| 1 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5m depth for foundation etc or for shafts, wells cesspits manholes pier holes etc not exceeding 10 sqm on plan and in soft /loose soil etc complete all as specified and directed. |
| 2 | Returning, filing in, including spreading, levelling, watering and well rammingin layers not exceeding 25 cm in soft/loose soil etc complete all as specified and directed |
| 3 | Removal of excavated materials (soil) not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting points etc complete all as specified and directed. |
| 4 | M&L for sand filling under floor or in foundationsincluding gently punned as in cushioning to cable and for foundation in floor complete all as specified and directed. Note:- Punned thickness of sand shall be measured and paid. |
| 5 | M&L for brick protection cover to the under ground cable (with old size sub class \"B\" bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10 mmall as specified and directed. |
| 6 | M&L for boring of existing road / path upto 100mm for laying of GI pipe protection cover to the under ground cable and making good distrubed area / surface all as specified and directed. |
| 7 | S&F galvanised tube of 50 mm bore, light grade with all fitting laid in trenches complete all as specified and directed. |
| 8 | S&F galvanised tube of 80 mm bore, light grade with all fitting laid in trenches complete all as specified and directed. |
| 9 | M&L in repair for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 sq. mm 3.5 core complete all as specified and directed. Note - Excavation,earth work,sand,brick and protection pipe shall be measured and paid seperately. |
| 10 | M&L in repair for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sq. mm 3.5 core complete all as specified and directed. Note-Excavation,earth work,sand,brick and protection pipe shall be measured and paid seperately. |
| 11 | M&L in repair for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sq. mm 3.5 core complete all as specified and directed. Note :-Excavation, earth work, sand, brick and protection pipe shall be measured and paid seperately. |
| 12 | M&L in repair for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 185 sq. mm 3.5 core complete all as specified and directed. Note-Excavation,earth work,sand,brick and protection pipe shall be measured and paid seperately. |
| 13 | Disconnecting & taking out the existing unserviceable LT panel and S&F new LT Panel (415 Volts, 50 Hz , 3-phase, 4 wire supply) CPRI approved, factory assembled, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 40mm x 40mm x 6mm angle iron frame and 3.15 mm(for external) and 2 mm (for internal) thick MS Sheet CRCA sheet with both side (front and back) hinged , double door opening for external, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel grey paint first quality over a coat of red oxide primer complete mounted on angle iron leg made of angle iron 40mm x 40mm x 5 mm and 60 cm high above GL and 15 cm embedded in ground with PCC 1:2:4 type B1 of block size 30x30x30 cm comprising of the following:(a) Copper Bus bar: - Bus bar chamber having 4 nos air insulated copper strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer MCCB, as well as outgoings shall have copper TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.(b) Incoming: -(i) MCCB 4 pole, LT 415 Volts, 50 Hz AC grade, 400 amps rating 4 pole,50 KA, Adjustable thermal and adjustable magnetic release specially fixed for incoming supply with overload, short circuit and earth fault protection, adjustable type (Ics=100%Icu) - 01 No. (ii) Voltmeter 0-500V with selector switch 96 mm X 96 mm square flush mounted, with three-way rotary selector switch - 01 No.Continue....(at Sl Item No. 13.01) |
