Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | SCHEDULE A PART I (BUILDING WORKS) |
| 2 | Lump sum price worked out by the contractor for Building works as listed in Sch ‘A’ Part I |
| 3 | SCHEDULE A PART II (INTERNAL WATER SUPPLY) |
| 4 | Lump sum price worked out by the contractor for Building works as listed in Sch ‘A’ Part II |
| 5 | SCHEDULE A PART III (INTERNAL Electric Supply) |
| 6 | Lump sum price worked out by the contractor for Building works as listed in Sch ‘A’ Part III |
| 7 | SCHEDULE A PART IV (External Water Supply) |
| 8 | Lump sum price worked out by the contractor for Building works as listed in Sch ‘A’ Part IV |
| 9 | SCHEDULE A PART V (External Electric Supply) |
| 10 | Lump sum price worked out by the contractor for Building works as listed in Sch ‘A’ Part V |
| 11 | SCHEDULE A PART VI (Area Drainage) |
| 12 | Lump sum price worked out by the contractor for Building works as listed in Sch ‘A’ Part VI |
| 13 | SCHEDULE A PART VII (Sewage Disposal) |
| 14 | Lump sum price worked out by the contractor for Building works as listed in Sch ‘A’ Part VII |
| 15 | SCHEDULE A PART VIII (Chain Link Fencing) |
| 16 | Lump sum price worked out by the contractor for Building works as listed in Sch ‘A’ Part VIII |
| 17 | SCHEDULE A PART IX (Road/Path/culvert) |
| 18 | Lump sum price worked out by the contractor for Building works as listed in Sch ‘A’ Part IX |
| 19 | SCHEDULE A PART X (Air Conditioning) |
| 20 | Lump sum price worked out by the contractor for Building works as listed in Sch ‘A’ Part X |
| 21 | SCHEDULE A PART XI (Earthwork and Site Clearance) |
| 22 | Lump sum price worked out by the contractor for Building works as listed in Sch ‘A’ Part XI |
| 23 | Sch A PartXII (Miscellaneous Items of B/R and E/M) |
| 24 | Supply and fixing of PVC low level flushing cistern 10 ltr capacity dual flushing white with inlet, ball valve, float and handle incl brackets incl 32mm dia PVC flush pipe for low level cistern fixed as in repair complete all as specified and directed. |
| 25 | Supply, installation, testing & commisioningof flame proof motor of capacity 2 HP, foot/flange mounted, 1440 RPM, 415 Volts incl pump 110 LPM temp 90 degree along with mounting base plate coupling & PCCfoundation as permanufacturer design, complete all as specified & directed. |
| 26 | Supply, installation & testing of flow meter flanged end SS 304, out put 4 to 20 mA, operating temp 70 degree celcius, mounting in line horizontal, flame proof enclosure, 230 V AC,9 Character X 2 Line LED Display, flow range 4 to 40 m3/hr, for line size 50 NB (2 inch) complete all as specified & directed |
| 27 | Supply & fix DOL starter of 2 HP incl 4 sqmm 3 core cable from starter to motor, complete all as specified and directed |
| 28 | Supply and fix Foot Valve conforming to IS 4038, Size 50 mm (2”) dia , complete all as specified & directed |
| 29 | Supply and fix Strainer Y type conforming to IS, size 50 mm (2”) dia complete all as specified & directed |
| 30 | M&L for construction of brick masonary valve chamber with 3.15 mm thick MS sheet covered on angle iron frame of size 50mm x 50mm x 6mm duly painted with two coat of black bituminous paint over coat of red oxide primer with and including all necessary earth work, excavation in soft/loose soil, returning filling in and removed of surplus soil to a distance not exc. 50 mtr, PCC work 15 mm thick in 1:3:6 in foundation projected 10 cms on all sides of external wall, brick work wall 23 cm thick with brunt sub class B bricks in cm 1:4, 15 mm thick plastering in cm 1:4 on internal wall surface and exposed external water surface etc with necessary locking arrangement with 50 mm size one No. Lock complete of internal size 600 mm x 600 mm x 600mm complete all as specified and directed. |
| 31 | Supply and fixing Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 280 V with output voltage stabilized at 230 V with accuracy of + 2.5% and suitable for 2 TR AC all as specified and directed. |
| 32 | Supply and fixing Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 280 V with output voltage stabilized at 230 V with accuracy of + 2.5% and suitable for 1.5 TR AC all as specified and directed. |
| 33 | Supply and fixing concealed type GI Sheet enclosure for Modular switches/ socket etc. complete with a 20 amps modular type motor starter (2 module) with one single pole modular type ‘C’ curve MCB of capacity 20 Amps (1 Module) & 20 Amps 3 pin Module socket (2 module) including 20 A plug top and electrical connection all as specified and directed. |
