| 1 | Taking down carefully copper / aluminium point wiring (light, fan, switch,socket or power, Bell & Two way point) complete with fitting such asswitches, sockets, ceiling rose,sketch light fittings etc, and making good the disturbed surface ofwalls and floors etc complete all as specified and directed. |
| 2 | Taking down carefully main switches DB\"s/ MCB DB\"s and making good the disturbed surfaces of wallsetc complete all as specified and directed. |
| 3 | Taking down carefully copper / aluminium sub mainwiring including teak wood batten / conduit and making good the disturbed surface of walls directed. |
| 4 | Material and labour for point wiring with 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor drawn through and incuding medium grade PVC conduit with all accessories such as elbow, tee, bend etc, ISI marked,concealed on wall/ceiling and incuding provision of 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor green colour as earth continuity conductor and connected to common earth dolly with suitable size of lugs, including or modular metal flush box for fixing modular switch, socket etc and mild steel sunken boxes made out of 1.6 mm thick mild steel sheet metal with earth dolly and coated of red oxide primer both internally and externally including provision of new 3 mm thick plastic laminated sheet top cover for housing the switches, socket outlets, fan regulators etc with brass screws and brass washers and making good the disturbed surfaces as per existing for one light point controlled by one way switch complete all as specified and directed. Note :- Switches, socket and fan regulators and modular box inner and outer cover plate to be measured and paid separately. |
| 5 | All as per item no 04.00 above but one bell point controlled by one bell Push |
| 6 | All as per item no 04.00 above but one 5 Amps socket out let point controlled by one switch on same board with other switches. |
| 7 | All as per item no 04.00 above but one 5 Amps socket out let point on independent board controlled by one switch. |
| 8 | All as per item no 04.00 above but one light point controlled by one, two way switch 5 Amps |
| 9 | All as per item No 04.00 above but wiring with 2.5 sq mm single core copper conductor for one socket out let 15/16 amps point on the independent board. |
| 10 | Material and labour for point wiring with 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor drawn through and non metallic rigid PVC conduit/ casing caping double lock system with all accessories such as elbow, tee, bend etc, ISI marked on wall/ceiling and incuding provision of 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor green colour as earth continuity conductor and connected to common earth dolly with suitable size of lugs, including mild steel sunken boxes made out of 1.6 mm thick mild steel sheet metal with earth dolly and coated of red oxide primer both internally and externally including provision of new 3 mm thick plastic laminated sheet top cover for housing the switches, socket outlets, fan regulators etc with brass screws and brass washers and making good the disturbed surfaces as per existing for one light point controlled by one way switch complete all as specified and directed. Note :- Switches, socket and fan regulators to be measured and paid separately. |
| 11 | All as per item no 10.00 above but one bell point controlled by one bell Push |
| 12 | All as per item no 10.00 above but one 5 Amps socket out let point controlled by one switch on same board with other switches. |
| 13 | All as per item no 10.00 above but one 5 Amps socket out let point on independent board controlled by one switch. |
| 14 | All as per item No 10.00 above but wiring with 2.5 sq mm single core copper conductor for one socket out let 15/16 amps point on the independent board. |
| 15 | Material and labour for point wiring with 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor drawn through in existing conduit on wall/ceiling and incuding provision of 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor green colour as earth continuity conductor and connected to common earth dolly with suitable size of lugs, including mild steel sunken boxes made out of 1.6 mm thick mild steel sheet metal with earth dolly and coated of red oxide primer both internally and externally including provision of new 3 mm thick plastic laminated sheet top cover for housing the switches, socket outlets, fan regulators etc with brass screws and brass washers and making good the disturbed surfaces as per existing for one light point controlled by one way switch complete all as specified and directed. Note :- Switches, socket and fan regulators to be measured and paid separately. |
| 16 | All as per item no 15.00 above but one bell point controlled by one bell Push |
| 17 | All as per item no 15.00 above but one 5 Amps socket out let point on independent board controlled by one switch. |
| 18 | All as per item No 15.00 above but wiring with 2.5 sq mm single core copper conductor for one socket out let 15/16 amps point on the independent board. |
| 19 | Supply and fixing switch piano flush button single pole one way 5 amps, AC 240 Volts complete all as specified and directed. |
