| 1 | Part A |
| 2 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 3 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 4 | 2 X 16 sq. mm + 1 X 6 sq. mm earth wire |
| 5 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 6 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 7 | 100 A, 30kA, FPMCCB |
| 8 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. |
| 9 | 16 A switch |
| 10 | 3 pin 6 A socket outlet |
| 11 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 12 | 16 A switch |
| 13 | 6 A switch |
| 14 | 6 pin 16 A socket outlet |
| 15 | 3 pin 6 A socket outlet |
| 16 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 17 | 1 or 2 Module (75mmX75mm) |
| 18 | Supplying and fixing 16 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 19 | Single pole |
| 20 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 21 | 25 mm |
| 22 | Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Cable in existing conduit/ on surface, Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force: 11.5Kg etc. complete as required. |
| 23 | 1 run of cable |
| 24 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt). Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm). |
| 25 | 36 watt |
| 26 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required |
| 27 | 3 x 1.5 sq. mm |
| 28 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 29 | 16 way, Double door |
| 30 | Part B |
| 31 | Supplying and fixing of computer point RJ-45 modular type in compatiable box along with cover plate etc. complete make legrand or equivalent |
| 32 | Supply and fixing of 63A 240/415 V 10KA C curve TPN minitature Ckt breaker suitable for inductive load of following connection in the existing MCB DB complete with connection testing and commissioing etc as required make Havells/Legrand/Scheider |
| 33 | 63 A TPN MCB |
| 34 | 63 A, 10 kA, \"C\" curve dule pole MCB |
| 35 | Supply of sheet steel MCB enclosure for 4 pole MCB |
| 36 | Supply of sheet steel MCB enclosure for 2 pole MCB |
| 37 | Supply of 32 mm PVC cassing |
| 38 | Hylam sheet (3mm thick) of required size 2\"/2\" |