| 34 | M&L Bituminous premixed semi dencse asphaltic 30 mm thick (consolidated thickness) with 5.5 % binder content by wt of total mix paving bitumen(VG-30) viscocity grade mixed in hot mix plant transported to site on tippers and laid with mechanical paver, and rolled to uniform smoothsuface with 8 to 12 tonne capacity power roller and compacted to required camber and gradient and all directed and specified by Engineer-in-charge.Note :-(i)The mix design shall be got done from approved lab and got approved from AGE(I) before commencement of work.(ii)In the event of variation in the mix design in the percentage of binder content on minus side, the difference in quantity of binder content will be adjusted through supply only rate at market rate or procurment rate whichever is more paving bitumen VG-30.However no adjustment shall be applicable if excess quantity of binder content is used/approved in the execution of work under this item. |
| 35 | S&F for sign baord of size 1800x1200 mm made on 2mm thck Alluminium sheeet.The bard shall be covered using 3M India type IV retro reflective sheet of Blue colou, the letter on it shall be of white colour.The board shall be suppoprted by 32mm bore stainless steel round pip and 25x12 mm tupbular pipe.The pipe of size 3600mm each including cutting or gun welding, polishing, buffing complete with necessary holes, nuts and bolts, caps and anchor plates of SS grade 304 ASTM as per drawing and instructions of Eng-in-Charge including cost of RCC/PCC earth work with S&F of type IX retro reflective sheeing as per ASTM-D-4956-07 in two layers of approved colur over ACM/Aluminum sheet complete with adhesive and pressure method and providing cutting hoisting and fixing in position including fabrication of 3mm ACM made of two aluminum sheet of 25mm thick each having a distance of 2.5 mm filled with rubber polymer including provision of block of size 60 cm x 60 cm x 120 cm made of PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) cast in situ at each legs for fixing sign board including necessary earth work complete all as specified and directed |
| 36 | Supply & installation, testing and commissioning of 5 MVA, 33/11 KV, 3 Phase, 50 Hz, ONAN Cooled, oil immersed, copper wound outdoor type step down Power Transformer with 9 position ON LOAD Tap Changer (OLTC) (tapping range +5% to -15% in steps of 2.5% each) with remote tap cubical changer (RTCC) panel & automatic Voltage regulator (AVR) complete with first filling of IS: 335 ISI marked filtered & dehydrated transformer oil and other standard fittings / accessories like HV Bare bushing, LV Cable box, Buchholz Relay, OTI, WTI, Marshelling Box etc andwith vector group Dyn-11 including PCC foundation for placing transformer as per manufacturer instruction/drawing complete all as specified and confirming to IS: 2026 or latest IS specification for higher efficiency and manufacturer shall hold license/certificate from BIS to this effect. Note: The transformer will have its initial oil filling to appropriate level and confirming to relevant IS and tested up to 60 KV die electric strength (cost of oil including testing with desired dielectric strength deem to be included in quoted rates) |
| 37 | (a) Three nos porcelain bushing suitable for 33 KV on HV side complete with copper rods, nuts and washers and arching horns.(b) One cable box LV side (Secondary side) consisting of threeNos porcelain with copper bushing rods complete with nuts and washers with two Nos cable gland suitable for reception / taking out of PVC /XLPE insulated heavy duty HT armoured cables including gland, joint and jointing materials complete.(c) Oil conservator with filter type drain valve and oil level gauge.(d) Dehydrating breather with first fill of dehydrating agent. (Silica gel)(e) Explosion vents.(f) Thermometer pocket on tank cover. |
| 38 | (g) One No. 100 mm dia, dial type thermometer, vapour pressure type having range 0-120 degree Celsius with metal guard having maximum perimeter reading temperature indicator with resisting device for transformer. (h) Two earthing terminals on tank cover to facilitate fixing of 32 X 6 mm galvanized iron earth strip for earthing of neutral & body. (j) Rating plate and terminal marking plate.(k) Oil level gauge.(l) Oil drain filler valve.(m) Lifting lugs.(n) Oil filling hole with cap / plug with connecting plate complete. (o) Air release valve plug. (p) Four plain solid cast steel detachable rollers. (q) Extra bushing for neutral, outside the LT Cable box for providing independent earthing for neutral. |