| 20 | Supply and fixing in repair switch piano flush button single pole one way 5 amps, AC 240 Volts complete all as specified and directed. |
| 21 | Supply and fixing socket outlet flush type 5 Amps, 5 pin, AC 240 Volts complete all as specified and directed. |
| 22 | Supply and fixing in repair socket outlet flush type 5 Amps, 5 pin, AC 240 Volts complete all as specified and directed. |
| 23 | Supply and fixing switch piano flush button single pole one way 15 Amps AC 240 volt complete all as specified and directed. |
| 24 | Supply and fixing in repair switch piano flush button single pole one way 15 Amps AC 240 volt complete all as specified and directed. |
| 25 | Supply and fixing socket outlet flush type multipurpose 2 in1, 3 pin 5 and 15 Amps, AC 240 volts complete all as specified and directed. |
| 26 | Supply and fixing in repair socket outlet flush type multipurpose 2 in1, 3 pin 5 and 15 Amps, AC 240 volts complete all as specified and directed. |
| 27 | Supply and fixing bell push single pole, 6 Amps, AC 240 Volts, flush type complete all as specified and directed. |
| 28 | Supply and fixing in repair bell push single pole, 6 Amps, AC 240 Volts, flush type complete all as specified and directed. |
| 29 | S&F in replacement Lamp holder, PVC / Polycarbonate type with back plate suitable for B22 lamp complete all as specified anddirected. |
| 30 | Supply and fixing celing rose surface bakelite 63.5 mm dia three terminal complete all as specified and directed. |
| 31 | Supply and fixing in repair celing rose surface bakelite 63.5 mm dia three terminal complete all as specified and directed. |
| 32 | Supply and fixing electronic Fan regulator 450 watt 2 module, with 5 step type regulator complete all as specified and directed. |
| 33 | Supply and fixing in repair for electronic Fan regulator 450 watt 2 module, with 5 step type regulator complete all as specified and directed. |
| 34 | Supply and fixing ding dong Bell, AC 240 Volts,single pole complete all as specified and directed. |
| 35 | Supply and fixing Bell multi music typeAC 240 Volts, single pole complete all as specified and directed. |
| 36 | Refixing paino switch of any capacity 5 /15 amps obtained from respective item of BOQ complete all as specified and directed. |
| 37 | Refixing socket 5 amps or 15 amps capcaity obtained from respective item of BOQ complete all as specified and directed. |
| 38 | Supply and fixing white finished single mounting one modular inner plate & outer top cover plate suitable for housing modular accessories with one module metal flush box complete all as specified and directed. |
| 39 | All as per item no 38.00 above but suitablefor 2 modules |
| 40 | All as per item no 38.00 above but suitablefor 3 modules |
| 41 | All as per item no 38.00 above but suitablefor 4 modules |
| 42 | All as per item no 38.00 above but suitablefor 6 modules |
| 43 | All as per item no 38.00 above but suitablefor 8 modules |
| 44 | All as per item no 38.00 above but suitablefor 12 modules |
| 45 | Supply and fixing modular Switch10 Amps single pole, one waycomplete all as specified and directed. |
| 46 | Supply and fixing Modular Socket outlet, multi purpose, 5 Pin 10 Amps flush typecomplete all as specified and directed. Make: Legrand, Model: Myrius / Anchor, Model: Woods / Schneider, Model: Opale. |
| 47 | Supply and fixing ModularBell push flush type,10 Amps fixedcomplete all as specified and directed. |
| 48 | Supply and fixing Modular Socket outlet, multi purpose, 6 pin 16 Amps universal socketcomplete all as specified and directed. |
| 49 | Supply and fixingModularSwitch 16 Amps single pole, one waycomplete all as specified and directed. |
| 50 | Supply and fixing modular fan regulator 150 Watt of four step type complete all as specified and directed. |
| 51 | Supply and fixing Modular Socket outlet 3 pin 25 Amps two module AC 230 volts complete all as specified and directed. |
| 52 | Supply and fixingModularstarter Switch 25 Amps two module AC 230 volts complete all as specified and directed. |
| 53 | Supply and fixing in repair PVC rectangular block for mountingswitches, sockets ,fan regulatoretc with 3 mm thick plastic laminated sheet cover of size 350 x 300 x 50 mm complete all as specified and directed. |
| 54 | All as per item no 53.00 above but of size 250 x 200 x 50 mm. |
| 55 | All as per item no 53.00 above but of size 200 x 150 x 50 mm. |
| 56 | All as per item no 53.00 above but of size 175 x 100 x 50 mm. |
| 57 | All as per item no 53.00 above but of size100 x 100 x 50 mm size. |
| 58 | Supply and fixing in repair pressed steel terminal rectangular sunken boxes made out of 1.6 mm thick mild steel sheet metal with earth dolly for mounting, switches, sockets, fan regulator etc including 3.00 mm thick plastic laminated sheet cover of suitable size for MS box size of 250 x 300 x 50 mm with brass screws and brass washers complete all as specified and directed. |
| 59 | All as per item no 58.00 above but of MS box size of 200mm X 250 mm |
| 60 | All as per item no 58.00 above but of MS box size of 200mm X 150 mm |
