| 1 | Wiring for light point/ fan point/ exhaust fanpoint/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, withpiano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single corecable etc as required.Group A |
| 2 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 4 | Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep |
| 5 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator 8 way, Double door |
| 6 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA,C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 7 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (b) 63 amps |
| 8 | Supplying and fixing following rating, double pole, (single phaseand neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DBcomplete with connections, testing and commissioning etc. as required. 40 A |
| 9 | Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan Fresh Air Type complete with shutter blades etc. as required. |
| 10 | Brush Less Direct Current (BLDC) Motor Supply, Installation, Testing and Commissioning ofceiling fan with Brush LessDirectCurrent(BLDC)Motor,classofinsulation: B,3nos.metal( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%,suitable for operation withregulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019fan Supply, earthing etc. complete as req1200 mm,service value≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 11 | SITC of 10W surface/wall mounted LED Bulkhead factual impact dust and water resistant luminaires with IP 65/66 protection |
| 12 | LED Batten light (System lumen efficacy ≥105 Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body materialand construction as per IS : 10322 withdriver (Replaceable)as per the requirement with Driver efficiency >85% ,Operating voltage AC140-270 Volt,freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20,CRI>80, Flicker free, (flickershould be below 5 %), life time (LED,Driver & electrical circuitary), ofminimum 50000BurningHourswith,70%ofinitialLumenmaintained tilllife ends, CCT3000°K/ 4000°K / 5700°K/6000°K/6500°K(AsperANSIBin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BISstandard andtrade markcertificate(T.C.).Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. completeinallrespecti/cconnectionswith1.5sqmmFRLS,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy≥105 <120lm/Watt output . LM79 & LM80 Test reportfromNABLlab foralltestingrequiredforLED fixtures asper BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsink ofaluminumhousing such that LED junction temperature shall not rise above 90°C) CRCA Sheet Body (Thickness > 0.50 mm) 18- 22 watt |
| 13 | Supply,installation,testing and commissioning of Single /three phasemonoblock pumpset complete with all accessories workable on 240/415 Volts 50 Hz AC supply (a)01 HP (.75 KW) single phase pumpset head from 12-30 mtr suction and delivery 25X25 mm |
| 14 | LED Flood Light, powder coated pressure die cast aluminum (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg 120deg as per the application and the project requirement deg., suitable tilt able fitting, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) 135 lm/Watt output . LM79 & LM80 Test reportfromNABLlab foralltestingrequiredforLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsinkofaluminumhousing such that LED junction temperature shall not rise above 90°C) 70 watt |
| 15 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*4 sqmm |
| 16 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle). |
| 17 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 18 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 19 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required. |