| 39 | (r) First filling of new and unused transformer oil IS-335/93 (fourth revision) marked filtered and tested upto 60KV dielectric strength at 2.5 mm air gap between testing electrodes.(s) One danger notice board having conventional danger sign of skull with bones in painted in red colour. (t) Buchholz relay (having contacts for alarm & trip).Note I :- Certification of electric strength shall be submitted by the contractor, after filling the oil. Note II :- Including all control wiring with copper conductor multi core of suitable size (Transformer to control panel in MRS bldg) |
| 40 | Supply, installation, testing and commissioning of 2500 KVA Distribution Transformer, 11/0.433 KV, 3 phase4 wire, 50 HZ, double copper wound outdoor type step down transformer, oil immeresed naturally cooled (ONAN) with externally cooling tubes laminated core type delta connected on primary HV side and star connected on secondary LV side in accordance with vector symbol DYN-11 (vector group 4) with brought on secondary LV side for earthing and having tapping on HTside upto +7.5% in step of +2.5% and impedence 4.5% complete with first filling of IS: 335 ISI marked filtered & dehydrated transformer oil and 9 position on load tap changer (OLTC) (tapping range +10% in steps of 2.5% each) with remote tap cubical changer (RTCC) panel & automatic voltage regulator (AVR) with vector group DYN-11. The transformer shall be complete with standard fittings and accessories like Buchholze relay, conservator tank, explosion vent, air breather, thermometer & in/out gate valves, oil level indicator with a minimum level switch, pressure relief valve, lifting gear/lugs, drain valve, and a filter/strainer valve with a blanking plate/plug etc including PCC Foundation for Transformer as per manufacturer instruction/drawing complete all as specified and confirming to IS:1180 or latest IS specification for high energy efficiency (minimum BEE level-II or higher) and manufacturer shall hold license/certificate from BIS to this effect.Note: The transformer will have its initial oil filling to appropriate level and confirming to relevant IS and tested up to 60 KV die electric strength (cost of oil including testing with desired dielectric strength deem to be included in quoted rates) |
| 41 | Supply & fixingDO fuse assembly, triple pole mounted on porcelain HT insulator 6 Nos and MS galvanised steel frame rating upto 200 Amp, 11000 Volt, post insulator type on channel (two insulator for one phase) complete with expulsion type fiberglass fuse carrier barral type and including DO fuse and electrical connections complete all as specified and directed. |
| 42 | Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 630Amp, 26.3kA/3-sec, comprising of01 INCOMING CUM OUTGOING VCB Panelsconfirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 630Amp, continuous rated Copperbusbars and droppers, 02 Nos. Rack-In-Rack-Out Handles, structure made from AluZinc/CRCA sheets to prevent corrosion and rusting.The complete panel including HT and LT chamber with FRLS wiring shall be manufactured by approved OEM at its own facility, and same will be verified via stage/final inspection. The Board shall consist of following panels:- |
| 43 | (i) 11kV, 630Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of cir-cuit breaker, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (110VDC).(ii) Current Transformers 11kV, 300-150/1-1-1, Core1: Class 5P10, 2.5VA, Core2: Class 0.5, 2.5VA, Core3: Class PS-X - Set of 03 Nos. The \"PS\" core will be of suitable knee point voltage and ratio so as to successfully implement Transformer Differential protection scheme for the upstream existing power transformer.(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - Set of 03 Nos. |
| 44 | (iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+04PT Inputs with microprocessor based protection scheme for tripping the breaker on vari-ous faults like (a) Directional over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensingThe relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs.Relay setting should be possible through inbuilt software or through addtional software supplied by the relay manufacturer. Make of the relay shall be same as make of switchgear panels. |
| 45 | (v) Metering Equipment including:-(a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01 No Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring cur-rent, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on Mod Bus via RS485 port. |
| 46 | (vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button(d) Trip Circuit Healthy |
| 47 | (vii) 06-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip(c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) PT Fuse FailureThe Annunciator will be complete with required Acknowledge/Test buttons as required |