| 61 | All as per item no 58.00 above but of MS box size of150mm X 100 mm |
| 62 | All as per item no 58.00 above but of MS box size of 100mm X 100 mm |
| 63 | Supply and fixing in repair plastic laminated bakelite sheet cover of Hylam brand 3.00 mm thick including cutting holes for switches, sockets etc as per requirement including fixing with brass machine screws and washer for size 275 mm X 325 mm complete all as specifed and directed. |
| 64 | All as per item no 63.00 above but of size225 mm X 275 mm |
| 65 | All as per item no 63.00 above but of size 225 mm X 175 mm |
| 66 | All as per item no 63.00 above but of size175 mm X 125 mm |
| 67 | All as per item no 63.00 above but of size125 mm X 125 mm |
| 68 | Supply and fixing distribution board Vertical Triple pole & nuetral (VTPN) 415 volts iron clad, verticle type double door with IP-43 1K-09 protection suitable for MCCB as outgoing 415 volts 3 phase 50 C/s 4 way, complete with appropriate size copper bus bar and netural link confirming including cutting chases to wall for fixing DB and making good the disturbed wall surface complete all as specified and as directed by Engineer-in-Charge. |
| 69 | Supply and fixing double door TPN DBs 4 wayof powder coated DB\"s suitable for MCB\"s fitted with bus bar,Neutral link,Earth bar and Din ral & DB\"s will be fitted concealed in wall / surface as per site required complete all as specified and directed. |
| 70 | Supply and fixingdouble door SPN DBs 12 wayof powder coated DB\"s suitable for MCB\"s fitted with bus bar,Neutral link,Earth bar and Din ral as per existing finishing complete all as specified and directed. |
| 71 | Supply and fixingdouble door SPN DBs 8 wayof powder coated DB\"s suitable for MCB\"s fitted with bus bar,Neutral link,Earth bar and Din ral as per existing finishing complete all as specified and directed. |
| 72 | Supply and fixing double door SPN DBs 4wayof powder coated DB\"s suitable for MCB\"s fitted with bus bar,Neutral link,Earth bar and Din ral as per existing finishing complete all as specified and directed. |
| 73 | Supply and fixing single door SPN DBs 2 wayof powder coated DB\"s suitable for MCB\"s fitted with bus bar,Neutral link,Earth bar and Din ral as per existing finishing complete all as specified and directed. |
| 74 | Supply and fixing MCB SPN 5 to 40 amps 10 KA ,C-series including connection with suitable size aluminium / copper lugs complete all as specified and directed. |
| 75 | Supply and fixingMCB SPN 40 to 63 amps 10 KA ,C-seriesincluding connection with suitable size aluminium / copper lugs complete all as specified and directed. |
| 76 | Supply and fixingMCB SP 240 volts 5 to 32 Amps, 10 KA breaking capacity,\"C\" type including connection with suitable size aluminium / copper lugs complete all as specified and directed. |
| 77 | Supply and fixing MCB TPN 50 to 63 amps 10 KA ,C-seriesincluding connection with suitable size aluminium / copper lugs complete all as specified and directed. |
| 78 | Supply and fixing MCCB 3 Pole 100 amps 415V, breaking capacity of 16 KA and Icu= 100% of lcs including connection with suitable size aluminium / copper lugs complete all as specified and directed. |
| 79 | Refixing MCB TPN/SPN/SP any size, capacity obtained from respective item of BOQ complete all as specified and directed. |
| 80 | Refixing LED tube light fittings any type, wattage and any size obtained from respective item of BOQ complete all as specified and directed. |
| 81 | Supply and fixing LED tube light batten box type with decorative end caps suitable single tube 1x 18/20 watt T8 lamps type complete with both end bi-pin holder and all accessories internally pre wired and fixed to wall/ceiling incl fittings accessories and connecting with all accessories internally pre wired and incl connecting up with twin core twisted flexible copper conductor cable suitable size all as specified. |
| 82 | supply and fixing LED tube rod 18/20 watt230 volt T8 type complete with electric electronic driver incl fittings accessories and connecting with all accessories internally pre wired and incl connecting up with twin core twisted flexible copper conductor cable suitable size all as specified. |
| 83 | Supply and fixing LED Batten light Aluminium Housing 18/20 watt230 volt T8 type complete with electric electronic driver incl fittings accessories and connecting with all accessories internally pre wired and incl connecting up with twin core twisted flexible copper conductor cable suitable size all as specified. |
| 84 | Supply and fixing LED batten tube light fitting 1x 10 watt 230 voltwall/ ceiling mounted luminaire with polycarbonate hoiusing and integrated electronic driver with all accessories internally pre wired and incl connecting up with twin core twisted flexible copper conductor cable suitable size all as specified. |
| 85 | Supply and fixing Wall light fixture lantern made up of metal with chrome finish and white colour diffuser complete with LED 9 watt lamp B-22 base including all necessary accessories and connection complete all as specified and directed. |