| 14 | Continue....(from Sl Item No. 13.00)(iii) Ammeter size 96 mm X 96 mm square dial flush pattern having dual range 500 amp with three-way rotary selector switch - 01 no.(iv) Three Nos CTs of suitable ratio (set of three)-01 Set(v) Indicating lamps (R,Y,B) - 01 set of three(vi) On-load change over switch 400 Amp, 4 pole, 415 volt - 01 No.(c) Outgoing(i) MCCB 4 pole, 415 Volts, 50 Hz AC grade 200 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 01 Nos.(ii) MCCB 4 pole, 415 Volts, 50 Hz AC grade 160 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu). -02 Nos.(iii) MCCB 4 pole, 415 Volts, 50 Hz AC grade 100 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 02 Nos.Note: -(i) All incoming/ outgoing cables shall be connected by suitable size gland plate /glands. And All spreader terminals of MCCBs should be connected with extension links (bus bar).(ii) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (iii) Panels shall be placed above 60 CM from ground level(iv) Outgoing Cables shall be fed with solid busbar connectors. |
| 15 | Disconnecting & taking out the existing unserviceable LT panel and S&F new LT Panel (415 Volts, 50 Hz , 3-phase, 4 wire supply) CPRI approved, factory assembled, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 40mm x 40mm x 6mm angle iron frame and 3.15 mm(for external) and 2 mm (for internal) thick MS Sheet CRCA sheet with both side (front and back) hinged , double door opening for external, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel grey paint first quality over a coat of red oxide primer complete mounted on angle iron leg made of angle iron 40mm x 40mm x 5 mm and 60 cm high above GL and 15 cm embedded in ground with PCC 1:2:4 type B1 of block size 30x30x30 cm comprising of the following:(a) Copper Bus bar: - Bus bar chamber having 4 nos air insulated copper strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer MCCB, as well as outgoings shall have copper TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.(b) Incoming: -(i) MCCB 4 pole, LT 415 Volts, 50 Hz AC grade, 250 amps rating 4 pole, 36 KA, Adjustable thermal and adjustable magnetic release specially fixed for incoming supply with overload, short circuit and earth fault protection, adjustable type (Ics=100%Icu) - 01 No. (ii) Voltmeter 0-500V with selector switch 96 mm X 96 mm square flush mounted, with three-way rotary selector switch - 01 No.Continue....(at Sl Item No. 14.01) |
| 16 | Continue....(from Sl Item No. 14.00)(iii) Ammeter size 96 mm X 96 mm square dial flush pattern having dual range 500 amp with three-way rotary selector switch - 01 no.(iv) Three Nos CTs of suitable ratio (set of three)-01 Set(v) Indicating lamps (R,Y,B) - 01 set of three(vi) On-load change over switch 250 Amp, 4 pole, 415 volt - 01 No.(c) Outgoing(i) MCCB 4 pole, 415 Volts, 50 Hz AC grade 100 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 03 Nos.(ii) MCCB 4 pole, 415 Volts, 50 Hz AC grade 63 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu). -03 Nos. Note: -(i) All incoming/ outgoing cables shall be connected by suitable size gland plate /glands. And All spreader terminals of MCCBs should be connected with extension links (bus bar).(ii) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (iii) Panels shall be placed above 60 CM from ground level(iv) Outgoing Cables shall be fed with solid busbar connectors. |
| 17 | Disconnecting & taking out the existing unserviceable LT panel and S&F new LT Panel (415 Volts, 50 Hz , 3-phase, 4 wire supply) CPRI approved, factory assembled, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 40mm x 40mm x 6mm angle iron frame and 3.15 mm(for external) and 2 mm (for internal) thick MS Sheet CRCA sheet with both side (front and back) hinged , double door opening for external, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel grey paint first quality over a coat of red oxide primer complete mounted on angle iron leg made of angle iron 40mm x 40mm x 5 mm and 60 cm high above GL and 15 cm embedded in ground with PCC 1:2:4 type B1 of block size 30x30x30 cm comprising of the following:(a) Copper Bus bar: - Bus bar chamber having 4 nos air insulated copper strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer MCCB, as well as outgoings shall have copper TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.(b) Incoming: -(i) MCCB 4 pole, LT 415 Volts, 50 Hz AC grade, 200 amps rating 4 pole, 36 KA, Adjustable thermal and adjustable magnetic release specially fixed for incoming supply with overload, short circuit and earth fault protection, adjustable type (Ics=100%Icu) - 01 No. (ii) Voltmeter 0-500V with selector switch 96 mm X 96 mm square flush mounted, with three-way rotary selector switch - 01 No.Continue....(at Sl Item No. 15.01) |