| 48 | (viii) Control Equipment incl. :-(a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC(e) MCBs for DC(f) Heater Switch with Thermostat - 01no.(g) 3-pin socket with ON/OFF switch - 01no.(h) CFL/LED Lamp with ON/OFF switch - 01no. |
| 49 | (ix) Flush mounted Auxillary Protection Relays including:-(a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay.(d) DC Supervision Scheme |
| 50 | (x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel with Transformer differential relay situated in the 33kV CRP for achieving the required protection. |
| 51 | The panel shall be complete with all allied items and accessories, including:-(i) Cost of construction of foundation as per manufacturer design, including foundation frame (sup-plied by OEM), channels etc. for HT Panel as required at site are deemed to be included in the quoted rate.Note:- (i) License parter, system integrator, panel builder, half-panel is not allowed for 11kVVCB Panel. All works shall be done at OEM own works. (ii) All items will be transported in wooden packaging to avoid any damage. Acceptance of material will be discretion of GE. Contractor has to remove the material in case of rejection of material at no extra cost.(iii) Factory acceptance test shall be carried out for11 KV HT VCBPanels. |
| 52 | Supply & installation of control cable copper 4 pair 4.0 sqmm, PVC insulated and PVC Round Sheathed, Multicore Annealed Bare Copper Conductor (flexible) industrial cable for Voltage Grade 1100 Volt complete all as specified & directed |
| 53 | Supply & installation of control cable copper 10 pair 4.0 sqmm, PVC insulated and PVC Round Sheathed, Multicore Annealed Bare Copper Conductor (flexible) industrial cable for Voltage Grade 1100 Volt complete all as specified & directed |
| 54 | Supplying , installation, testing and commissioning of 11 KV, 630 Amps having short circuit capacity 21kA/3-sec, Outdoor (IP54), RMU (Ring main unit) 5-way comprising of 05 Nos 630 Amp Fixed-Type motorized spring-charging VCBelectrolytic grade copper busbars all inside single, gas-filled, robotically welded stainless steel 304 (Non Ferrite Non Megnetic Grade) tank with min. thickness 3+0.5 mm, IP 67 Degree of Protection , internal-arc classified 21kA/1sec, on-site-repairable with site replacable bushing/coupling/mechanism, gas refilling etc. The enclosure shall have padlockable double-door access with anti-theft higes, fully covering the front facia and cable boxes to ensure fail-safe anti-theft protection. The unit alongwith Bus-connected, fixed-type potential transformer shall include the following along with all necessary accessories and fittings as required at site. |
| 55 | (A)02 Nos incoming VCB module and 03 Nos outgoing VCB module eachconsisting of following accessories :- (i)Each function-unit consists of a vacuum-circuit breaker in combination with a three position-switch.The three-position-switch fulfills the operation of the disconnector-function and earthing function. (ii)12kV, 630A Fixed-Type VCB module with series disconnector cum earthing switch of short circuit breaking current/withstand - 21kA/3-sec, Making Capacity - 50kAp-01 No(iii)Aux. contacts - 1NO+1NC-01 No(iv)Stored-energy motorized high-endurance spring charging mechanism (M1+), with inbuilt spring-charging lever and mechanically latched ON/OFF push-buttons to allow handle-less and un-inhibited operation -01 No (v)Cable terminals (site replacable Cable bushings situated not beyond 300mm from cable-cover to allow ease of access for installation/testing/replacement purposes) with double-door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access upto 11 KV , 120 Sqmm , 3 Core, XLPE AL cable termination in live-condition. Each Set of Three (vi) Right angle boots (push on type)-Each set of Three (vii) 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. Relay should have facility to display the maximum loaded phase current also.Relay shall record minimum 5 fault records with time stamping.Relay shall be communicable with RS 485 Port on MODBUS Protocol-01 No(viii) Associated ring-core cast-resin insulated CTs 100-50/1 Amp , 2.5 VA, 10P10 for protection - Each Set of Three(viii) Associated ring-core cast-resin insulated CTs 100-50/1 Amp , 2.5 VA, 10P10 for metering - Each Set of Three(ix) Arc proof cable covers with self Interlocking mechanism with earth switch -01 No(x)Capacitive voltage indication fixed type system as per IEC61243 with LED -01 No(xi) Push button for breaker trip (xii) Shunt trip coil 24V DC - 01(xiii)ON, OFF, TRIP mechanical indication on the front mimic of the panel - 01. (xiv) Emergency Trip Push Button - 01. (xv) Multifunction Meter - 1 No |
