| 1 | Supply, install, testing and commissioning in repair factory madeout door typeLT panel board of size not less than 1.5 mtr X 1mtr X 0.300 mtr, 440 volts , 3 phase , 4 wire system with powder coating providedto make it dust /vermin proof manufactured by CPRI approved manufacturer. The panel shall be made with 3.15 mm thick CRCA sheet for outer shell and inner shell made out of 1.6 mm thick CRCAsheet,double door with front openable with locking arrangement, provision of threaded earthing stud at bottom, inner shell be compartmentalized, front openable single door system lockable. Inner shell completely vermin proof and to accommodate incoming/outgoing MCCBs, MCBs, and TPN aluminium bus and extension links. Aluminium bus bar of capacity 600 Amps- 4Nos,including neutral duly insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size/rating of epoxy resininsulator all housed in suitable bus bar chamber.All control wires shall be as per the OEM recommendations and shall be properly bunched,tied, ferrulled for proper indentification and crimped with adequate size of lugs andprovision and fixing of Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps completealong with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable size of cable glands etc. Computer cut shelf adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided complete all as specified and directed. The panel shall consists of following accessories:- |
| 2 | Note : (i) Electrical connection from switchgear to bus bar would be through copper strips of suitable size.(ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size.(iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminumlugs of suitable rating incommensurate with that of switchgear.(iv)Cable glands would be provided for incoming & out going cables in panels.(v)The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item.(vi)The panel is to be fixed with Angle Iron Frame of size 50mm x 50mm x 6mm with bottam of panel having minimum 60cm height from existing ground/floor level. |
| 3 | Aluminium bus bar strips with proper colour code -04 No, 400 A capacity, insulator, nuts bolts etc complete. |
| 4 | Indicator Lamp-01 Set (Set of three) |
| 5 | IncommerMCCB 4P250Amp, 415V, 36 KA Ics = 100 Icu Adjustable type - 01 No |
| 6 | Outgoing, MCCB 4P125amp, 415V, 25 KAIcs = 100 Icu Adjustable type - 01 No |
| 7 | Outgoing, MCCB 4P100amp, 415V, 25 KAIcs = 100 Icu Adjustable type - 03 No |
| 8 | MCBTPN 32A,10KA B curve - 01 Nos for Street light panel |
| 9 | Digital Voltmeter 0 to 500 Vand Digital Ampmeter0 to 400A. with selector switich Make-Legrand/Minilac |
| 10 | Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles. |
| 11 | Supply, install testing and commissioning in repair factory madeout door typeLT panel board of size not less than 1mtr X 0.900mtr X 0.300 mtr, 440 volts , 3 phase , 4 wire system with powder coating providedto make it dust /vermin proof, manufactured by CPRI approved manufacturer. The panel shall be made with 3.15 mm thick CRCA sheet for outer shell and inner shell made out of 1.6 mm thick CRCAsheet, double door with front openable with locking arrangement, provision of threaded earthing stud at bottom, inner shell be compartmentalized, front openable single door system lockable. Inner shell completely vermin proof and to accommodate incoming/outgoing MCCBs, MCBs, and TPN aluminium bus and extension links. Aluminium bus bar of capacity 500 Amps- 4Nos,including neutral duly insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size/rating of epoxy resininsulator all housed in suitable bus bar chamber.All control wires shall be as per the OEM recommendations and shall be properly bunched, tied, ferrulled for proper indentification and crimped with adequate size of lugs andprovision and fixing of Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps completealong with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable size of cable glands etc. Computer cut shelf adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The panel shall consists of following accessories complete all as specified and directed:- |