| 86 | Supply and fixing in repair Energy Savings Long Life 15 Watt 230 Volts50 Hz, IP20 rating recessed mounting downlight withaluminium housing and heat sink for better thermal performance and morden and minimalist design with flushed diffuser and as per site requirement ceiling cutout fitting for cool/warm or natural white light options as required including electronic driver of suitable capacity with PF>0.9 complete all as specified and directed. |
| 87 | Supply and fixing in repair Energy Savings Long Life 15 Watt 230 Volts50 Hz, IP20 rating surface mounting downlight withaluminium housing and heat sink for better thermal performance and morden and minimalist design with flushed diffuser and as per site requirement ceiling cutout fitting for cool/warm or natural white light options as required including electronic driver of suitable capacity with PF>0.9 complete all as specified and directed. |
| 88 | Supply and fixing in repair Energy Savings Long Life 12 Watt 230 Volts50 Hz, IP20 rating recessed mounting downlight withaluminium housing and heat sink for better thermal performance and morden and minimalist design with flushed diffuser and as per site requirement ceiling cutout fitting for cool/warm or natural white light options as required including electronic driver of suitable capacity with PF>0.9 complete all as specified and directed. |
| 89 | Supply and fixing in repair Energy Savings Long Life 18 Watt 230 Volts50 Hz, IP20 rating recessed mounting downlight withaluminium housing and heat sink for better thermal performance and morden and minimalist design with flushed diffuser and as per site requirement ceiling cutout fitting for cool/warm or natural white light options as required including electronic driver of suitable capacity with PF>0.9 complete all as specified and directed. |
| 90 | S&F recessed mounting fitting 1 x 36/42 watt ultra modern design Natural white/ Warm white architectural LED luminaire (2X2) feet which provides soft-light and glare free symmetrical illumination suitable for Armstrong / Grid Ceiling including LED driver and 36/42 watt LED for cool/warm or natural white light options as required including electronic driver of suitable capacity with PF>0.9 complete all as specified and directed. |
| 91 | S & F in replacement Building security LED light luminaire 1X25 W, pressure die cast housing with toghned glass, 240V, efficacy Min 110 Lm/Watt, IP-66, 5 KV external SPD , THD<10%, PF>0.95, CCT-5700K, High power SMD LEDs with LDR sensor working 10 Lm visibility for automatic ON/OFF operation and including cable for connection from celling rose with 1.5 Sqmm 3 CorePVC insulated stranded copper conductor (FRLS) cable including GI bracket medium grade bent to shape etc all as specified and directed. |
| 92 | Supply and fixing LED bulk head 10 watt fittings environmental friendly ultra modern energy saving surface mounted decorataive bulk head fitting with driver and prewired and necessary electric connection with PVC insulated twin twisted flexible copper wire of size 0.75 Sqmm complete all as specified and directed. |
| 93 | M&L for Sub main wiring two run single core PVC insulated unsheathed cable FRLSH 1100 volts grade, 6.00 Sqmm size with multistranded copper conductor, drawn in but excluding non metallic rigid PVC conduit including one run of 4.00 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor green colour as earth continuity conductor cable connected to earth dolly complete all as specifed and directed. |
| 94 | All as peritem No 93.00 but with two single core 4.0 Sqmm sizewith 2.5 Sqmm cable as earth conductor complete. |
| 95 | All as peritem No 93.00 but with two single core 2.5 Sqmm sizewith 2.5 Sqmm cable as earth conductor complete. |
| 96 | All as peritem No 93.00 but with two single core 1.5 Sqmm sizewith 1.5 Sqmm cable as earth conductor complete. |
| 97 | M&Lfor Rigid non metallic PVC conduitISI marked, medium grade, inclusive of all fitting such as tees,bends. Junction boxes, elbows saddles. Pipe hooks,couples and lock outs etc 25 mm external dia, fixed on surface mounted complete and making good disturbedsurfaces in repairs all directed. |
| 98 | M&Lfor Rigid non metallic PVC casing capingISI marked, medium grade,not less than 25 mm base size inclusive of all fitting such as tees,bends. Junction boxes, elbows saddleshooks,couples and lock outs etc fixed on surface mounted complete and making good disturbedsurfaces in repairs all directed. |
| 99 | Supply & fixing Sheet metal earth plug, socket, single pole and neutral with single pole MCB 32 Amps 240 volts fixed in repairs complete. |
| 100 | Supply and fixing ofEarthing to panel with galvanised steel earth plate electrode60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to galvanised earth lead wire 4.0mm dia by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3 of MES Schedule pt-I 2009, GI earth lead strip protected by GI pipe 40 mm dia medium grade and connected to earth test point includingexcavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion all as specified and directed. |
| 101 | (Note : The Scope of Work contained in \"Sch of Credit\" amounting to Rs. 50,172.00 (refer Sch of credit). The Quoted sum shall be arrived at after deducting the amount of “Sch of Credit” from the total amount of the ‘BoQ’ |