| 56 | (B)03 No. Bus-connected, fixed-type Auxiliary transformer accomodated in separate compartment of matching height and depth, positioned along-side or top ofRMU for metering consisting of following accessories :- (i)Voltage transformer of the ratio 11kV/√3/110V/√3, 25VA Class 1.0 with HT fuses on primary side and MCB on secondary. (ii)2x12 Volt DC battery-01 Set (iii) Battery charger-01 No (iv) HRC fuse-links for primary side isolation and AC/DC MCBs for secondary isolation-01 Set (v) Anti-condensation space-heater-01 No (vi)CFL lamp for illumination and 3-pin socket with switch -01 No |
| 57 | (C) Additional equipment deliverd separately or mounted seperately :- (i)Operationg Handle for Manual Isolator/Disconnector/Earthing Operation-02 Nos(ii) Standard Manometer -01 No (iii) Operation and Maintenance Manual -01 No (iv) Installation & Commissioning Manual -01 No (v) Cable clamping provision (standard) -01No |
| 58 | NOTES:- (i) It is preferable to have all feeder-switches inside single stainless steel compartment with incomer feeders at the extremities to prevent chances of failure due to plug-in coupling arrangement. (ii) Necessay interclocking arrangement shall be provided for safety and operations(iii) Above switchgear shall confirm to relevant IEC (62271-200) for design, manufacturing and internal arc compliance. Any claims towards internal arc compliance, number of mechanical/electrical/short-circuit operations, gas-leakage rates etc. shall not be accepted unless proven via type-test reports of model being offered.(iv) Cost of construction of foundation including construction material, necessary earth work and excavatonas per manufacturer design forRMU completeall as required at site and as directed and deemed to be included in the quoted rate. |
| 59 | Supply and installation 33 KV single phase out door oil cooledCT of ratio 150-100/1-1 Amp class 1.0 – 5P10 burden 15 VA insulation level 70 KV/170 KV as per IS-2705 complete all as specified and directed. |
| 60 | Supply and installation 33 KV single phase out door oil cooled PTof ratio 33 KV/rt 3/110V/rt10V/rt 3Class 0.5-3, Burden 50 VA – 50 VA, insulation level 70/170 KV., voltage factor 1.2 Cont and 1.9 for 30 Sec, conforming to IS-3156 complete all as specified and directed. |
| 61 | M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed.Note: If any damages/loss to existing service such as OFC cable/Water pipe line/Electric cables etc shall be repaired immediately by the contractor. Rate quoted above deemed to be inclusive of the same. |
| 62 | Supply, installation, testing and commissioning ofHT out door type feeder pillar box (factory made and CPRI Type Tested ), floor mounted, cubical enclosed type, made out from 3.15 mm thick CRCA sheet, of minimum size 1.0x0.9x0.8 m with two part front operated hinged doors, canopy type roof, weather and vermin proof, one closed HT bus bar chamber having 3 phase aluminium bus bar of size 50 x 10 mm, 15 KA short circuit rating for one second, one GI earth bus fixed out side the bus bar chamber, two nos cable gland suitable for 150 sqmm 3.0 core HT XLPE cable with and including HT danger notice board on both sides, frame made out of ISA 50 mm x 50 mm x 6mm with cable entry & exit through socket at bottom (Fixed with cable glands and gasket) for maintaining specific bendingradius of cable including providing two coat of powder coated paint to out side surface and two coat of synthetic enamel paint over a coat of red oxide primer to inside surface and necessary foundation/platform of the HT Feeder pillar box with PCC (1:2:4) type B1 (using 20 mm grade stone aggregate) complete all as specified and as directed complete all as specified and as directed. |
| 63 | Supply, install, testing and commissining Back up power supply with30 Volt DC low maintainance type chargable battery of 15 cells of 02 Volts, 100 Amp hour each s including battery chargerset and control equipment of suitable sizein sheet steel cabinate of 02 mm thick floor mounted typefor input 230 volts (+ ) (-) 5%single phase 50 Hz AC complete for 33 KV&11 KV VCB pannel with compltete control wiring for connecting the DC triping system to realys wiring shall be copper conducter of single core and size not less than 2.5 Sqmm runinginPVC conduit complete all as specified and directed |
| 64 | S&F HT 11 KV insulation electrical rubber mat 1m x 2m x 10 mm thickness as per IS: 15652:2006 Class A complete all as specified and as directed |