| 18 | Continue....(from Sl Item No. 15.00)(iii) Ammeter size 96 mm X 96 mm square dial flush pattern having dual range 500 amp with three-way rotary selector switch - 01 No.(iv) Three Nos CTs of suitable ratio (set of three) - 01 Set(v) Indicating lamps (R,Y,B) - 01 (set of three)(vi) On-load change over switch 200 Amp, 4 pole, 415 volt - 01 No.(c) Outgoing(i) MCCB 4 pole, 415 Volts, 50 Hz AC grade 63 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 04 Nos.Note: -(i) All incoming/ outgoing cables shall be connected by suitable size gland plate /glands. And All spreader terminals of MCCBs should be connected with extension links (bus bar).(ii) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (iii) Panels shall be placed above 60 CM from ground level(iv) Outgoing Cables shall be fed with solid busbar connectors. |
| 19 | Disconnecting & taking out the existing unserviceable LT panel and S&F new LT Panel (415 Volts, 50 Hz , 3-phase, 4 wire supply) CPRI approved, factory assembled, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 40mm x 40mm x 6mm angle iron frame and 3.15 mm(for external) and 2 mm (for internal) thick MS Sheet CRCA sheet with both side (front and back) hinged , double door opening for external, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel grey paint first quality over a coat of red oxide primer complete mounted on angle iron leg made of angle iron 40mm x 40mm x 5 mm and 60 cm high above GL and 15 cm embedded in ground with PCC 1:2:4 type B1 of block size 30x30x30 cm comprising of the following:(a) Copper Bus bar: - Bus bar chamber having 4 nos air insulated copper strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer MCCB, as well as outgoings shall have copper TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.(b) Incoming: -(i) MCCB 4 pole, LT 415 Volts, 50 Hz AC grade, 400 amps rating 4 pole,50 KA, Adjustable thermal and adjustable magnetic release specially fixed for incoming supply with overload, short circuit and earth fault protection, adjustable type (Ics=100%Icu) - 01 No. (ii) Voltmeter 0-500V with selector switch 96 mm X 96 mm square flush mounted, with three-way rotary selector switch - 01 No.Continue....(at Sl Item No. 16.01) |
| 20 | Continue....(from Sl Item No. 16.00)(iii) Ammeter size 96 mm X 96 mm square dial flush pattern having dual range 500 amp with three-way rotary selector switch - 01 no.(iv) Three Nos CTs of suitable ratio (set of three)-01 Set(v) Indicating lamps (R,Y,B) - 01 set of three(vi) On-load change over switch 400 Amp, 4 pole, 415 volt - 01 No.(c) Outgoing(i) MCCB 4 pole, 415 Volts, 50 Hz AC grade 250 amps rating and 36 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 02 Nos.(ii) MCCB 4 pole, 415 Volts, 50 Hz AC grade 100 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu). -02 Nos.Note: -(i) All incoming/ outgoing cables shall be connected by suitable size gland plate /glands. And All spreader terminals of MCCBs should be connected with extension links (bus bar).(ii) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (iii) Panels shall be placed above 60 CM from ground level(iv) Outgoing Cables shall be fed with solid busbar connectors. |
| 21 | Disconnecting & taking out the existing unserviceable LT panel and S&F new LT Panel (415 Volts, 50 Hz , 3-phase, 4 wire supply) CPRI approved, factory assembled, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 40mm x 40mm x 6mm angle iron frame and 3.15 mm(for external) and 2 mm (for internal) thick MS Sheet CRCA sheet with both side (front and back) hinged , double door opening for external, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel grey paint first quality over a coat of red oxide primer complete mounted on angle iron leg made of angle iron 40mm x 40mm x 5 mm and 60 cm high above GL and 15 cm embedded in ground with PCC 1:2:4 type B1 of block size 30x30x30 cm comprising of the following: (a) Copper Bus bar: - Bus bar chamber having 4 nos air insulated copper strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer MCCB, as well as outgoings shall have copper TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.