| 12 | Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size.(ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size.(iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminumlugs of suitable rating incommensurate with that of switchgear.(iv)Cable glands would be provided for incoming & out going cables in panels.(v)The cost of fixing of the panel on suitable PCC (1:3:6) type C-1 (using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item.(vi)The panel is to be fixed with Angle Iron Frame of size 50mm x 50mm x 6mm with bottam of panel having minimum 60cm height from existing ground/floor level. |
| 13 | Aluminium bus bar strips with proper colour code -04 No, 500 A capacity, insulator, nuts bolts etc complete. |
| 14 | Indicator Lamp-01 Set (Set of three) |
| 15 | Incomer MCCB 4P250 amp with thermal magnetic release , 415V, 36 KA- 01 NoMake Legrand cat no-4220 49 //Havells |
| 16 | Outgoing, MCCB 4P100 amp with thermal magnetic release , 415V, 25 KA- 02 No (for Distribution panel) Make Legrand cat no-4200 52/Havells |
| 17 | Outgoing, MCCB 4P63 amp with thermal magnetic release , 415V, 25 KA- 03 No (for Distribution panel) Make Legrand cat no-4200 53 /Havells |
| 18 | Digital Voltmeter 0 to 500 Vand Digital Ampmeter0 to 400A. with selector switich Make-Legrand/Minilac |
| 19 | Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles. |
| 20 | Supply, laying, jointing, commissioning and testing XLPEinsulated screened PVC bedded, armoured,heavy duty underground electric cable in repair with stranded aluminium conductor 1100 volts grade confirming to IS-7098 (Part-I-1988) laid in trenches/ducts/wall / floor / pipes/ poles including cable glands and aluminium lugsof appropriate size, PVC sleeve etcincluding dismantling of old LT UG cables complete all as specified and directed for following sizes . Make :- Havells / Gloster / Finolex / Polycab |
| 21 | 300 sq mm 3.5 core . |
| 22 | 240 sq mm 3.5 core |
| 23 | 150 sq mm 3.5 core |
| 24 | 95 sq mm 3.5 core |
| 25 | 70 sq mm 3.5 core |
| 26 | 50 sq mm 3.5 core . |
| 27 | 35 sq mm 3.5 core |
| 28 | 25 sq mm 3.5 core |
| 29 | 16 sq mm 4 core |
| 30 | NOTE :- Earth work , bricks , riddled earth , GI pipe for protection of cable will be measured & paid under under relevant items of schedule . |
| 31 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size25 Sqmm to 50 Sqmm 3.5 core/4 core cable complete all as specified and directed. |
| 32 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts gradeof size from 70 Sqmm to 120 Sqmm 3.5 core /4 core cable complete all as specified and directed. |
| 33 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of sizefrom 150 Sqmm to 185 Sqmm 3.5 core/4 core cable complete all as specified and directed. |
| 34 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of sizefrom 240 Sqmm to 300 Sqmm 3.5 core/4 core cable complete all as specified and directed. |
| 35 | Supply and Fixing in repair ofdouble fitted polymer fabric HDPE fresh air filter(Filter class-G3 as per EN 779) washable/cleanable type having efficiency 95% to 99% down to particle size of 20 micron, fabricated out of CRCA sheet metal duly painted with two coat of grey hammer tone spray painted over two coats of red oxide primer, with lifting handle, Box/flanged type, aluminium spacer etc, of make Thermadyne/ Pall supralon filter / Micron filter complete all as specified and directed of following sizes :- |
| 36 | 600 mm x 500 mm x 45mm |
| 37 | 600 mm x 600 mm x 45mm |