| 65 | Supply , Installation , comissioning and testing of CPRI approved type LT panel board cubical type of the minimum size (2250MM x 1800MM x 800MM) , outdoor type 415 Volts ,50 Hz , 3 phase, 4 wire supply floor mounted , factory made , dust and vermin proof ( protection class IP-54) made out of 50mm X 50mm X6mm angle iron frame and 3.15 mm thick MS CRCA sheet with front hinged opening double door , rubber lining , locking arrangement ,powder coating painting of siemens grey shade ( RAL -7032) on all steel surfaces. The cubical shall have a bottom channel of size 100MMx50MM duly coated with Zinc metal coating. A detachable predrilled gland plate at the bottom complete comprising of following:04 Nos copper bus bar 6000 Amps capacity for phase & neutral duly supported on suitable size of epoxy insulators fixed in dust and vermin proof MS enclosure having adequate clearance between conductors and earth for easy maintenance . These should have colour coding for RYB and neutral to enable immediate identification . All the incoming connections to ACB/ MCCBs shall be made with suitable size Copper strip . (a) Incoming :(i) ACB 4 pole , 415 Volts , AC supply , 4000 Amps , Manually operated drawout type, 50 KA breaking capacity-01 No .(b) Outgoing :(i) Provision for connection and termination of copper bus bar of suitable size having 4000 A capacity (ii) MCCB 4 pole ,415 volts , AC supply , 400 Amps, 36 KA breaking capacity Ics=Icu at 415 volt AC , 50 Hz with microprocessor release with spreader link on both side-01 Nos (iii) Provision of cable entrance space with suitable metallic cable gland alongwith gland plate for entry of 08 Nos 400 sqmm 3.5 core aluminium cable. |
| 66 | (c) LED multifunction Meter -01 No.(d) LED indicating lamp ( RYB) -03 Nos |
| 67 | Supply , Installation , comissioning and testing of LT panel board CPRI type tested of suitable size and shape, indoor cubical type (415 Volts ,50 Hz , 3 phase, 4 wire supply ) floor block mounted , factory made , dust and vermin proof ( protection class IP-54) made out of 50mm X 50mm X6mm angle iron frame and 3.15 mm thick MS CRCA sheet with front & rear double door hinged opening , rubber lining , locking arrangement,powder coated paint of approved shade simens grey ( RAL -7032) on all steel surfaces. The cubical shall have a bottom channel of size 75 x 40 mm duly coated with zinc metal coating , a detachable predrilled gland plate at the bottom complete all as specified and directed including PCC foundation as per manufaturer instructions complete comprising of following:03 Nos aluminium bus bar 800 Amps capacity for phase , 01 No aluminium bus bar 630 Amps capacity for neutral duly supported on suitable size of epoxy insulators fixed in dust and vermin proof MS enclosure having adequate clearance between conductors and earth for easy maintenance . These should have colour coding for RYB and neutral to enable immediate identification . All the incoming connections to MCCBs shall be made with suitable size tinned aluminium bus bar of rating 800 Amps . (a) Incoming : MCCB 400 Amp, 4 pole , 415 Volts , AC supply, 36 KA breaking capacity Ics=Icu at 415 volt AC , 50 Hz with microprocessor release -01 No (b) Outgoing : MCCB 315 Amps, 4 pole , 415 volts , AC supply, 36 KA breaking capacity Ics=Icu at 415 volt AC , 50 Hz with thermal magnetic release -02 Nos (c) Voltmeter digital type 3 phases AC , 0-500 volt incl selector switch for reading all 3 phase -01 No forincomer & 02 Nos for outgoing.(d) Ampere metre digital type 3 phase AC , 0-800 Amps with suitable CTs incl selector switch for reading all three phase -01 No forincomer & 02 Nos for outgoing.(e) Phase indicating LED lamp with holder 230 Volts for all 3 phases ( RYB) -03 Nos(Make : PSC/Shalabh/Sparsh/Prestige or equivalent as approved by AGE (I)) |
| 68 | M&Lfor earthing complete with galvanised steel earth plate electrode 600x600x6.00 mm thick, burried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal/coke and common saltupto 0.90 meter depth all around the earth plate and connected to earth leadof GI strip 25x4 mm by means of bolts, nuts, check nuts and washers of GI or steel and thimbles and other end of the earth wire connected to equipments/panels and protected by galvanized iron or steel pipe medium grade 40 mm bore and water pipe 20 mm bore GI light grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of2009 and also including making test point for testing of earthingcomplete all as specified and as directed. Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 50mm thick reinforced with XPM weighting not less than 4 KG/sqmmin lieu of CI cover.2. Charcoal/coke and commonsaltupto 0.90 meter depth shall be filled in layers of 15 centimeters all around the earth plate. 3.On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values. |