(b) Incoming: -(i) MCCB 4 pole, LT 415 Volts, 50 Hz AC grade, 400 amps rating 4 pole,50 KA, Adjustable thermal and adjustable magnetic release specially fixed for incoming supply with overload, short circuit and earth fault protection, adjustable type (Ics=100%Icu) - 01 No. (ii) Voltmeter 0-500V with selector switch 96 mm X 96 mm square flush mounted, with three-way rotary selector switch - 01 No.Continue....(at Sl Item No. 17.01) |
| 22 | Continue....(from Sl Item No. 17.00)(iii) Ammeter size 96 mm X 96 mm square dial flush pattern having dual range 500 amp with three-way rotary selector switch - 01 no.(iv) Three Nos CTs of suitable ratio (set of three)-01 Set(v) Indicating lamps (R,Y,B) - 01 set of three(vi) On-load change over switch 400 Amp, 4 pole, 415 volt - 01 No.(c) Outgoing(i) MCCB 4 pole, 415 Volts, 50 Hz AC grade 160 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu). -04 Nos.(ii) MCCB 4 pole, 415 Volts, 50 Hz AC grade 100 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 02 Nos.(iii) MCCB 4 pole, 415 Volts, 50 Hz AC grade 63 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 04 Nos.Note: -(i) All incoming/ outgoing cables shall be connected by suitable size gland plate /glands. And All spreader terminals of MCCBs should be connected with extension links (bus bar).(ii) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (iii) Panels shall be placed above 60 CM from ground level(iv) Outgoing Cables shall be fed with solid busbar connectors. |
| 23 | Disconnecting & taking out the existing unserviceable LT panel and S&F new LT Panel (415 Volts, 50 Hz , 3-phase, 4 wire supply) CPRI approved, factory assembled, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 40mm x 40mm x 6mm angle iron frame and 3.15 mm(for external) and 2 mm (for internal) thick MS Sheet CRCA sheet with both side (front and back) hinged , double door opening for external, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel grey paint first quality over a coat of red oxide primer complete mounted on angle iron leg made of angle iron 40mm x 40mm x 5 mm and 60 cm high above GL and 15 cm embedded in ground with PCC 1:2:4 type B1 of block size 30x30x30 cm comprising of the following:(a) Copper Bus bar: - Bus bar chamber having 4 nos air insulated copper strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer MCCB, as well as outgoings shall have copper TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.(b) Incoming: -(i) MCCB 4 pole, LT 415 Volts, 50 Hz AC grade, 250 amps rating 4 pole, 36 KA, Adjustable thermal and adjustable magnetic release specially fixed for incoming supply with overload, short circuit and earth fault protection, adjustable type (Ics=100%Icu) - 01 No. Continue....(at Sl Item No. 18.01) |
| 24 | Continue....(from Sl Item No. 18.00)(ii) Voltmeter 0-500V with selector switch 96 mm X 96 mm square flush mounted, with three-way rotary selector switch - 01 No.(iii) Ammeter size 96 mm X 96 mm square dial flush pattern having dual range 500 amp with three-way rotary selector switch - 01 no.(iv) Three Nos CTs of suitable ratio (set of three)-01 Set(v) Indicating lamps (R,Y,B) - 01 set of three(vi) On-load change over switch 250 Amp, 4 pole, 415 volt - 01 No.(c) Outgoing(i) MCCB 4 pole, 415 Volts, 50 Hz AC grade 100 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 04 Nos.Note: -(i) All incoming/ outgoing cables shall be connected by suitable size gland plate /glands. And All spreader terminals of MCCBs should be connected with extension links (bus bar).(ii) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (iii) Panels shall be placed above 60 CM from ground level(iv) Outgoing Cables shall be fed with solid busbar connectors. |