| 38 | 600 mm x 400 mm x 45mm |
| 39 | 500 mm x 500 mm x 45mm |
| 40 | 500 mm x 400 mm x 45mm |
| 41 | Supply and Fixing in repair of double fitted polymer fabric HDPE fresh air filter(GL-type) washable/cleanable type having efficiency 95% to 99% down to particle size of 5 micron, fabricated out of CRCA sheet metal duly painted with two coat of grey hammer tone spray painted over two coats of red oxide primer, with lifting handle, Box/flanged type, aluminium spacer etc, including taking down of make Thermadyne/ Pall supralon filter / Micron filter complete all as specified and directed of following sizes :- |
| 42 | 600 mm x 500 mm x 300 mm |
| 43 | 600 mm x 600 mm x 300 mm |
| 44 | 600 mm x 400 mm x 300 mm |
| 45 | 500 mm x 500 mm x 300 mm |
| 46 | 500 mm x 400 mm x 300 mm |
| 47 | 500mm x 400 mm x 300 mm bag type filter 5 micron |
| 48 | Supply and Fixing in repair offilter \"HEPA\"(EN-1882) with fibre glass paper filtering media capacited 1000 CFM efficiency 99.97% down to particle size of 0.3 to 0.5 micron aluminium frames box type ofsize 500x400x300mm including taking downof make Thermadyne/ Pall supralon filter / Micron filter complete all as specified and directed. |
| 49 | Supply and fix in repair MCCB of following capacities complete all as specified and directed:-Make : L & T/Legrand/ABB/Havells |
| 50 | 400A,TP.415V,50 Hz, 36 KA adjustable type, ics=100%icu |
| 51 | 250A,TP.415V,50 Hz 36 KA adjustable type, ics=100%icu |
| 52 | 160A,TP.415V,50 Hz 36 KA adjustable type, ics=100%icu |
| 53 | 125A,TP.415V,50 Hz, 25KA adjustable type, ics=100%icu |
| 54 | 100A,TP,415V,50Hz,25KA , ics=100%icu |
| 55 | 63A,TP,415V,50Hz,25KA , ics=100%icu |
| 56 | 40A,TP,415V,50Hz,16KA , ics=100%icu |
| 57 | 32A,TP,415V,50Hz,16KA , ics=100%icu |
| 58 | Supply and fixing 415 Volt 10 kA \"C\" curve MCB of TP upto 100 Amps and current carrying capacity in the DB \ Panel complete all as specified and directed. Make : L & T/Legrand/ABB/Havells |
| 59 | Supply and fix in repair of contactor of following capacities suitable for existing of panel and sample complete all as specified and directed. Make : L & T, Seimense, Legrand |
| 60 | 70A, TP with 2 NO + 2 NC |
| 61 | 40A, TP |
| 62 | 32A, TP |
| 63 | 25A, TP |
| 64 | 18A, TP |
| 65 | 12A, TP |
| 66 | 9A, TP |
| 67 | 3TF 52 with 2 NO + 2 NC |
| 68 | 3TF 54 with 2 NO + 2 NC |
| 69 | Supply and fix in repair of over load relay following capacities suitable as per the existing sample complete all as specified and directed. Make : L & T, Seimense, Legrand |
| 70 | MN5 of rating 20A to 33A |
| 71 | MN5 of rating30A to 50A |
| 72 | MN5 of rating 14A to 23A |
| 73 | MN5 of rating9A to 15A |
| 74 | MN5 of rating6A to 10A |
| 75 | MN5 of rating4.5A to 7.5A |
| 76 | Supply and fix in repair of Fuse holder Suitable for Bolted fuse-links rating 20 Amp suitable as per site requirement complete all as specified and directed.Make : L & T, Seimense, Legrand |
| 77 | Supply and fix in repair of Bolted fuse links SG BS type rating 2 Amp to 20 Ampsuitable as per site requirement complete all as specified and directed.Make : L & T, Seimense, Legrand |
| 78 | Supply and replace unservisable/rusted blower motor base plate of MS sutiable for 5 HP and 3 HP as per site requirment all as directed the cost of fabrication work for fixing the base plate is included in the cost complete all as specified and directed. |
| 79 | Supply and Replacement AHU blower DIDW fan blower having out velocity not exceeding S.P.(mm/wg) 50 to 60 m/s energy efficent fan with double inlet , double with forward or backward curved impeller for high static pressure mounted on aluminum extended side rail base frame, and to be fitted on the existing AHU for following complete all as specified and directed:Make:Kruger (MH Phase -1 Central AC Plant) |