| 69 | M&L for earthing complete with galvanised steel plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mts deep below ground level with top edge of the plate not less than 1.50 Mtrs below ground level connected to glavanised iron Wire 4.0 mm dia by means of bolts, nuts check nuts and washers of galvanised iron or steelconnected to earthing test point all as specified incl 15 mm GI tubing medium grade and necessary fitting for protection of GI wire incl laying of charcoal dust and common salt in alternate layer, PCC Pit (1:3:6) type C-1 using 20 mm graded stone aggregate, RCC cover 40mm thick (1:2:4) type B-0 using 12.5mm graded stone aggregate reinforced with 6 mm dia round bar @ 75mm C/C both ways with MS handle 8mm dia, plastering 15mm thick CM (1:6) externally upto 150mm below ground level , GI funnel with 20mm dia medium grade GI pipe for watering and wire mesh incl excavation and earth work and disposal of surplus soil complete all as specified and shown on electrical plate No 3 of SSR Part (2009) and connected to earth test point incl testing and marking Bldg Nos and writing Test Results on a 3.0mm thick painted M.S. earth pit marking Plate (200mm x 100mm) duly welded with a 450mm long 10mm dia round M.S. rod, fixed with the earth pit chamber by grouting complete including taking out old unserviceable earthing system including demolishing with old earth pit chambers and removing of debris from the site with levelling the ground all as specified an directed. |
| 70 | M&Lfor earthing complete with Copper earth plate electrode 600x600x3.15 mm thick, burried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal/coke and common saltupto 0.90 meter depth all around the earth plate and connected to earth leadof copper strip 32x6 mm by means of bolts, nuts, check nuts and washers of GI or steel and thimbles and other end of the earth wire connected to equipments/panels and protected by galvanized iron or steel pipe medium grade 50 mm bore and water pipe 20 mm bore GI light grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of2009 and also including making test point for testing of earthingcomplete all as specified and as directed. Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 50mm thick reinforced with XPM weighting not less than 4 KG/sqmmin lieu of CI cover.2. Charcoal/coke and commonsaltupto 0.90 meter depth shall be filled in layers of 15 centimeters all around the earth plate. 3.On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values. |
| 71 | Supplying & laying burnt clay bricks, sub class \"B\", designation 75,old size laid in trenches over cable protection complete all as specified and directed. |
| 72 | S&F 7 meter long hot dipped galvanized octagonal poles with top at 70mm Bottom at 130mm, made out of 3 mm Thick HT sheet along with base plate of size 220 x 220 x 12 mir, including up to 1500mm long single arms, bracket made out of 48mm dia, Gi pipe, M20 in PCD 205mm, 700mm long and projected 100 \"J\" Type EN8 grade set of 04 Nos Foundation bolts alongwith templates, also including provision of the following : -(a) MCB SP 6A,230 V \"B\" series, 10 KA-01 No. (b) 4 Way DMC connector, bolt type having locking arrangement, weather proof and water proof control space -01 No.Notes :-(a) The rate quoted shall also be deemed to include the cost for provision of 50mim bore PVC pipe from cable trench to center of the pole concrete.(b) The concrete for foundation, Reinferced and formwork will be included in above quoted rates.(c) The excavation and earth work for foundation of pole shall be measured and paic separately as approved by the AGE (l).\" complete all as specified and directed. |
| 73 | M & L for cable route indicator for 11000 Volts grade cable with 150 mm dia cast iron plate circular or rectangular in shape of minimum 8 mm thickness welded with 35x35x4 mm angle iron mast 0.5 mtr from the GL including PCC foundation 1:3:6 type C1 of size 30x30x45 cm and necessary earth work all as directed. |