| 25 | Disconnecting & taking out the existing unserviceable LT panel and S&F new LT Panel (415 Volts, 50 Hz , 3-phase, 4 wire supply) CPRI approved, factory assembled, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 40mm x 40mm x 6mm angle iron frame and 3.15 mm(for external) and 2 mm (for internal) thick MS Sheet CRCA sheet with both side (front and back) hinged , double door opening for external, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel grey paint first quality over a coat of red oxide primer complete mounted on angle iron leg made of angle iron 40mm x 40mm x 5 mm and 60 cm high above GL and 15 cm embedded in ground with PCC 1:2:4 type B1 of block size 30x30x30 cm comprising of the following:(a) Copper Bus bar: - Bus bar chamber having 4 nos air insulated copper strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer MCCB, as well as outgoings shall have copper TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.(b) Incoming: -(i) MCCB 4 pole, LT 415 Volts, 50 Hz AC grade, 320 amps rating 4 pole, 36 KA, Adjustable thermal and adjustable magnetic release specially fixed for incoming supply with overload, short circuit and earth fault protection, adjustable type (Ics=100%Icu) - 01 No. Continue....(at Sl Item No. 19.01) |
| 26 | Continue....(from Sl Item No. 19.00)(ii) Voltmeter 0-500V with selector switch 96 mm X 96 mm square flush mounted, with three-way rotary selector switch - 01 No.(iii) Ammeter size 96 mm X 96 mm square dial flush pattern having dual range 500 amp with three-way rotary selector switch - 01 no.(iv) Three Nos CTs of suitable ratio (set of three)-01 Set(v) Indicating lamps (R,Y,B) - 01 set of three(vi) On-load change over switch 320 Amp, 4 pole, 415 volt - 01 No.(c) Outgoing(i) MCCB 4 pole, 415 Volts, 50 Hz AC grade 160 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 04 Nos.Note: -(i) All incoming/ outgoing cables shall be connected by suitable size gland plate /glands. And All spreader terminals of MCCBs should be connected with extension links (bus bar).(ii) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (iii) Panels shall be placed above 60 CM from ground level(iv) Outgoing Cables shall be fed with solid busbar connectors. |
| 27 | Disconnecting & taking out the existing unserviceable LT panel and S&F new LT Panel (415 Volts, 50 Hz , 3-phase, 4 wire supply) CPRI approved, factory assembled, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 40mm x 40mm x 6mm angle iron frame and 3.15 mm(for external) and 2 mm (for internal) thick MS Sheet CRCA sheet with both side (front and back) hinged , double door opening for external, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel grey paint first quality over a coat of red oxide primer complete mounted on angle iron leg made of angle iron 40mm x 40mm x 5 mm and 60 cm high above GL and 15 cm embedded in ground with PCC 1:2:4 type B1 of block size 30x30x30 cm comprising of the following:(a) Copper Bus bar: - Bus bar chamber having 4 nos air insulated copper strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer ACB, as well as outgoings shall have copper TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.(b) Incoming: -(i) ACB (Air Circuit Breaker) 4 Pole, 415 V, 50 KA, Manual Drawout type with microprocessor release of capacity 630 Amps and including extension terminals and Ics = 100% IcuContinue....(at Sl Item No. 20.01) |
| 28 | Continue....(from Sl Item No. 20.00)connecting using suitable fasteners, modification / fabrication if required - 01 No. (ii) Voltmeter 0-500V with selector switch 96 mm X 96 mm square flush mounted, with three-way rotary selector switch - 01 No.(iii) Ammeter size 96 mm X 96 mm square dial flush pattern having dual range 500 amp with three-way rotary selector switch - 01 no.(iv) Three Nos CTs of suitable ratio (set of three)-01 Set(v) Indicating lamps (R,Y,B) - 01 set of three(c) Outgoing(i) MCCB 4 pole, 415 Volts, 50 Hz AC grade 250 amps rating and 36 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 02 Nos.(ii) MCCB 4 pole, 415 Volts, 50 Hz AC grade 160 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu). -02 Nos.(iii) MCCB 4 pole, 415 Volts, 50 Hz AC grade 100 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 02 Nos.Note: -(i) All incoming/ outgoing cables shall be connected by suitable size gland plate /glands. And All spreader terminals of MCCBs should be connected with extension links (bus bar).(ii) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (iii) Panels shall be placed above 60 CM from ground level(iv) Outgoing Cables shall be fed with solid busbar connectors. |
