable lugs in GODs, Drop Out units, insulators and cable end terminations etc of weasel with permissible sag as per IS rules etc including taking down old unserviceable ACSR conductor of any type and size complete all as specified and directed. |
| 43 | Supply and fix in repair disc type insulator, porcelain, vitreous 145mm high and 255 mm dia ball and socket type, white, brown or green single disc assembly for tension with tension clamps for couductor, working pressure 6600 Volt, complete all as specified anddirected. |
| 44 | Supply and fix in repair pin type insulator, porcelain, vitreous, white, brown or greenincluding one galvanised mild steel spindle, two galvanised iron washers and onegalvanisedironnut 150mm height, 150mm dia for 6600 volts grade, complete all as specified and directed. |
| 45 | Material and labour for complete removal of existing treatement of HT pole and structure steel surfaces and applying two coat of synthetic enamel paint over one coat of red oxide including preparation of surface complete all as specified and directed. |
| 46 | Supply and fix 3mm thick rubber insulatingmat of size 1mx 2 m, conforming to IS-15652, Class-C for working voltage upto 33 KV complete all as specified and directed. |
| 47 | Supply and fix in repair MCCB, 400 Amps, 4 pole, 415 Volt, 50 Hz, Breaking capacity 36 KA, fixed thermal and fixed magnetic setting type complete all as specified and directed. |
| 48 | Supply and fix in repair MCCB, 200 Amps, 4 pole, 415 Volt, 50 Hz, Breaking capacity 36 KA, fixed thermal and fixed magnetic setting type complete all as specified and directed. |
| 49 | Supply and fix in repair MCCB, 160 Amps, 4 pole, 415 Volt, 50 Hz, Breaking capacity 25 KA, fixed thermal and fixed magnetic setting type complete all as specified and directed. |
| 50 | Material and labour for PCC (1:3:6) type C-2 (using 40mm graded stone aggregate) as in foundation , filling and mass concrete complete all as specified and directed. |
| 51 | Material and labour for cement concrete (1:3:6) type C1 (20 mm graded stone aggregate) as in kerbes, coping etc chamfered edges including formwork including demolition of existing cement concrete and removal of rubish from site complete all as specifiedand directed, |
| 52 | Material and labour for making sign board of size 1.00m (l) x 1.50m (w) for E/M installations at different location, made of stainless steel frame of 50mm x 50mm x 1.80mm thick hollow square section stainless steel bar in all side including fixing arrangement of retro reflective sheet (encapsulated lens type) in white colour over the blue sticker, height exc. 100 mm but not exc. 150mm cut to size and paste on mild steel plate and paste on blue sticker which stick on stainless steel sheet as per manufacturer instructions and welded on two No. 50 mm x 50mm x 1.80mm thick hollow square section stainless steel of length 3 m fixed in PCC foundation of size 0.45x0.45x0.45m with PCC (1:2:4) type B1 (using 20mm graded stone agregate) and necessary excavation including taking down old unserviceable existing board complete all as specified and directed, |
| 53 | Material and labour for earthing complete with GI earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to GI earth strip of size 32 x 6 mm earth lead by means of nuts, bolts, check nuts, washers of galvanised iron as steel,protected by 40 mm bore HDPE pipe of pressure rating 6 kgf/sqcm allas directed including cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 42 x 42 x 10cm thick reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 15 cm long, bent to shape as lifting handle, funnel,wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part-I including testing on completion and including taking down existing earthing sets complete all as specified and directed.Note:- GI strip upto 7.5m length including testing shall be included in quoted rates. |
| 54 | Supply installation, commissioning and testing including providing all necessary electrical connection, 6.6 KV HT feeder pillarbox(CPRI Approved), outdoor type ,factory made out of3.15 mm thick MS sheet of size 1.0m x 1.0 m x 0.6 m deep having hinge opening arrangement in front and back side and bottom frame made out of angle iron of size 50x50x6mm thick and 04 Nos legs, 0.5 meter length with cable entry and exit circular hole with cable gland & gasket at bottom complete including painting to all internal and external exposed steel surfaces with powder coating paint (5 stage process) with duly fixed in ground with necessary PCC foundation (1:2:4) type B1, with danger notice plate of 1.6mm thick mild steel sheet, vitereous enamelled (white), with letters to be written 6600 Volt, figures and conventional skull and bones in signal red colour, fixing lugs, bolts, screws etc completeincluding necessary excavation work for taking out cable loop and refilling the trenches and feeder pillar box made reptile proof and comprising of the following accessories:- Location : Sub Stn No 1.(a) Anodized Aluminiumbus bar of capacity 1200 Amp ( Size 100mm x 12 mm)- 03Nos.(b) 6.6 KV HT Base PVC insulator for fixing of busbar (03 x 03 - 9 Nos.) including taking down old unserviceable HT feeder pillarbox complete all as specified and directed. |
| 55 | Material and labour for cleaning of HT/LT electric supply installation by spraying of weeds herbicide for kill unwanted vegetation around near and arround electrical power house installation, pump house installation, 4 pole structure installation, 6 pole structure installation and main receiving substation by cutting grass, removing unwanted bushes removing unwanted debris and making good by filling fresh soil, levelling the area and removing unwanted debris from the premises at a distance above 50m from the site complete all as specfied and directed. Note :- Incase of any damages to any existing fixtures and accessoires connected with the installation, contractor has to responsible for making good as per existing without any extra cost. Location:- (a)MRS Sub Station - 800 Sqm. (b) 6 Pole structure- 600 Sqm. (c) 4 Pole Structure - 600 Sqm. (d)BISON Lab Sub Stn - 1200 Sqm. (e)Sub Stn No 1 - 1200 Sqm. (f)Sub Stn No 2 - 800 Sqm. (g)HQ Sub Stn - 800 Sqm. (h)MAFI Sub Stn - 600 Sqm.(j)MT Sub Station- 360 Sqm |