| 74 | Supply & Insatllation of Sandwich type 4 Pole Bus bar trunkingfor interconnection between Transformer and LT Panel, of 433 Volt (3Ph 4W system) of Copper Busbars, of capacity 6000A/50KA SC for 1 sec, with 50% integral G.I. housing as earth,Bend Provision, Flange End Provision, Adoptor Box and Copper Flexible, Bus Trunking enclosure shall be suitable in dimension duly supported at regular intervals on insulators made of high dielectric strength totally enclosed in bus duct of made of 1.6mm thick G.I. sheet,IP66 with Canopy Outdoor,& multi layer insulation of Class-F, Temperature rise as per IEC 61439 – 1&6. with 2 nos of external Copper earthing of size 50x6mm shall be run on both sides and throughout the length of bus duct and all metallic noncurrent carrying parts shall be connected to it complete all as specified and directed. |
| 75 | Taking down old serviceable 33/11 KV 2000 KVA capacity Power transformer from plinth MRS marshelling yard after disconnection of all power/control cables and shifhting from AGE (I) AF Memaura to GE (AF) Bareilly including loading & unloading by necessary T&P complete all as specified and directed.(Note : Damage to transformer during transit will not be accepted, if any damage caused, then it will be rectified by contractor on his own expense) |
| 76 | Taking down old serviceable 33 KV CT & PT assembley from MRS marshelling yard after disconnection of all power/control cables and shifhting from AGE (I) AF Memaura to GE (AF) Bareilly including loading & unloading by necessary T&P complete all as specified and directed.(Note : Damage to CT/PT during transit will not be accepted, if any damage caused, then it will be rectified by contractor on his own expense) |
| 77 | S&F for LLDPE based underground packaged type septic tank of capacity 6000 Litrs polyethylene tank. First zone is septic zone where sledge is stabilized by anaerobic digesion. Second zone is pall ring media zone having surface area of 190 Sq. ft/Cum and retain micro-organissum long enough to digest the organic waste which result in 70% of BOD reduction from final out let. It is provided with inlet & outlet pipe of 100 mm dia vent pipe of 50mm dia, internal piping, manhole cover of 400mm dia & bar section, placed over and including 150mm thick PCC bed in PCC 1:4:8 type D-2 using 40mm graded stone aggregate for base with 150mm projection from outer dia of tank all around including necessary earthwork i.e. excavation in soft/loose soil and removal from site upto a distance of 1.5 km and including sand filling in excavated pit after erection of tank and pipe connections complete all as specified and directed. |
| 78 | M &L for Construction of soakage well for 1.8m dia(internal Dia) and 3m effective depth including neccesary excavation iin earth work in any type of soil, plain cement concrete 1:3:6 type C-2(using 40mm graded crushed stone aggregate) as in foundation, brick work in cement mortar 1:4 in walls & honey combed brick wall, reinforced cement concrete M-25 (design mix) asin slab cover including pre cast cover sla having 8mm dia TMT bar reinforced, plain cement concrete band , form work to sides and soffits of RCC slab & filling with brick bats loose filling complete all as specified and shown in drawings. |
| 79 | Supply, stretch and fix concertina coil 750mm dia in stress position hot deep galvanised steel wire coated with CLR anti corrosive paints making diamond shape with the help of dove tail clips (18 SWG), the concertina coil is to be fixed with barbed wire at points where coil touched the bottom barbed wire with the help of lug rings (24 SWG) including all fittings like fastener clips, steel lug rings etc complete all as shown in drg all as specified and directed. Note: (i)Stretch length of each coil shall be 6 mtr. (ii)weight of each coil shall not be less than 9kg complete all as specified and directed |
| 80 | Supply and fix flush mounted VTPN DBs, 415 volt IP - 43 protection IK-09 with metal double door with 200 Amp copper bus bar with 2 neutral bar, earth bar and cables management fully insulated bus bar with set of wire and door earthing with provision of space of 100 amps MCCB as incomer and SP/TP MCCBs as outgoing 4 way complete all as specified and as directed. Note MCB and MCCB shall be measured and paid separately |
| 81 | Supply & fix LED security light 25watt IP - 65 having pressure dia cast aluminum housing with heat resistant toughened glass, 4kV internal and 10kV external surge protection, min 100 Im/watt, colour Temperature 6000 to 6500 K,PF>0.95,CRI>75, and THD<10,230 volts AC 50Hz internal wiring with bracket and suitable for mounted on floor complete all as specified and directed. |
| 82 | S&F RJ 11 Tele Jack single with shutter 1 module complete with GI box and front cove all as specified |
| 83 | S&F TV socket Jack single with shutter 1 module complete with GI box and front cove all as specified |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
| 7 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail