| 1 | WIRING |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 3 | Group C |
| 4 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 5 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 6 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 7 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 8 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 9 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 10 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 11 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 12 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 13 | Supplyingandfixingtwomodulesteppedtype electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 14 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 15 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 16 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet (3Module) and 15/16 A modular switch, connections etc. as required. |
| 17 | Supplying and fixing extra conduit down rod of 20 mm dia, 2 X 10 cm length, wiring with 2 X 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable including painting etc. as required. (Note : Morethan5cmlengthshallberoundedtothe nearest 10 cm and 5 cm or less shall be ignored) |
| 18 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 19 | Installation, Testing and Commissioning ofexhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 20 | Upto 450 mm sweep |
| 21 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 22 | Wiring for group controlled (looped) light point/fan point/exhaustfanpoint/callbellpoint (without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit,and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 23 | Group A |
| 24 | Supplying of following specification exhaust fan including connection etc. as required. Make:havells/almonard or Equivalent |
| 25 | Heavy duty 380mm sweep exhaust fan speed>1400rpm |
| 26 | MCCB, MCB & DB\"S |
| 27 | Providingandfixingfollowingratingandbreaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 28 | 160 A,36KA,FPMCCB |
| 29 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar,neutralbusbar,earthbar,dinbar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 30 | 16 way, Double door |
| 31 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 32 | 8 way (4 + 24), Double door |
| 33 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DBcompletewithconnections,testingand commissioning etc. as required. |
| 34 | Single pole |
| 35 | Double pole |
| 36 | Triple pole |
| 37 | Four pole |
| 38 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 39 | Supplying and fixing following rating,double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 40 | 25 A |
| 41 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in theexistingMCBDBcompletewithconnections, testing and commissioning etc. as required. |
| 42 | 63 A |
| 43 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \"C\" curve DPMCBcompletewithconnections,testingand commissioning etc. as required. |
| 44 | Supplying and fixing TP/FP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V \"C\" curve TP MCB complete with connections, testing and commissioning etc. as required. |
| 45 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCCB and MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 46 | 12 way (160 MCCB + 36), Double door |
| 47 | Supplying and fixing following rating, following pole, 415 V, C curve MCB suitable for inductive loadintheexistingMCB DBcompletewith connections, testing and commissioning etc. as required. |
| 48 | 40-63 A TP |
| 49 | 40-63 A FP |
| 50 | Supply and fixing of Rotary Handle |
| 51 | Supply and fixing of Rotary Handle Vary depthsuitable for MCCB rating upto 160A including necessory arrangement, cutting, welding, shaping etc. as required for fixing on exixting panel . |
| 52 | CABLE TRAYS |
| 53 | Supplying and installing following size of perforated Hot Dipped GalvanisedIron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling withtwo numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts,fastner etc as required. |
| 54 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 55 | EARTHING |
| 56 | Supplying and fixing 12 SWG copper wire on surface or in recess for loop earthing as required. |
| 57 | LED LIGHT |
| 58 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body materialand construction as per IS : 10322 with driver (Replaceable)as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt,frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20,CRI>80, Flicker free, (flickershould be below 5 %), life time (LED, Driver & electrical circuitry), ofminimum 50000BurningHours with 70%ofinitial Lumenmaintained tilllife ends, CCT 3000°K / 4000°K / 5700°K /6500°K (AsperANSIBin), SDCM(Standard Deviation Colour Matching) <3,Maximum power consumption shouldnotmorethanthespecifiedratingand Fixture shall be of relevant BIS standard. ManufacturesWordMark/NameEngraved/ Embossing/ Screen printing on housing. complete inallrespecti/c external connectionswith 1.5sq mm FRLS/HFFR,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy ≥105 <120lm/Watt output . LM79 & LM80 Test report andalltestingrequiredforLED fixtures as per BISshall be submitted.Shape size andCCTshallbeasapprovedbyEngineer-in- Charge as per requirement. (Thermalmanagement: heatsinkofaluminiumhousing such that LED junction temperature shall not rise above 90°C). |
| 59 | 18- 22 Watt -Powder coated die cast /Extruded aluminiumBody (Thickness > 1.20 mm) |
| 60 | BLDC FAN |
| 61 | Brush Less Direct Current (BLDC) Fan without Remote Supply,Installation,TestingandCommissioningof ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body PowerFactornotlessthan 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%,suitable for operation withregulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019fani/c externalconnectionswith 1.5sq.mmFRLS/HFFR, PVC insulated copper conductor singlecorecable andearthingetc.asrequired. |
| 62 | 1200mm,service value≥ 6.0 CM/Min/Watt, air delivery 230 CM/Min (Minimum) |
| 63 | MV CABLE LAYING |
| 64 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 65 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 66 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 67 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 68 | MV CABLE JOINTING & END TERMINATION |
| 69 | Supplyingandmakingendterminationwithbrass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KVgrade as required. |
| 70 | 3½ X 95 sq. mm (45mm) |
| 71 | MISC.CIVIL ITEMS |
| 72 | Supply and fixing Fan Hook |
| 73 | Supplying and fixing of8/10 mm \"S/U\" type steel fan hook including chipping,welding, painting making good the damagesetc. as required |
| 74 | LABOUR |
| 75 | Removing following items, handing over to EMU store safely as required. |
| 76 | Tube light and Light fixture with/with outrad/clamp |
| 77 | Cealing fan withrad, regulator from switch board, including stacking of fan leafs |
| 78 | Point wiring including cealing rose, conduit, wires, switches(modular/piano type) switch board, clamps etc. as required |
| 79 | submain wiring including conduit, wires, clamps etc. as required |
| 80 | Switch board of any size including wires, switches(modular/piano type) switch board, clamps, GI/plastic box etc. as required |
| 81 | 2C,4C,3.5C armoured Al/Cu Cable of size less than 35 Sqmm etc. as required |
| 82 | SP Main switch board (HRC) of any size including wires, switch board, clamps etc. as required |
| 83 | SPN DB (Fuce type) of any size including wires, DB, clamps etc. as required |
| 84 | Three phase DB (Fuce type) of size less than 1Mtr.X0.5Mtr. including wires, DB, clamps etc. as required |
| 85 | CABLE |
| 86 | Supply of following size PVC/ XLPE Aluminium Armoured Cable, 650/1100V. Grade confirming to IS:7098 (Pt-1)1988 |
| 87 | 3.5x95 Sq.mm |
| 88 | PANEL BOARD AND ACCESSORIES |
| 89 | BUS BAR |
| 90 | Supplying and fixing of copper bus bar suitable for 160A MCCB switch from switch to the busbar in the existing panel board Including drilling the holes, nuts and bolts and insulation on the bus bar with colour code, hylum sheet for covering the busbar and other necessory arrangements to meet IS codes etc. as required. |
| 91 | Drawing and Approval |
| 92 | Submission of as fitted drawings and SLD of the work in Autocad DWG and PDF format alongwith physical copy of the samein the format and standard to get the approvalfrom electrical inspectorate.(along withseal,signature and license details) etc as required. |