| 29 | Disconnecting & taking out the existing unserviceable LT panel and S&F new LT Panel (415 Volts, 50 Hz , 3-phase, 4 wire supply) CPRI approved, factory assembled, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 40mm x 40mm x 6mm angle iron frame and 3.15 mm(for external) and 2 mm (for internal) thick MS Sheet CRCA sheet with both side (front and back) hinged , double door opening for external, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel grey paint first quality over a coat of red oxide primer complete mounted on angle iron leg made of angle iron 40mm x 40mm x 5 mm and 60 cm high above GL and 15 cm embedded in ground with PCC 1:2:4 type B1 of block size 30x30x30 cm comprising of the following: (a) Copper Bus bar: - Bus bar chamber having 4 nos air insulated copper strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer MCCB, as well as outgoings shall have copper TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.(b) Incoming: -(i) MCCB 4 pole, LT 415 Volts, 50 Hz AC grade, 320 amps rating 4 pole, 36 KA, Adjustable thermal and adjustable magnetic release specially fixed for incoming supply with overload, short circuit and earth fault protection, adjustable type (Ics=100%Icu) - 01 No. Continue....(at Sl Item No. 21.01) |
| 30 | Continue....(from Sl Item No. 21.00)(ii) Voltmeter 0-500V with selector switch 96 mm X 96 mm square flush mounted, with three-way rotary selector switch - 01 No.(iii) Ammeter size 96 mm X 96 mm square dial flush pattern having dual range 500 amp with three-way rotary selector switch - 01 no.(iv) Three Nos CTs of suitable ratio (set of three)-01 Set(v) Indicating lamps (R,Y,B) - 01 set of three(vi) On-load change over switch 320 Amp, 4 pole, 415 volt - 01 No.(c) Outgoing(i) MCCB 4 pole, 415 Volts, 50 Hz AC grade 160 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu). -02 Nos.(ii) MCCB 4 pole, 415 Volts, 50 Hz AC grade 100 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 02 Nos.(iii) MCCB 4 pole, 415 Volts, 50 Hz AC grade 63 amps rating and 25 KA rupturing capacity, adjustable thermal and fixed magnetic type (Ics=100%Icu) - 02 Nos.Note: -(i) All incoming/ outgoing cables shall be connected by suitable size gland plate /glands. And All spreader terminals of MCCBs should be connected with extension links (bus bar).(ii) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (iii) Panels shall be placed above 60 CM from ground level(iv) Outgoing Cables shall be fed with solid busbar connectors. |
| 31 | M&L in repair for earthing with galvanised iron earth plate electrode 600mm x 600 mm & 6 mm thick buried directly in ground vertically (earth pit not less than 2.25 metre deep below normal GL) with top of earth plate not less than 1.5 metre below Ground level, connected to GI strip 25x4 mm (up to 7.5 metre) by means of GI nuts, bolts & washers , earth strip protected with & including 40mm dia light grade GI pipe (up to 7.5 metre) all as shown in electrical plate No 3 of MES Schedule Part I, with & including PCC 1:3:6type C1for pit with cover of 50 mm thickRCC 1:1.5:3 type A1 reinforced with welded steel wire fabric not less than 4 Kg per Sqm, watering arrangements with 20 mm GI medium grade pipe , GI funnel with GI mesh, filling with common salt & charcoal in alternate layers, necessary excavation and earth works in any type of soil, including test point, testing & commissioning, complete all as specified and directed.Note :- 1. The insulation procedure shall be followed as per instruction of the earth electrode manufacturer. 2. GI pipe of suitable size for protection against mechanical damage of main earth strip from earth electrode to test point up to 7.5 metre to be provided. The cost for the same shall be deemed to be included in the quoted rate. GI strip & GI protectionpipe beyond 7.5 metre shall be measured & paid separately.3. If desired earth resistance is not obtained during testing ,the earthing shall be re-done with out any extra cost. |