| 80 | Model : BDB-250-CM D20 |
| 81 | Model: KAT \"9/9\" S D20 |
| 82 | Supply and Replacement AHU blower DIDW fan blower having out velocity not exceeding S.P.(mm/wg) 50 to 60 m/s energy efficient fan with double inlet , double with forward or backward curved impeller for high static pressure mounted on aluminum extended side rail base frame, existing AHU of following capacity of Blowers motors ( Phase - 2 Central AC Plant) complete all as specified and directed :- |
| 83 | Blower for Capacity 5 HP motor Make- as per site requirement |
| 84 | Blower for Capacity 3 HP motor Make- as per site requirement |
| 85 | Supply & fixing, testing and commissioning of ACB 4 pole, 415 Volts, 630 Amps, 50KAManual Draw out type with microprocessor based LSIG & inbuilt temprature rise protection consisting of digital LCD display with battery back up,Current Metering andRS 485 Port. conforming to IS/IEC 60947-2 complete with all accessories , including dismantling old ACB from the existing panel, complete all as specified and directed. Make :- Legrand/Havells/ABB/L&T |
| 86 | Supply & fixing, testing and commissioning of ACB 4 pole, 415 Volts, 800 Amps, 50KAManual Draw out type with microprocessor based LSIG & inbuilt temprature rise protection consisting of digital LCD display with battery back up,Current Metering andRS 485 Port. conforming to IS/IEC 60947-2 complete with all accessories , including dismantling old ACB from the existing panel, complete all as specified and directed. Make :- Legrand/Havells/ABB/L&T |
| 87 | Supply & fixing, testing and commissioning of ACB 4 pole, 415 Volts,1000 Amps, 50KAManual Draw out type with microprocessor based LSIG & inbuilt temprature rise protection consisting of digital LCD display with battery back up,Current Metering andRS 485 Port. conforming to IS/IEC 60947-2 complete with all accessories , including dismantling old ACB from the existing panel, complete all as specified and directed. Make :- Legrand/Havells/ABB/L&T |
| 88 | Dismantling and taking out old AHU unit from the room and Supply, Install, Testing and commisiong by OEM new AHUunit with blower motor 7.5 hp and internal coil heater 20 watts and connecting with Inlet and outlet pipe with suitable welding work and refixing the ducting work of the the AHU room complete all as specified by OEM of the AC plant and complete all as specified and directed.Note :- (i)The guarentee of 12 months is to be provide by the the OEM of the AHU Unit for which rates are included in quotated rate.ii)The cost of training to the working staff / operator inclusive in quotated rate.iii)Trial run to be given for at least 72 hours from the changing of the AHU unit .(iv)Contractor has to visit the AC plant and check the AHU room parameters befour quoting the tender. Make:- BLUE STAR/ VOLTAS/ DAIKIN/ CARRIER |
| 89 | Decarbonizing and servicing of LT indoor/outdoor Panel/feeder pillar box of Plant room and AHU rooms any type and cleaning dirt and dust from the panel and removing unserviceable MCCBs, burnt busbars sleeves, unserviceable indicator lamps, unserviceable Ammeter,unserviceable Volt meter , replacing burnt, damaged bus bar of any size and fixing proper hanging front and rear openings, welding of hinges including welding of brokieng MS sheet using extra sheetsreplace burnt thimbles with new existing size thimbles replacing with new MCCB,incluidng dismantling the existing connected cables and re-connecting the same cables, complete all as specified and directed. Note :- (i) The rates are inclusive of any T&P used for cleaning the panels. (ii) The rates inclusive of minor spares ( Nut bolts , washers, insulation sleeves, indicator lamps, CT coils push buttons etc) (iii) Minor fabrication work for reparing the doors ans hingesare included in the quoted cost. |